Nortek Linear eMerge e3 Series User manual

PRINTER’S INSTRUCTIONS:
MANUAL,INSTALLATION,E3 EMERGE,UL - P/N: 620-100531 B - INK: BLACK - MATERIAL: GUTS 80G WOOD FREE, COVER 157G COATED GLOSS ART
SIZE: FLAT 17.000” X 11.000”, FOLDED 8.500” X 11.000” - FOLDING: ALBUM FOLD - BINDING: SADDLE STITCH - SCALE: 1-1
e3 eMerge
Access Control System
Document Number: 620-100531, Rev. B
Installation Instructions

Notices
All rights strictly reserved. No part of this document may be reproduced, copied, adapted, or
transmitted in any form or by any means without written permission from Nortek Security &
Control LLC.
Standards Approvals
This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection
against harmful interference when the equipment is operated in a commercial environment.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his own expense.
e3 eMerge systems are Level I UL 294 listed devices and must be installed in controlled locations.
Corporate Office
Nortek Security & Control LLC
1950 Camino Vida Roble, Suite 150
Carlsbad, CA 92008-6517
Tel: (800) 421-1587 / 760-438-7000
Fax: (800) 468-1340 / 760-931-1340
Technical Support
Tel: (800) 421-1587
Hours: 5:00 AM to 4:30 PM Pacific Time, Monday - Friday
Notice
It is important that this instruction manual be read and understood completely before installation
or operation is attempted. It is intended that the installation of this unit will be performed only
by persons trained and qualified in the installation of access control equipment. The important
safeguards and instructions in this manual cannot cover all possible conditions and situations
which may occur during installation and use. It must be understood that common sense and
caution must be exercised by the person(s) installing, maintaining and operating the equipment.
This installation manual is for e3 eMerge systems.

www.linearcorp.com 1e3 eMerge Installation Instructions
Contents
1.0 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
1.1 Access Control Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.2 System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3 Installation Overview Checklist. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.0 Control Panel Layout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.1 Control Panel Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.0 Installing the Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
3.1 Mounting the Compact Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.2 Mounting the Metal Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.0 System Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
4.1 Power Connection for Systems using Compact Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.2 Power Connection for Systems using Metal Enclosure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
4.3 PoE Connection (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.0 Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.1 System Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.2 Wiring the Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.3 System Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.4 Door Lock Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.0 Readers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.1 Wiring the Readers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
7.0 Network Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
7.1 Preparing for the Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
7.2 Connecting to the Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
7.3 Adding a Client. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
7.4 Configuring the Client and Server on the Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
7.5 Programming the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
8.0 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
9.0 Test, Maintenance and Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
9.1 Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
9.2 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
9.3 Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
9.4 Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
10. Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

www.linearcorp.com 2e3 eMerge Installation Instructions
1.0 Introduction
is manual contains information regarding the basic installation, wiring and conguration of the
e3 eMerge browser-based access control systems. Systems are available in a space-ecient and
durable plastic housing or in a heavy-duty steel cabinet featuring a self-contained battery back-up
with a supervised power supply. All systems use the same control panel layout and system wiring.
1.1 Access Control Overview
Access control systems are designed to monitor and control access throughout a building or
restricted area. An access control system involves the use of an access device (card, PIN code,
etc.), which is presented at an entry device (reader/keypad) to gain access. When access is granted,
a door is unlocked for a pre-programmed amount of time and a transaction is recorded in a
database for reporting or tracking purposes.
1.2 System Overview
Systems are available in a variety of models starting with one door, two reader congurations.
Models can be upgraded with expanded capabilities using optional software license keys. e
e3 eMerge includes Ethernet support, an integrated web server and Power over Ethernet (PoE)
support.
Specifications
Processor Cortex 1GHz
On-board RAM 512MB DDR2 (333MHz)
Power Regulated 12VDC @ 2A
Operating system Embedded Linux
Transactions per second > 30
Plastic enclosure (W x H x D): 12.25 in x 11.1 in x 2.23 in
Steel enclosure (W x H x D) 17.75 in x 14.25 in x 6.5 in
Temperature specification -4°F to 120°F (-20°C to 50°C)

www.linearcorp.com 3e3 eMerge Installation Instructions
1.3 Installation Overview Checklist
e following list presents the steps required for successfully installing a system.
❒Mount the enclosure
❒Connect the readers
❒Wire the inputs and outputs
❒Connect power to the system
❒Obtain IP address and other TCP/IP information from network administrator
❒Congure the network settings for the system
❒Connect the system to a local area network (LAN)
❒(Optional) Add licenses for additional doors and readers
Note: The checklist
provides a logical
sequence for installing a
system.

www.linearcorp.com 4e3 eMerge Installation Instructions
2.0 Control Panel Layout
2.1 Control Panel Components
e following illustration shows the e3 control panel wiring and components.
Note: Wiring methods
shall be in accordance
with the National
Electrical Code/NPFA 70
and all local codes.
Note: The terminals
are designed to accept
12-22 AWG, solid or
stranded wire.
Note: To factory default
the system, press &
hold S1 for 20 seconds.
When released, the
system will start the
factory default process.
It is VERY important to
wait 2-3 minutes for a
solid blue LED (DL1)
before programming the
system. All user data will
be erased, including the
license key.
AUX RELAY 1
AUX RELAY 2
AUX RELAY 3
AUX RELAY 4
-
TAMPER
OUT READER
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
DOOR 1
DOOR 2
DOOR 3
DOOR 4
ETHERNET
TMP -
TMP +
FLT -
FLT +
-
+
PWR FAULT
Micro SD
SLOT
RESET
LED BANK
LAN LED
DL8
DL7
DL6
DL5
DL4
DL3
DL2
DL1
DL17
DL16
DL15
DL14
DL13
DL12
DL11
DL10
DL9
DL19
DL18
JP1
S2
S1
External
+12VDC
POE
(Default)
JP1 - Power Input
EARTH
GROUND &
READER
SHIELD LEAD
D0 IN
D1 IN
D0 OUT
D1 OUT
2
1
3
4
D9
S2: Hardware reset
S1: Factory default
+
12VDC
INPUT
GND
INPUT
12V
AUX IN
GND
AUX IN
INPUT
GND
INPUT
D0 IN
D1 IN
D0 OUT
D1 OUT
12V
REX
GND
DOOR
CONTACT
AUX INPUT 4
GND
AUX INPUT 3
IN READER
REX
GND
DOOR
CONTACT
OUT READER
IN READER
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
DOOR 2 LOCK
DOOR 1 LOCK
DOOR 3 LOCK
DOOR 4 LOCK
OUT READER
D0 IN
D1 IN
D0 OUT
D1 OUT
INPUT
GND
INPUT
12V
AUX IN
GND
AUX IN
INPUT
GND
INPUT
D0 IN
D1 IN
D0 OUT
D1 OUT
12V
REX
GND
DOOR
CONTACT
AUX INPUT 2
GND
AUX INPUT 1
IN READER
REX
GND
DOOR
CONTACT
OUT READER
IN READER
-
+-+
+-
+
-
Figure 2.1. Board Layout
Table 2.1: LED Indicators Table 2.2: Default I/O States
LED Condition
➀DL17 Red On = Power On Middle Board
➁D9 Red On = Power On Bottom Board
➂DL1 Blue On = System is Rebooted
DL1 to DL16 Blue On = System is Booting
➃DL19, DL18 Blue Blink = Network Connection
NOTE: System start up time is approx. 60 secs.
Attribute Default State
Door Status Inputs
Normally Open, Unsupervised, 8 Sec. Held Open Time
REX Inputs Normally Open, Momentary, Unsupervised
Auxiliary Inputs Normally Open, Unsupervised
Door Lock Outputs Not Energized, Single Pulse, 3 Second Unlock Time
Aux Outputs Not Energized, Single Pulse, 3 Seconds On
Note: For UL installations, the maximum Ethernet cable length is 30m (98.5 FT).

www.linearcorp.com 5e3 eMerge Installation Instructions
3.0 Installing the Control Panel
3.1 Mounting the Compact Enclosure
e housing is designed to accommodate the necessary wiring connections for most installations.
e compact enclosure is optimized to run wires under the back panel and thru the knockouts
shown in Figure 3.1 and Figure 3.2. e enclosure should be mounted vertically on a wall, in a
secure location within normal temperature and humidity levels.
Installing the Panel
1. Run all necessary wires to the panel location.
2. Remove the enclosure’s cover by removing the two screws in the front of the housing.
3. Level the enclosure on a sturdy wall. Mark the mounting holes with a pencil.
4. Partially insert screws into the top two mounting holes and hang the enclosure on the screws.
5. Pull all wires through the knock-out holes in the enclosure. Label each wire according to its use.
6. Recheck for level, insert the two lower screws, and tighten all four mounting screws.
Enclosure
Knockouts
Cover Screw
Cover Screw
Enclosure Knockouts
Mounting Hole
Cover
Tam p e r
EARTH
GROUND
& READER
SHIELD
LEAD
Wire Tie Down
Loops
Figure 3.1. Compact Enclosure
Note: The compact
enclosure will not
accommodate a backup
battery. If using a backup
battery, a separate
housing must be installed
or use PoE supply with
suitable UPS backup.
Note: The plastic
housing is not listed for
installations that require
UL 294.
Note: Tie down loops are
located in the enclosure
and used to provide
strain relief for field
connections.
Note: This device
complies with Part
15 of the FCC Rules.
Operation is subject
to the following two
conditions: (1) this device
may not cause harmful
interference, and (2) this
device must accept any
interference received,
including interference
that may cause
undesired operation.
Note: Choose a centrally
located, secure, clean
and dry area near an
AC power source. Avoid
mounting the panel within
6 feet of any equipment
that generates electrical
interference.
Caution: This equipment
includes electronic
components that are
highly sensitive to
static electricity. Please
discharge by touching
an earth ground before
installing or handling this
equipment.

www.linearcorp.com 6e3 eMerge Installation Instructions
Mounting Extensions
If running surface wires, 6 extension legs may be snapped onto the back of the enclosure to
provide additional space behind the enclosure for the wires.
Figure 3.2. Mounting Feet / Extensions for Compact Enclosure

www.linearcorp.com 7e3 eMerge Installation Instructions
3.2 Mounting the Metal Enclosure
e metal enclosure is designed to accommodate one or two 12VDC 7Ah backup batteries and
the necessary wiring connections for most installations. Conduit knock-outs are provided on all
sides of the enclosure. e enclosure should be mounted vertically on a wall in a secure location
within normal temperature levels. A minimum of 12 inches of space around all sides of the
enclosure is recommended.
Installing the Panel
1. Run all necessary wires to the panel location.
2. Remove the enclosure’s cover by unlocking the door and disconnecting the ground wire. e
door may be lifted out of the hinge slots.
3. Remove the metal cabinet knock-outs required for wire entry and install bushing or conduit
connectors as needed to protect wires from damage.
4. Level the enclosure on a sturdy wall. Mark the mounting holes with a pencil. (e cabinet
can be vertically or horizontally mounted depending on space requirements.)
5. Partially insert screws into the top two mounting holes and hang the enclosure on the screws.
6. Pull all wires through the knock-out holes in the enclosure. Label each wire according to its use.
7. Recheck for level, insert the two lower screws, and tighten all four mounting screws.
8. Re-install the door and connect the ground wire to the door.
Figure 3.3. Metal Enclosure
Note: Choose a centrally
located, secure, clean
and dry area near an
AC power source. Avoid
mounting the panel within
6 feet of any equipment
that generates electrical
interference.
Caution: This equipment
includes electronic
components that are
highly sensitive to
static electricity. Please
discharge by touching
an earth ground before
installing or handling this
equipment.
Note: Tie down loops are
located in the enclosure
and used to provide
strain relief for field
connections.
WireTie Down Loops
Mounting holes
Cabinet knockouts
Power Supervision
& Battery Charger
Module
Cover Tamper
EARTH
GROUND
& READER
SHIELD LEAD

www.linearcorp.com 8e3 eMerge Installation Instructions
4.0 System Power
e system panel requires a 12VDC, 2A supply (not included). For UL installations, a Linear
Plug in Power supply (PIP) is required (see below). e system may also be powered by a high
Power over Ethernet (PoE) injector using an optional Linear PoE module.
♦Linear 12VDC/24W (2A) PIP; P/N 0-291312RU
♦Linear 12VDC/60W (5A) PIP; P/N 0-299177RU (required for UL installations)
♦Linear e3 PoE module; P/N 620-100159 (requires additional high power PoE injector). PoE
is not supported for installations requiring UL294.
4.1 Power Connection for Systems using Compact
Enclosure
Power Supply Connection
1. Connect 12VDC from the included power supply to the +12V and GND input terminals
on the panel. Note: e3 eMerge systems require a 12VDC, 2 amp Class 2 power supply. Incorrect
voltage will damage the product and void the warranty.
2. Connect an earth ground to the green earth ground lead provided in the enclosure.
3. Turn on the power supply. If using a PIP for the power supply, it must be plugged into a
dedicated receptacle that is not controlled by a switch.
4. e power LEDs (DL17 and DL9) on the panel will turn on to indicate power is present.
Figure 4.1. Power Connection
Note: Wiring methods
shall be in accordance
with the National
Electrical Code/NPFA 70
and all local codes.
MINIMUM
Cable Specifications for
power: Use a minimum
of 16 AWG Belden (2
conductor) or equivalent.
Maximum distance: 6
feet (1.8 meters).
Note: For PoE
applications only use
UL294B listed PoE
power supplies.
Caution: A 12VDC power
supply MUST be used.
Incorrect voltage will
damage the product and
void the warranty.
Note: Power should only
be applied to the system
when all connections are
secured and tested.
TMP -
TMP +
FLT -
FLT +
–
+
Earth
GND
12 VDC
12 VDC
12 VDC
+–
1 2 3
12VDC/24W PIP 12VDC/60W PIP
Connection for Linear PIP
1 2 3 4
EARTH
GROUND &
READER
SHIELD LEAD
Earth
GND
+–
Note: A green wire pigtail for
earth ground is provided in all
enclosures
-
+
Use 60W
PIP for the UL
installations.
Note: A separate power supply MUST be
used for door locks and accessories. A power
supply shared between the system and door
locks and accessories may cause damage or
intermittent operation.

www.linearcorp.com 9e3 eMerge Installation Instructions
Power Fault Connection
e controller is equipped with a power fault input that can be utilized as follows:
1. Determine whether your power fault input device uses a normally closed or normally open
conguration. Please refer to instructions provided by the manufacturer.
2. Connect the power fault input device to PIN 3 and PIN 4 on the terminal strip.
3. Verify that the power fault input device is functioning properly.
Figure 4.2. Power Fault Connection
Tamper Protection
A tamper switch is mounted inside the enclosure and is pre-wired to the tamper input on the
terminal strip. If the cover is removed for any reason the tamper switch will activate, triggering a
condition that can be linked to an event action in programming (e.g., send an e-mail or generate
an output).
Note: The system
settings must match the
requirement (normally
open or normally closed)
of the power fault
detection device.
TMP -
TMP +
FLT -
FLT +
–
+
Power Fault Input

www.linearcorp.com 10 e3 eMerge Installation Instructions
4.2 Power Connection for Systems using the Metal
Enclosure
Systems using metal enclosures include a factory installed power supervision module as shown in
Figure 4.3.
Power Supply Connection
1. Connect 12VDC from the included power supply to the RED (+) and BLACK (-) leads
on the panel. Note: e3 eMerge systems require a 12VDC, 2 amp Class 2 power supply. Incorrect
voltage will damage the product and void the warranty.
2. Connect an earth ground to the green earth ground lead provided in the enclosure.
3. Turn on the power supply. If using a PIP for the power supply, it must be plugged into a
dedicated receptacle that is not controlled by a switch.
4. e power LEDs (DL17 and DL9) on the panel will turn on to indicate power is present.
5. Connect the leads to the battery (see below).
Figure 4.3. Power Connection for Systems using Metal Enclosure
Battery Connection
e metal enclosure provides charging and space for up to two 12VDC/7Ah sealed lead-acid
batteries (not included). e battery provides standby power when the primary power source is
lost. e control panel will utilize backup battery until the battery voltage reaches 11VDC at
which point the entire system shuts down.
Connecting Batteries in Parallel
Connecting batteries in parallel will double the capacity (amp hours) of the backup while
maintaining the proper voltage. Parallel connected battery connection is shown in Figure 4.3.
Warnings:
♦Use caution when installing batteries. Incorrect use can damage the battery, controller or can
cause a re.
♦Connect a maximum of two identical batteries in parallel. DO NOT connect batteries in
series. is will damage your system and void the warranty.
♦e battery backup and charging uses advanced circuitry. Maximum charge rate is 650mA.
Once the battery is fully charged it is maintained with an occasional 10mA charge. Ensure
these ratings do not exceed the manufacturer’s rating for the battery.
♦Properly dispose of old batteries.
RED RED
BLACKBLACK
BATTERY #1 BATTERY #2
Use minimum of 12GA stranded wire.
Use insulated terminals on battery terminals.
To Power Supervisor &
Battery Charger Module
Connect Batteries in Parallel !!!
DUAL BATTERY INSTALLATION
Note: Wiring methods
shall be in accordance
with the National
Electrical Code/NPFA 70
and all local codes.
Caution: A 12VDC power
supply MUST be used.
Incorrect voltage will
damage the product and
void the warranty.
Minimum
Cable Specifications
for power: 16 AWG
Belden (2 conductor) or
equivalent. Maximum
distance: 6 feet (1.8
meters).
Note: The system will
not power up using the
backup battery. The
12VDC power must be
present to power up the
system.
Note: Replace the
backup battery every 2 to
3 years.
Note: Parallel connected
batteries will take
approximately twice as
long to charge as a single
battery.
TMP -
TMP +
FLT -
FLT +
-
+
12VDC
Earth
Ground
Lead
- +
-+

www.linearcorp.com 11 e3 eMerge Installation Instructions
To determine standby battery time:
1. Determine the total standby load of the system by adding the maximum and standby current
draw of the devices connected to the panel. For example, if the system consists of the control
panel (200 mA) and one 75 mA reader the total standby load is 275 mA (200 mA+ 75 mA).
2. Divide the total standby load by 1000 to convert it to amps. For example, 275 / 1000 = .275.
3. Divide the amp-hour rating of the battery by the total standby load to determine the standby
time for the system. For example, 7.0 / .275 = 25.5 hours standby time using a 7 AH battery
with a system that consists of the control panel and one 75 mA reader.
Power Fault
If AC power loss is detected, the power supervision module will automatically switch to the
backup battery and activate the fault input. e fault input can be congured via programming to
trigger an event such as e-mail or popup message. e transaction will be logged in the history of
the controller.
Tamper Protection
A tamper switch is mounted inside the enclosure and is pre-wired to the tamper input on the
terminal strip. If the cover is removed for any reason the tamper switch will activate, triggering a
condition that can be linked to an event action in programming (e.g., send an e-mail or generate
an output).
4.3 PoE Connection (optional)
Systems can be powered using Power over Ethernet (PoE), which is a method for providing
power via Ethernet cabling. To place the controller in PoE mode, move the Power Input Jumper
to the left position as illustrated in Figure 4.4.
A Power over Ethernet installation must use a high-power 30W PoE injector and the Linear
E3-POE module. Refer to the PoE module’s installation guide for specic installation
information.
Figure 4.4. Power Input Jumper
e3 PoE Module Installed
Note: For PoE
applications only use
UL294B listed PoE power
supplies. PoE is not
supported for installations
requiring UL294.
Note: Each controller
consumes 200 mA of
current at 12VDC (2.4W).
Note: When a power
fault is detected, and
the battery backup is
used, system may be
configured to back up
database and log files to
the microSD card.
Note: A PoE module
is required for each
controller that will use the
PoE option.
Note: Linear E3-POE
module; P/N 620-100159
(requires additional high
power injector) Linear
30W PoE injector:
POE-PLUS
JP1
EXTERNAL 12VDC
POE
(Default)

www.linearcorp.com 12 e3 eMerge Installation Instructions
5.0 Inputs and Outputs
5.1 System Inputs
Systems have the capability of monitoring door status (door contact) inputs, request to exit
(REX) inputs, and auxiliary general purpose inputs.
All inputs are assigned default features that can be congured as needed.e following table
shows the default states for each of the inputs:
Table 5.1: Default Input States
Input Default State
Door Status Inputs Normally Open, Unsupervised, 8 Second Held Open Time
REX Inputs Normally Open, Momentary, Unsupervised
Auxiliary Inputs Normally Open, Unsupervised
Door Status Input
e door status input monitors whether the door is in an open or closed state. A door status
switch (typically a magnetic reed switch) will change states when the door is opened or closed.
e door status input does not require any programming to enable however, you will have to
select either normally open (NO, factory default) or normally closed (NC) operation in the panel.
Simply connect a magnetic reed switch to the appropriate door input as shown in the control
panel illustration, Figure 2.1.
Request To Exit
e Request to Exit (REX) input is a momentary input closure that activates the door output
relay for the same amount of time as a valid card swipe or keypad entry. REX devices can include
a press-to-exit switch on the inside of a door or a passive infrared detector (motion detector),
which allows convenient egress.e REX input does not require any programming. Simply
connect a normally open (NO, factory default), momentary input device to the REX inputs as
shown in the control panel illustration, Figure 2.1.
Auxiliary Inputs
e auxiliary inputs are general purpose inputs that can be used with a variety of input devices
including CO2 detectors, alarm system integration, etc. ese inputs can be congured via
programming to trigger a dened action such as to activate an auxiliary output.

www.linearcorp.com 13 e3 eMerge Installation Instructions
5.2 Wiring the Inputs
All inputs may be congured for normally open (factory default) or normally closed contacts with
supervision or non-supervision. Use standard 1k ohm resistors for supervision. Refer to Figure
5.1 for the acceptable wiring congurations.
Figure 5.1. Input Circuit Configurations
Tamper Protection
A tamper switch is mounted inside the enclosure for connection to pin 5 and pin 6 on the
terminal strip. If the cover is removed for any reason the tamper switch will activate, triggering a
condition that can be linked to an event action in programming (e.g., send an e-mail or generate
an output).
Figure 5.2. Tamper Input Wiring
Note: Wiring methods
shall be in accordance
with the National
Electrical Code/NPFA 70
and all local codes.
Normally Open
Normally Closed
Normally Open
Normally Closed
SUPERVISED UNSUPERVISED
Resistor Value = 1k Ohm
Factory
Installed
Tamp e r
12VDC
TMP -
TMP +
FLT -
FLT +
–
+
Minimum Cable
Specifications: 22 AWG
Belden or equivalent.
Maximum distance: 2000
feet.

www.linearcorp.com 14 e3 eMerge Installation Instructions
5.3 System Outputs
All systems have door lock relays and auxiliary output relays that may be activated in response
to reader activity, time schedules or input conditions. All relays are Form-C SPDT and provide
non-powered dry contacts rated for 2A. e number of available door lock relays and auxiliary
output relays will depend on the number of licensed doors.
Output Defaults
All outputs are assigned default features that can be congured as needed.e following table
shows the default states for each of the outputs:
Table 5.2: Default Output States
Output Default State Default Response
Door Lock Outputs Not Energized, Single Pulse 3 second unlock time in response to corresponding reader
activity (Reader 1 activates door 1 lock relay)
Aux Outputs Not Energized, Single Pulse No default response. Must be configured via programming.
Wiring Requirements
e cable must be the proper gauge for the current load and should not be routed in parallel
with other wiring especially high voltage or AC wiring. Refer to the Table 5.3 for wiring
recommendations:
Table 5.3: Recommended Wiring Requirements
Total Amps Voltage (AC or DC)
Wiring Gauges and Distance
14 16 18 20 22
.5 A
12V 1500 ft 1000 ft 600 ft 375 ft 225 ft
24V 2000 ft 1200 ft 750 ft 450 ft 300 ft
1.00 A 12V 800 ft 500 ft 300 ft 200 ft 100 ft
24V 1000 ft 600 ft 400 ft 200 ft 150 ft
2.00 A
12V 400 ft 240 ft 150 ft 90 ft 60 ft
24V 480 ft 300 ft 180 ft 120 ft 70 ft

www.linearcorp.com 15 e3 eMerge Installation Instructions
5.4 Door Lock Outputs
e door lock outputs can be congured to operate in fail-secure or fail-safe modes.
Wiring the Door Locks
Connect locking devices to the door relay as shown in Figures 5.3 through 5.5. Refer to the
door strike specications to determine the appropriate voltage and conguration. WARNING:
DO NOT USE THE CONTROL PANEL’S POWER SUPPLY FOR THE LOCKING
DEVICE. A SEPARATE POWER SUPPLY MUST BE USED.
NC
C
NO
CONTROL PANEL’S
DOOR LOCK RELAY
DC POWER
SUPPLY
+
-
DIODE 1N4933
OR
EQUIVALENT
+
-
Fail Secure
DC Door Strike
Figure 5.3. Fail Secure DC Door Strike (without power, door strike is locked)
NC
C
NO
DC POWER
SUPPLY
+
-
DIODE 1N4933
OR
EQUIVALENT
+
-
CONTROL PANEL’S
DOOR LOCK RELAY
Fail Safe
DC Door Strike
Figure 5.4. Fail Safe DC Door Strike (without power, door strike is unlocked)
NC
C
NO
CONTROL PANEL’S
DOOR LOCK RELAY
AC POWER
SUPPLY
MOV SNR-D56K2
OR
EQUIVALENT
Fail Secure
AC Door Strike
Figure 5.5. Fail Secure AC Door Strike (without power, door strike is locked)
Note: Wiring methods
shall be in accordance
with the National
Electrical Code/NPFA 70
and all local codes.
Caution: Do not use the
control panel’s power
supply for the locking
device.
A separate power
supply must be used
.
Caution: The diode or
MOV must be installed as
shown in the illustrations.
Failure to install these
protection devices may
damage the control board
or erratic operation.

www.linearcorp.com 16 e3 eMerge Installation Instructions
6.1 Wiring the Readers
e control panel can accept up to 8 readers or keypads. Each reader port on the panel supports a
12VDC reader with Wiegand output format. Readers can be installed as primary (entry) readers
for each door as well as optional secondary (exit) readers.
e maximum power available for individual reader is 750 mA @ 12 VDC with a combined
maximum of 1.5A for the controller. Determine the reader’s power consumption by referring to
the documentation included with the reader. Exceeding the maximum current for individual readers
or for the controller will damage the protection fuses and void the warranty.
Wiring Readers
1. Remove power from the control panel.
2. Pull the reader wiring through a knock-out in the panel’s enclosure.
3. Connect the color-coded wires from the reader’s wiring harness to the appropriate location
of terminal strip as shown in Figure 6.1.
4. Remove excess shield to ensure that it is not exposed. An exposed shield can cause
interference. Tape o any exposed shield with electrical tape.
Figure 6.1. Reader Wiring (typical)
Note: Wiring methods
shall be in accordance
with the National
Electrical Code/NPFA 70
and all local codes.
IN READER
RED
SILVER
Note: A green wire pigtail for
earth ground is provided in all
enclosures. Reader shields
must be properly grounded per
manufacturers installation
requirements.
12 V
LED
BUZZ
GND
IN D0
IN D1
OUT D0 OUT D1
GRN WHT BLK
OUT READER
RED
SILVER
12 V
LED
BUZZ
GND
IN D0
IN D1
OUT D0 OUT D1
GRN WHT BLK
6.0 Readers
Caution: Improper
power wiring will damage
the fuse and void the
warranty.
Minimum Cable
Specifications:
Twisted, shielded 22
AWG (250 ft.) or 18
AWG (500 ft.) Belden
#9535 (5 conductor) or
equivalent. Please follow
manufacturers installation
requirements.

www.linearcorp.com 17 e3 eMerge Installation Instructions
7.0 Network Connection
e controllers must be located in a trusted network environment where a protected network
security system (rewall, etc.) is installed and maintained. Obtain the following information from
your network administrator before conguring the controller:
♦IP address
♦Subnet Mask
♦Gateway
♦DNS 1 and 2
7.1 Preparing for the Network
To allow for the system to be recognized on the local network, it is necessary to change the
controller’s IP address as follows:
1. Connect your programming computer directly to the Ethernet port of the controller as
shown in Figure 7.1. A standard Ethernet may be used for the direct connection - crossover
is not required. (You may also connect the computer and controller to an Ethernet Switch.)
A standard Ethernet may be used for the direct connection - crossover is not required.
Figure 7.1. Connecting to the Control Panel
2. Assign a static IP address of 192.168.0.149 to the computer. (For instructions on how to
change the static IP address of a Windows computer, please visit: http://technet.microsoft.
com/en-us/library/710457).
3. After assigning the static IP address,
open a web browser and
enter the IP address of the
controller (Default = 192.168.0.250).
4. e controller presents the e3 page as shown in Figure 7.2. To log on, enter the default user
ID and password (admin/admin).
Figure 7.2. Login Page
Note: For UL
installations, the
maximum Ethernet cable
length is 30m (98.5 FT.).
ETHERNET
LAN LED
Note: If a DHCP server
is present, IP Addresses
are dynamically
assigned. A static IP
address is strongly
recommended for the
controller because a
DHCP Server may assign
a new IP Address.
Caution: The system is
exposed to potential risks
if installed on a network
without proper security
precautions. Consult the
appropriate on-site IT
administrator.

www.linearcorp.com 18 e3 eMerge Installation Instructions
5. Browse to the Network Conguration (IP address) page as shown in Figure 7.3. Enter
the static IP address, Subnet Mask, Gateway and DNS server so that it matches the
requirements of the local network. (Refer to the User Manual for complete programming
information.)
Figure 7.3. Network Settings Page
6. Click Save & Reboot and the system will reboot. (Reboot will take approximately 2
minutes.) Note: e system data will be lost if the controller is powered down without
performing Save & Reboot.
7. Disconnect the programming computer from the control panel. e system is now ready for
the local network.
7.2 Connecting to the Network
1. Pull an Ethernet cable through the opening in the enclosure nearest the Ethernet port.
2. Plug the RJ-45 connector into the Ethernet port on the controller.
3. Connect to the local area network (LAN) as shown in Figure 7.4.
Figure 7.4. Connecting to a LAN
If the network connection is functioning properly, the LAN LEDs on the control panel will
illuminate as shown in Figure 7.5. e local computers will then be able to access the system by
entering the IP address of the controller.
eMerge e3 LAN
Client Computer
Router
Internet
Note: The system
data will be lost if the
controller is powered
down without performing
Save & Reboot.
Cable specification:
CAT 5 or better with an
RJ-45 connector wired
straight through to a
network hub, switch or
router.
Table of contents