Novar HPC User manual

DOC. #569062000 2/20/01 PRINTED IN U.S.A.
HPC/HPC Plus
Installation Instructions
A
B
C
D
E
F
5705390-B
RELAY OUTPUT STATUS
HEAT PUMP CONTROLLER
SERIAL NUMBER
MODEL
SOFTWARE
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS
SUBJECT TO THE FOLLOWING TWO CONDITIONS:
1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE , AND 2) THIS
DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING
INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
MAX ALLOWABLE AMBIENT TEMP: 38 C (100 F) 70 C (158 F)
REFER TO INSTALLATION INSTRUCTIONS 5690620
TORQUE ALL TERMINALS TO 7 LB.-IN.
USE COPPER CONDUCTORS ONLY
LISTED ENERGY
MANAGEMENT
EQUIPMENT
SUBASSEMBLY
20M1
MADE IN USA
WARNING
THIS UNIT IS NOT INTENDED TO BE
USED AS A FINAL SAFETY DEVICE
OUTPUTS: 1A, 24VAC MAX PILOT DUTY, CLASS 2
POWER REQUIREMENTS: 24VAC, 8VA, CLASS 2
www.novar.com

FCC Information
This device complies with Part 15 of the FCC rules. Operation is subject to the following
two conditions: (1) This device may not cause harmful interference, and (2) this device
must accept any interference received, including interference that may cause undesired
operation.
NOTE! This equipment has been tested and found to comply with the limits for
a Class B digital device pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is
likely to cause harmful interference, in which case the user will be
required to correct the interference at his own expense.
CAUTION! Any changes or modifications not expressly approved by Novar
Controls Corporation could void your authority to operate this
equipment.
Industry Canada
This digital apparatus does not exceed the Class B limits for radio noise emissions from
digital apparatus set out in the interference-causing equipment standard entitled Digital
Apparatus, ICES-003, of Industry Canada.
Cet appareil numérique respecte les limites de bruits radioélectriques applicables aux
appareils numériques de Classe B préscrites dans la norme sur le matériel brouiller:
Appareils Numériques, NMB-003, édictée par l’Industrie Canada.
Disclaimer
LOGIC ONE® is a registered trademark of Novar Controls Corporation.
Lingo™ is a trademark of Novar Controls Corporation.
The material in this manual is for information purposes only. The contents and the
product it describes are subject to change without notice. Novar Controls Corporation
makes no representations or warranties with respect to this manual.
In no event shall Novar Controls Corporation be liable for technical or editorial omissions
or mistakes in this manual, nor shall it be liable for any damages, direct or incidental,
arising out of or related to the use of this manual.
Copyright © 2001 by Novar Controls Corporation. All rights reserved.
No part of this manual may be reproduced in any form or by any means
without prior written permission from Novar Controls Corporation.
Novar Controls Corporation
3333 Copley Road, Copley, OH 44321
Tel: (330) 670-1010 www.novarcontrols.com

Description
Novar Controls Corporation’s Heat Pump Controller (HPC) and the Heat Pump
Controller Plus (HPC Plus) are dedicated, direct digital control modules that
provide precise and integrated control for heat pump applications.
The HPC is applied to single-stage (1 H/1 C) heat pumps that energize the reversing
valve internally and require a “call for heat” or a “call for cooling” like a conventional
thermostat. It features a time delay that allows a loop water pump time to respond to
a call for heating or cooling before it actually energizes the heating or cooling outputs.
The HPC Plus energizes the reversing valve and compressors directly—it does
not contain a conventional heating or cooling output. Like the HPC, it
incorporates a compressor delay to allow time for a loop water pump to turn on
before energizing the compressors. The HPC Plus also features a special general
fault input to receive contact closure signals from a variety of safety switches.
This input can be used to initiate an alarm or shut down the heat pump unit when
the signal is received from the switch.
To select the proper unit for an application, examine the inputs and outputs of
these modules carefully.
This document provides procedures for mounting the HPC or HPC Plus,
connecting the power and network communications, wiring the inputs and
outputs, setting the module address, and checking installation.
NOTE! The HPC Plus requires an EP/2, Savvy, or Lingo as the
executive module. The HPC works with any executive module.
Specifications
Agency Approvals
UL, Energy Management Listed Device: UL/CUL File #E90949
Equipment UL-916:
Power Requirements
Voltage: 24 VAC, Class 2
Consumption: 8 VA
Operating Environment
Temperature: HPC: 32° to 100°F (0° to 38°C)
HPC Plus: –40° to 158°F (–40° to 70°C)
Humidity: 0 to 99% Relative, noncondensing
Physical Dimensions
Height: 5.5 inches
Width: 8 inches
Depth: 1.875 inches
Weight: 1.75 lb
DOC. #569062000 2/20/01 1
HPC/HPC Plus Installation Instructions

Precautions
Take the following precautions during installation:
§Observe national and local electrical codes.
§Observe voltage and current limits marked on the module.
§Do not connect 115 volts to any terminal of the HPC or HPC Plus. They are
Class 2 (low voltage) control devices.
§Do not use the HPC or HPC Plus as a final safety device.
Mounting the HPC or
HPC Plus
The HPC and HPC Plus are designed to be mounted in the control compartment
of the heat pump. Be careful that the module and mounting hardware do not
interfere with proper operation of the heat pump.
Use the following procedure to mount the HPC or HPC Plus.
Step Procedure
1 Turn off all power to the heat pump unit before installing the HPC
or HPC Plus.
2 Position the HPC or HPC Plus against the mounting surface and
mark the surface to show the location of the four mounting screw
holes (see Figure 1).
3 Drill holes at the locations marked on the mounting surface.
4 Insert metal screws (not included) through the module and the
mounting surface and tighten to secure the module.
2DOC. #569062000 2/20/01
HPC/HPC Plus Installation Instructions
A
B
C
D
E
F
5705390-B
RELAY OUTPUT STATUS
HEAT PUMP CONTROLLER
SERIAL NUMBER
MODEL
SOFTWARE
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS
SUBJECT TO THE FOLLOWING TWO CONDITIONS:
1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE , AND 2) THIS
DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING
INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
MAX ALLOWABLE AMBIENT TEMP: 38 C (100 F) 70 C (158 F)
REFER TO INSTALLATION INSTRUCTIONS 5690620
TORQUE ALL TERMINALS TO 7 LB.-IN.
USE COPPER CONDUCTORS ONLY
LISTED ENERGY
MANAGEMENT
EQUIPMENT
SUBASSEMBLY
20M1
MADE IN USA
WARNING
THIS UNIT IS NOT INTENDED TO BE
USED AS A FINAL SAFETY DEVICE
OUTPUTS: 1A, 24VAC MAX PILOT DUTY, CLASS 2
POWER REQUIREMENTS: 24VAC, 8VA, CLASS 2
www.novar.com
Figure 1. HPC/HPC Plus mounting holes
Two mounting
holes on each
side

Supplying the HPC or
HPC Plus with Power
The HPC and HPC Plus are powered by 24-volts AC and rated at 8 VA. To
supply the module with power, connect the 24 volts to Terminals 15 and 16 by
the label marked “Power Input 8 VA.”
Figure 2 shows the power connections on the HPC or HPC Plus terminal strip.
NOTE! The 24-VAC power connection is isolated. One transformer
can be used to power multiple modules within the restrictions
of an 8-VA consumption.
Wiring the HPC or HPC
Plus
Wiring the Inputs
The HPC and HPC Plus have a removable terminal strip that uses screw
connections. The inputs are Terminals 1 through 10, located on the left side of
the terminal strip (see Figure 2).
NOTE! On the HPC Plus, Terminals 13 and 14 under the “Analog
Outputs” label are used as a digital input. A contact
closure safety switch can be connected to these terminals
as a general fault input.
DOC. #569062000 2/20/01 3
HPC/HPC Plus Installation Instructions
2161211511
+5V EADJ 24VACD
317 1813
S1
+
F
414
COM SHIELDGND
TEMP
SENSOR
INPUT
MODULE
NETWORK
5V MAX
POWER
INPUT
8VA
AUX
POT
ANALOG
OUTPUTS
0-10VDC, 1mA MAX
ALL INPUTS
AND OUTPUTS
ARE CLASS 2
STATUS
INPUT
OVER-
RIDE
SWITCH
RELAY OUTPUTS
1A, 24VAC MAX PILOT DUTY
519
S2
-
620
DI 1
T
R
721
RETRET A
822
DI 2
B
923 25
O/R CE
10 24 26
DF
ADDRESS
SWITCH
Figure 2. HPC/HPC Plus terminal strip

Auxiliary Potentiometer
An auxiliary potentiometer can be connected to the HPC or HPC Plus at the
terminals labeled “Aux Pot.”
Step Procedure
1 Connect the wiper wire to Terminal 1.
2 Connect the clockwise wire to Terminal 2.
3 Connect the counterclockwise wire to Terminal 4 at the “Temp
Sensor Input” label.
§This connection allows adjustments to the zone setpoint.
Novar Controls Corporation’s Futura Temperature Sensor (Model (FTS-3A) can
be used with the HPC or HPC Plus to obtain setpoint adjustment. Installation
instructions are included with the sensor.
Temperature Sensor Inputs
The temperature sensor input terminals are located at the “Temp Sensor Input”
label. Each HPC or HPC Plus must use a Remote Temperature Sensor
(RTS-UVC) for discharge air and one of the following sensors:
§UVC Wall-Mount Indoor Temperature Sensor (WTS-UVC)
§Futura Temperature Sensor (FTS-3 or FTS-3A with temperature setpoint
adjustment)
§RTS-UVC (for return air control)
Step Procedure
1 Connect the Wall-Mount Temperature Sensor’s plus wire (+) to
Terminal 3.
2 Connect the Remote Temperature Sensor’s red wire to Terminal 5.
3 Connect the black wire (–) from both sensors to Terminal 4.
To wire the other sensors to the HPC or HPC Plus, refer to the installation
instructions shipped with the sensors.
NOTE! Maximum recommended sensor wire length for connecting
the temperature sensors to the HPC or HPC Plus is 100 feet
using 22-gauge wire (Novar Controls WIR-1010, Belden
8761, or equivalent).
4DOC. #569062000 2/20/01
HPC/HPC Plus Installation Instructions

Status Input
Terminals 6, 7, and 8 (labeled “Status Input”) are for digital input connections.
§Terminals 6 and 7 are for the fan status.
§On the HPC, Terminals 7 and 8 are for filter status.
§On the HPC Plus, Terminals 7 and 8 are for the Compressor Stage 1 status.
These are dry contact closure, digital inputs and are connected as normally open
with the fan status as closing when the fan is on and the compressor status as
closing when the compressor is on.
Override Switch
A normally open momentary contact switch can be connected to Terminals 9 and
10 (Labeled “Override Switch”) to be used as a timed override. The override
switch can have a status LED. The software defines the length of time that the
override remains in effect.
The Futura Temperature Sensor provides an override switch and status LED.
Refer to the installation instructions shipped with the sensor for information
about proper connections.
General Fault Input (HPC Plus Only)
Terminals 13 and 14 under “Analog Outputs” are used to connect to a dry contact
closure input from a safety switch. The signal from the safety switch can be used
to initiate an alarm or shut down the heat pump (based on how the input is
defined in the software).
Use the following procedure to make the connections.
Step Procedure
1 Connect one wire from the safety switch to Terminal 13 (F).
2 Connect the other wire from the safety switch to Terminal 14
(GND).
DOC. #569062000 2/20/01 5
HPC/HPC Plus Installation Instructions

Wiring the Outputs
Table 1 outlines the HPC and HPC Plus analog and digital outputs.
Table 1. HPC and HPC Plus Digital and Analog Outputs
ANALOG OUTPUTS HPC PLUS HPC
Terminal 11 (D) Damper
Terminal 12 (E) Not Active
Terminal 13 (F) Used for General Fault Input
DIGITAL OUTPUTS HPC PLUS HPC
Terminal 21 (A) Fan Fan
Terminal 22 (B) Compressor Stage 2
Terminal 23 (C) Auxiliary Heat
Terminal 24 (D) Not Active
Terminal 25 (E) Reversing Valve Heating
Terminal 26 (F) Compressor Stage 1 Cooling
Damper Analog Output (HPC Plus Only)
The HPC Plus damper analog output terminals are listed under the label “Analog
Outputs” immediately to the right of the input connections (Figure 2).
Step Procedure
1 Connect the damper actuator’s control signal (+) to the Heat
Pump Controller Plus at Terminal 11 (D).
§This isa0to10-Volt, 1 mA maximum connection.
2 Connect the damper actuator’s common or ground connection to
Terminal 14 (GND) of the HPC Plus.
Terminals 13 (F) and 14 (GND) are used for making a connection from a general
fault input (refer to the “Wiring the HPC or HPC Plus, Inputs, General Fault
Input [HPC Plus Only]” section of these instructions). Terminal 12 (E) is not
active.
6DOC. #569062000 2/20/01
HPC/HPC Plus Installation Instructions

Relay Outputs
The digital relay output terminals are located on the far right side of the terminal
strip under the label “Relay Outputs.” Terminals 21–26 (A–F) are the actual
output connections. Use Figure 2 and Table 1 to determine the correct connections.
Digital relay output D (Terminal 24) is not active because of the analog damper
connection.
The digital relay outputs tie in directly to the six relay output status LEDs located
on the case of the HPC or HPC Plus. The relay output status LEDs match the
status of the relay:
§If the contact is closed, the relay is energized and the LED is on.
§If the contact is open, the relay is de-energized and the LED is off.
Terminal 20 is for one side of a 24 source to be regulated (switched) through
Terminals 21–26 (A–F). The relay outputs are isolated from the other
connections to permit the additional power source. The transformer powering the
module can be used if it has enough capacity.
Network
Communications
Use a suitable shielded cable (Novar Controls WIR-1010, Belden 8761, or
equivalent) to make the communication connections between the HPC or HPC
Plus and the module communications terminals of the executive module.
On the HPC or HPC Plus, the connections are Terminals 17, 18, and 19, located
under the label “Module Network 5V Max.” Make certain that the plus (+) and
minus (–) connections are made correctly.
CAUTION! The Shield connection is not a ground like the other
common grounds on the terminal strip. It is dedicated
for communications only. Do not connect any other
grounds to the Shield connection (Terminal 18).
DOC. #569062000 2/20/01 7
HPC/HPC Plus Installation Instructions

Setting the Module
Address Switches
Every LOGIC ONE module must have a unique address. The address switch is
located in the middle of the terminal strip (Figure 2).
Addresses are assigned in the software during system formatting. Use the system
printout to find the address of the HPC or HPC Plus being installed. Refer to
Figure 3 and set the switches with the correct address from 00 to 63. If a Lingo™
is used as the executive processor, address switches 64–127 duplicate the settings
for 00–63 (address switch 64 is the same as address switch 00, 65 is the same as
01, etc.). Record the setting on the module address label.
8DOC. #569062000 2/20/01
HPC/HPC Plus Installation Instructions
Figure 3. HPC/HPC Plus address settings

Checking Installation
Turn on the power to the HPC or HPC Plus. Make sure that power to the heat
pump unit and its control circuitry is on. If the executive module is operating
properly, the HPC or HPC Plus begins to control the heat pump in about 3
minutes (after performing a self-diagnostic check and establishing
communications with the executive module).
A schedule status indicator LED is located on the module’s case above the
terminal strip. If the module is communicating properly, this LED should be
flashing according to the scheduled mode.
§When the HPC or HPC Plus is in scheduled off mode, the LED is off and
flashes on briefly when communicating.
§When the module is in scheduled on mode, the LED is on and flashes off
briefly when communicating.
If a timed override switch has been installed and programmed, it can be tested for
proper operation by pressing it during a scheduled off mode. The LED flashes
rapidly until the override period ends.
The six relay output status LEDs indicate the status of each active digital output.
Verify that the LEDs are lit when the corresponding digital output is on.
If any faults or malfunctions still exist, they are picked up by the executive
module and announced by alarm messages.
Model and Part Numbers
Use the part numbers listed in Table 2 to order the necessary Novar Controls
parts.
Table 2. Novar Controls Part Numbers
PRODUCT MODEL NO. PART NO.
Heat Pump Controller HPC 738005000
Heat Pump Controller Plus HPC Plus 738025000
Futura Temperature Sensor for use with HPC FTS-3 732403000
Futura Temperature Sensor with temperature
adjustment potentiometer
FTS-3A 732401000
Remote Temperature Sensor for UVC RTS-UVC 736003000
UVC Wall-Mount Temperature Sensor WTS-UVC 736002000
Two conductor, shielded cable (Belden
8761equivalent
WIR-1010 709001000
DOC. #569062000 2/20/01 9
HPC/HPC Plus Installation Instructions

This page intentionally left blank.
10 DOC. #569062000 2/20/01
HPC/HPC Plus Installation Instructions
This manual suits for next models
3
Table of contents
Other Novar Controllers manuals