Set point
adjuster screw
Small screwdriver
Note colour
code guide
label when
fitting
Backplate
(rear view)
10m sensor connection
wire (supplied).
Clearance aperture for wire
should be approx 20mm dia
to allow passage of plug end.
Allow approx 75mm of wire
through for fitting to the
backplate
Wire can be located behind
awall panel or fixed to wall
surface.
Plug end
Before fixing the backplate
to the wall, fit the plug end
from sensor body into the
backplate.
Note that colour coded
connections are matching
Sensor can now clip onto
backplate
Wall
To fan connector
box terminal
marked NET
Fixing screws supplied
IMPORTANT! Please refer to the
installation instructions of the fan to
check the com atibility of this sensor.
Parts check list:
lES-TEMP Tem erature Sensor
l1 off 10 metre length of lugged
SELV cable
ES-TEMP Tem erature Sensor
Designed to be compatible with the Ecosmart
system, this temperature sensor unit is
supplied with a pre-plugged, 10 metre length
of communications cable. Note: longer
lengths are available if required.
The sensor operates with Safe Extra Low
Voltage (SELV) with power supplied from
the fan unit via the communications cable.
The ES-TEMP Sensor will vary the ventilation
rate automatically according to the
measured temperature.
Fault indication
The LED will change from green to red if
any fan connected in that zone has failed.
Multi le Sensors
Multiple sensors can be connected to the
networ . Please refer to the actual fan
installation instructions for exact
quantities.
Installing the Sensor
The sensor unit should be installed away
from any direct source of heat (e.g.
radiators) and areas where it would be
subjected to waterspray.
The Sensor is supplied complete with
10 metres of connecting cable with plugs
attached. Sensors are also supplied with all
fixings and are clipped into a bac plate wall
mounting brac et.
a) Fix one end of the 10m cable to the fans
customer connection box (connection
soc ets mar ed NET).
b) Select a suitable location for the sensor
and arrange the cable in position. Leave
approx. 75mm of the cable free at the
mounting point to ease the connection
of the plug. (fig. 1).
c) Carefully separate the sensor from the
bac plate using a small screwdriver
(see Fig 2) Note: the sensor will remain
connected by its internal cable.
d) Release this cable from the brac et by
simply pulling the plug off the soc et pins
in the bac plate.
e) Before fixing the bac plate to the wall,
connect the wall fixed cable end plug to
the upper set of pins on the brac et (fig 3)
Note: check the colour code matching on
when fitting the plug onto the pins.
Arrange the cable to lay in the cable slot
at the top of the bac plate moulding and
fix the brac et to the wall surface using
the screws supplied.
f) The sensor plug can now be connected
into the bac plate Note: check the colour
code matching when fitting the plug onto
the pins.
Clip the sensor body in the bac plate arms
and adjust the sensor body to the desired
position.
Data cable installation
A 4-core SELV data cable is used to
connect devices.
Do not run data cable in the same conduit
as the mains cables and ensure there is a
50mm separation between the data cable
and other cables. The maximum cable run
between any two devices is 300m when it
is installed in accordance with the
instructions.
Please note that the total data cable length
used in any system must be less than
1000m. Keep the number of cable joints to
a minimum to ensure the best data
transmission efficiency between devices.
Adjusting the sensor set oints
Adjustable tem erature setting 10 -35 oC
Assuming the sensor(s) are installed,
adjustment of the set points achieved by
tilting the sensor forwards which exposes
the adjustment aperture (see fig 5).
Using a small screwdriver, gently turn the
dial either cloc wise or anti-cloc wise to
increase or decrease the set point.
When adjustments are made to the sensor,
the LED light on the sensor front will flash
on and off to show the set point. First,
green flashes will indicate the set point in
TENS, then red flashes will indicate UNITS.
For example 2 green flashes and three
red flashes show a temperature set point
of 23 oC.
ES-TEMP
Temperature Sensors
Installation Guide
Figure 1.
Figure 2.
Figure 3.
Figure 4.
Figure 5.
Nuaire Limited Western Industrial Estate Caerphilly United Kingdom CF83 1NA
T: 029 2085 8400 F: 029 2085 8444 E: [email protected] W: www.nuaire.co.u
03. 07. 15. Leaflet Number 671128
The EMC Directive
2004/108/EC
The Low Voltage
directive
2006/95/EC
Sensor Res onse
Normal o eration
(Pro ortional band over ten 10 oC ste s)
When temperature RISES, the fans will increase
speed.
See figure 6 opposite, which shows a set point
at 19 0C.
For single phase fans, the speed steps are
approximate and the actual running speeds will
be dictated by the operating pressure of the
system and the type of impeller used in the blower.
Installation and Maintenance ECOSMART Temperature Sensor
19 2021 222324252627282930
10
9
8
7
6
5
4
3
2
1
Fan Speed
Room temperature (degrees C)
EXAMPLE:
Setpoint set
to 19oC
9 10 11 12 13 14 15 16 17 18 19
1
Deadband
Speed
Speed
Max Speed
Min Speed
Figure 6.
Technical or commercial considerations may, from time to time, ma e it necessary to alter the design, performance and
dimensions of equipment and the right is reserved to ma e such changes without prior notice.
Maintenance
The unit does not require any maintenance. However, for
optimum performance, it is advisable to remove any
accumulated dust with a low power vacuum cleaner.
NOTE: Installation and Maintenance of the equipment must
be as directed in the instructions provided with the unit.
Warranty
The 5 year warranty starts from the day of delivery and
includes parts and labour for the first year.
The remaining 4 years covers replacement parts only.
This warranty is conditional on planned maintenance
being underta en.
Service Enquiries
Nuaire can assist you in all aspects of service. Our Technical
Support department will be happy to provide any assistance
required.
Tele hone 029 2085 8400
Fax 029 2085 8444
2
03. 07. 15. Leaflet Number 671128

Popular Temperature Controllers manuals by other brands

Danfoss ECL Comfort 310 installation guide

Danfoss

Danfoss ECL Comfort 310 installation guide

Giacomini KTD3 Installation and operating instructions

Giacomini

Giacomini KTD3 Installation and operating instructions

Omron E5CC user manual

Omron

Omron E5CC user manual

CARLO GAVAZZI T2000 Series CGI Tempware Software Manual

CARLO GAVAZZI

CARLO GAVAZZI T2000 Series CGI Tempware Software Manual

Campbell CS240 product manual

Campbell

Campbell CS240 product manual

i-therm AI-5982 User's operating manual

i-therm

i-therm AI-5982 User's operating manual

F&F RT-825 user manual

F&F

F&F RT-825 user manual

Gemo DT109A manual

Gemo

Gemo DT109A manual

esera 11100 quick guide

esera

esera 11100 quick guide

ESD 92 Series manual

ESD

ESD 92 Series manual

ascon M1 line manual

ascon

ascon M1 line manual

Viessmann VITOTROL 100 operating instructions

Viessmann

Viessmann VITOTROL 100 operating instructions

Nibe ECS 40 Installer manual

Nibe

Nibe ECS 40 Installer manual

Warner KilnTroller II quick guide

Warner

Warner KilnTroller II quick guide

Burkert GENERIC 8400 instruction manual

Burkert

Burkert GENERIC 8400 instruction manual

Daikin IOM 1177-1 Installation operation & maintenance

Daikin

Daikin IOM 1177-1 Installation operation & maintenance

B&B 1TT user manual

B&B

B&B 1TT user manual

netvox R718PB14 user manual

netvox

netvox R718PB14 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.