nuaire.co.uk 029 2085 8200
Installation and Maintenance FAITH - 230V / 24V SELV Extract Fans
8
6.11 Decentralised Mechanical Extract Ventilation (dMEV)
FAITH units are suitable for decentralised mechanical extract
ventilation and are recognised by the Government’s Standard
Assessment Procedure (SAP) under the Product Characteristic Database
(PCDB).
In order to meet requirements, the unit must be set to the below
specifications:
•Run continuously (see Section 6.4) at 4, 6 or 8l/s, depending on
the requirements under Part F of the building regulation, Table 5.1a.
•Boost speed (see Section 6.6) should be set at 6, 8 or 13 l/s, again
see Building Regulation Part F Table 5.1a.
•Comfort Boost (see Section 6.5) should be set between trickle
speed and boost speed settings .
•Constant Flow – ON (see Section 6.7).
•Through Wall or In-Room (ducted) installation (see Section 6.8).
•All other settings are as per customers’ requirements.
7.0 MAINTENANCE
Before any maintenance or cleaning operation, switch off the fan and
disconnect from the power supply.
The magnetic front cover can be removed and cleaned with water and
a mild detergent using a soft cloth and the motor fan assembly can
be cleaned with a dry brush or dry cloth. Any other maintenance or
cleaning should be carried out by properly qualified personnel.
Ensure the unit does not come into contact with any kind of liquid
or solvent. If this should occur, contact a qualified technician before
reassembling the fan.
NOTE: The motor does not require lubrication as it is of the
maintenance free "sealed for life" type.
8.0 WARRANTY
The 5 year warranty starts from the day of delivery and includes parts
and labour for the first year. The remaining period covers replacement
parts only.
This warranty is void if the equipment is modified without
authorisation, is incorrectly applied, misused, disassembled, or not
installed, commissioned and maintained in accordance with the details
contained in this manual and general good practice.
The product warranty applies to the UK mainland and in accordance
with Clause 14 of our Conditions of Sale.
If any abnormalities in operation are detected, disconnect the unit from
the supply and contact a qualified technician immediately. Use original
spare parts only for repairs.
If the supply cord is damaged, it must be replaced by the manufacturer,
its service agent or similarly qualified persons in order to avoid a hazard.
Technical or commercial considerations may, from time to time, make it necessary to alter the design, performance and dimensions of equipment
and the right is reserved to make such changes without prior notice.
9.0 DISPOSAL AND RECYCLING
Information on disposal of units at the end of life.
This product complies with EU Directive 2002/96/EC.
The symbol of the crossed-out dustbin indicates that this
product must be collected separately from other waste at
the end of its life. The user must, therefore, dispose of the
product in question at suitable electronic and electro-
technical waste disposal collection centres, or else send
the product back to the retailer when purchasing a new,
equivalent type unit.
Separate collection of decommissioned equipment for recycling,
treatment and environmentally compatible disposal helps to prevent
negative effects on the environment and on health and promotes the
recycling of the materials that make up the equipment.
Improper disposal of the product by the user may result in
administrative sanctions as provided by law.
10.0 AFTER SALES ENQUIRIES
For technical assistance or further product information, including spare
parts and replacement components, please contact the After Sales
Department.
Telephone 02920 858 400
aftersales@nuaire.co.uk