1607UDSA-4GBEN, Pag. 7/40
1) Gas Appliance Classifications for Approved Venting Methods based on CEN-report CR1749:2001.
2) There is a difference between the gas connection diameter and the diameter of the supply line. Always use the most adequate dia of the supply line to minimize the
pressure drop through the gas pipes - if necessary, reduce the diameter of the supply line at the inlet of the unit.
3) Height from floor to bottom surface of heater. These are recommendations only. Positioning of unit heaters for proper performance is application dependent. Operation
is affected by other air moving equipment in the space, obstructions to the airflow, draughts and/or close proximity to doors or windows, etc ... Care should be taken to
avoid mounting the heaters above these recommendations, unless downturn nozzle options are used, as significant stratification may occur resulting in poor floor
coverage and higher energy losses through the roof structure.
4) Isothermal conditions +/-20°C ambient air temperature, discharge louvres zero deflection, v = 0,5m/s. The air throw will be influenced by the height of the building,
mounting height of the unit, ambient temperature & adjustment of the louvres.
5) Sound pressure measured in dB(A) : at 5m distance of the heater with A=160m² & Q=2
Model 008-4 011-4 015-4 020-4 025-4 030-4 035-4
Combuson air and flue, type B instal. (1) B22
Combuson air and flue, type C instal. (1) C12, C32, C42,C52, C62, C82
Flue & combuson air connecon collars mm 80 80 80 80 100 100 100
Heat input (Hs) kW 8,8 13,2 17,6 22,0 30,8 35,2 41,8
Heat input (Hi) kW 7,9 11,9 15,9 19,8 27,8 31,7 37,7
Heat output kW 7,3 11,0 14,6 18,2 25,5 29,2 34,7
Thermal efficiency %92929292929292
Gas consumpon nat gas G20 m³/h 0,84 1,26 1,68 2,10 2,94 3,36 3,99
prop G31 kg/h 0,62 0,93 1,24 1,55 2,16 2,47 2,94
Gas connecon size (not supply line) (2) 1/2” 3/4”
Temperature rise K32323232323229
Air flow m³/h 680 1020 1360 1700 2385 2725 3510
Motor speed rpm 1390 1390 1450 1450 930 1250 920
Recommended mounng height(3) m3333444
Horizontal throw(4) m 8 10 13 16 20 25 25
Sound pressure (5) dB(A) 47 46 47 48 43 49 44
Electrical service (class IP20) 230/240V 1N ~ 50Hz
Total electrical rang W 121 121 126 126 273 270 290
Weight (net) kg 30 33 38 40 54 57 86
Model 043-4 050-4 055-4 064-4 073-4 085-4 100-4
Combuson air and flue, type B instal. (1) B22
Combuson air and flue, type C instal. (1) C12, C32, C42,C52, C62, C82
Flue & combuson air connecon collars mm 100 100 130 130 130 130 130
Heat input (Hs) kW 50,8 58,6 66,0 77,7 88,0 102,7 117,3
Heat input (Hi) kW 45,8 52,8 59,5 70,0 79,3 92,5 105,7
Heat output kW 42,1 48,6 54,7 64,4 73,0 85,1 97,0
Thermal efficiency %92929292929292
Gas consumpon nat gas G20 m³/h 4,85 5,59 6,30 7,41 8,39 9,79 11,18
prop G31 kg/h 3,57 4,12 4,64 5,46 6,18 7,21 8,24
Gas connecon size (not supply line) (2) 3/4”
Temperature rise K28282828282828
Air flow m³/h 4535 5180 5830 6810 7770 9065 10360
Motor speed rpm 910 1360 940 930 900 890 1050
Recommended mounng height(3) m4444444
Horizontal throw(4) m28323533414139
Sound pressure (5) dB(A) 45 56 51 52 54 55 60
Electrical service (class IP20) 230/240V 1N ~ 50Hz
Total electrical rang W 290 500 500 500 770 770 960
Weight (net) kg 99 102 114 118 143 160 179
6. Technical data
Table 4 : Technical data
Gas category : II2H3+