
15
• Terminal4=Hispeed
• Terminal5=Medspeed
• Terminal6=Lowspeed
4.Replace the upper door and secure it to the unit.
5.Restore power to the unit.
High Efficiency Units (Variable & Fixed Speed)
IMPORTANT! This air handler has been designed to
give the installer maximum flexibility to optimize system
performance, efficiency, and comfort. Because there
are so many different ways to set up the air handler it is
important to read and follow these directions carefully.
B6EM&B6VMairhandlersusehighefficiencycirculating
air motors that come in two variations and both are
controlleddifferently.Thefixedspeedmotorcontrolboard
(Figure 15, page 23) controls the torque and the variable
speedmotorcontrolboard(Figure16)controlstheairflowat
aconstantCFM.Bothboardsusethesamecontrolboard.
Before operation, the air handler must be configured to
matchtheunitwiththesystem,systemoptions,andclimatic
conditions. When configured, the air handler responds
directly to the thermostat inputs, as well as the optional
humidistat (see page 13). During normal operation, the
motor will gradually change speeds during start-up, shut
down,whenthermostatinputschange,andwhentheduct
static pressure changes (vents closed or opened, filter
clogging, etc.). The air handler is configured by setting
the selector switches and removing jumper connectors.
Selecting Basic Heating Airflow
Fixed & variable speed motor control boards (Figures
15 & 16) contain a set of dip switches for setting the
blower speed.For B6EM models, pins 1-4 set the speed
for heating. For B6VM models, the A/B switch must be
set for the appropriate cabinet size (either setting can be
used for C-size cabinets).The airflow is set automatically
based on the amount of installed heat.For both B6EM &
B6VMmodels,thecoolingspeed isselectedviaswitches
5,6,7,&8.Todeterminetheappropriateswitchsettingsfor
your installation, seeTables 6, 7, 8, or 9 (pages 20 - 22).
Selecting Basic Cooling / Heat Pump Airflow
Thebasiccooling/heat-pumpairflowiscontrolledbysetting
switches5-8onthemotorcontrolboard(mountedonthe
blower).All airflows for other modes of operation (except
electric heat) are determined by this basic setting. FAN
ONLY would deliver 50% of the selected cooling airflow.
Table 8 (page 20) lists the basic airflow values versus the
airflowselectorswitchsettingsandrangesofbasicairflow
settingsrecommendedforeachnominalsystemcapacity.
• When operating in the heat pump mode, a higher
basic airflow setting will increase the energy efficiency
and capacity but will also decrease the supply air
temperature.
• Formaximumcapacityandenergyefficiency,selectan
airflow at or near the top of the range for that nominal
capacity. See Table 8 (page 21).
• Formaximumdehumidication,selectanairownearthe
middle or bottom of the range for that nominal capacity.
Additionalinformationonhumiditycontrolcanbefound
in the Humidistat and Delay Setting sections.
• Forthermostatswithadehumidieroutput,useaeld
supplied wire to connect the thermostat’s dehumidifier
output to the terminal marked DHUM.The thermostat
should be set so that the DHUM output should be high
(energized)whendehumidification isneeded.See also
Dehumidification Options section.
IMPORTANT! If coil icing is observed, the basic cooling/
heat-pump airflow selected may be too low. Verify the
setting selected is within the range shown inTable 8 and
thatthethesystemisproperlycharged.Pleaserefertothe
instructionssuppliedwiththeoutdoorunit.Ificingcontinues
to occur, raise the selected airflow one or two steps.
NOTE: Variable speed air handlers with SEER ratings
higherthan15arematchedwitha2-stagecoolingoutdoor
unit. They are programmed to operate at 75% of the
selected airflow while the system is in the lo-cool mode
and 100% of the selected airflow while in hi-cool mode.
Dehumidification Options
(B6EM or B6VM Models Only)
Both motor control boards (Figures 15 & 16, page 23)
have a DHUM connection that allows the system to
increase the amount of humidity that is removed from
the circulating air. This is accomplished by reducing the
CFM and allowing the cooling coil to become colder.This
will only occur when there is a call for cooling.There are
many ways that this can be electrically wired.
1.If the room thermostat incorporates a humidity sensor
andDHUMoutput,connecttheDHUMonthethermostat
to the DHUM terminal on the motor control board.
2.If using a separate humidistat, connect the DHUM & R
terminals on the humidistattotheDHUM & Rterminals
on the motor control board of the air handler. In this
option, the DHUM output of the humidistat must be set
to be normally open and closed when there is a call for
humidification. See Figure 10.
3.Ifahumidistatisnotavailable,itisanacceptableoption
to connect the R& DHUM terminals on the motor
control board together with a field supplied wire.This
option causes the blower to run at a reduced CFM for
10 minutes after a call for cooling. NOTE: If outdoor
unit is a heat pump, connect the Oterminal to DHUM.
DHUM
RR
DHUM
HUMIDISTAT
MOTOR
CONTROL BOARD
Figure 10. DHUM Wiring Configuration