15. 05. 17. Leaflet Number 671372
Installation and Maintenance NALT-H Metal Cased Centrifugal Fans
Technical or commercial considerations may, from time to time, make it necessary to alter the design, performance and
dimensions of equipment and the right is reserved to make such changes without prior notice.
For good EMC engineering practice, any sensor cables
or switched live cables should not be placed within 50mm of
other cables or on the same metal cable tray as other cables.
Isolation - Before commencing work make sure that the
unit, switched live and Nuaire control are electrically
isolated from the mains supply.
Please note this product must be earthed.
5.0 Electrical Wiring
Electrically isolate unit before commencing any work.
Ensure that the voltage and frequency of the electrical supply
match the information stated on the Rating Plate on the unit.
Wire the unit as shown in the wiring diagram. On connecting the
electrical supply ensure that the airflow direction corresponds
with the direction of airflow arrow sited on the unit.
Fig. 3.
Electrical Note: Because the run and start currents depend upon
the duty and associated duct work of an individual unit, the
values quoted in the table are nominal.
Run currents will be exceeded if the unit is operated beyond the
operating curve shown in the performance catalogue.
6.0 Maintenance
Electrically isolate unit before commencing any work.
Usage and conditions will dictate frequency of maintenance.
We recommend a thorough inspection and cleaning three months
after commissioning and, dependant on how the fan is found at
least annually thereafter.
Fans and systems should be maintained in accordance with the
HVCA Standard Maintenance Recommendations for Mechanical
Services in Buildings Volume 11 Ventilation and Air-conditioning.
Do not use a high pressure cleaner (steam jet) or any solvents
for cleaning purposes.
Do not immerse the unit in water.
Check all parts for security and general condition.
Ensure the impeller rotates freely.
7.0 Warranty
The unit has a one year warranty. The warranty starts from the
date of delivery and covers faulty materials or workmanship
and includes parts and labour.
This warranty is void if the equipment is modified without
authorisation, is incorrectly applied, misused, disassembled, or
not installed, commissioned and maintained in accordance with
the details contained in this manual and general good practice.
The product warranty applies to the UK mainland and in
accordance with Clause 14 of our Conditions of Sale. Customers
purchasing from outside of the UK should contact Nuaire
International Sales office for further details.
8.0 After Sales Enquiries
For technical assistance or further product information,
including spare parts and replacement components, please
contact the After Sales Department.
Telephone 02920 858 400
MOTOR
YELLOW-GREEN
BLACK
L N
BLUE
BROWN