
Page 18
1.12 Air distribution system
All materials used within the construction of the delivery and return air ducts must not represent a re hazard and
should be made from thermally inert materials. The selection of materials must take account of the environment
into which the heater and its air delivery system is expected to work, it must also take account of the stresses and
loadings placed upon it during its normal working life. Where interjoist spaces are used to route ducting these must be
lined with re resistant insulation material.
In installations where forced recirculation is a feature, a full and unobstructed return air path to the heater(s) must be
provided, with return air grilles connected by ducting directly to the return air inlet on the heater.
The limit for recirculation should not be greater than 85% re-circulated air to 15% fresh air.
Where the heater is installed within a compartment or plant room the return air and discharge air arrangement must
be such that the air circulation fan does not interfere with the operation of the ue. The return air intake and warm air
outlet should therefore be fully ducted to and from the heater, respectively, within the compartment or plant room.
If the inlet air is ducted to the outside, then the lowest edge of the inlet air duct must be at least 500mm above the
outside oor or ground level, it must also be tted with an access point(s) to allow for cleaning and servicing to occur.
The openings in the structure of the plant room, through which the ductwork passes must be of re resistant material
and constructed to prevent the likelihood of any re from spreading.
In ducted applications the ductwork must be designed so as to give a static pressure within the limits stated in section
1.15 of this manual. It should be noted that if the static pressure is too high, nuisance shut-down will occur when the
heater goes out on the overheat limit thermostat, if the static pressure is too low, then damage can be caused to the
fan motor.
Warm air outlets on ducted applications must be such that they cannot be closed or become blocked, which again
would lead to an increase in static pressure and nuisance shut-down. The outlets must not be sited so that warm air
can be discharged onto combustible materials, if necessary, guard rails should be used to ensure that effected areas
are kept clear.
Return air intakes must not be located so that potentially harmful or hazardous contaminated air can be drawn into the
system.
1.13 Flue system.
WARNING
It is essential that the products of combustion are ued to the outside of the building. Each heater must have its
own separate ue, with a ue diameter of not less than is detailed in section 1.15 within this manual.
The minimum vertical length of ue must not be less than 3m. The ue should rise vertically, and the number of bends
should be kept to a minimum.
Flue pipes below a height of 2m should be guarded against the possibility of being accidentally touched when hot by
personnel
It is strongly advised that BS 5854; 1980, and BS 5440; parts 1 and 2, are used as consultative documents
when considering ue requirements.
Care should be taken to ensure that the ue terminal is not situated in a high-pressure area, the proximity of buildings
and other obstacles which will inuence this must be taken into account, preferably at the design stage. See pages 15
& 16
Provision must be made for the disconnection of the ue for inspection and service requirements, and it is strongly
advised that where bends are tted inspection covers are included.