nVent RAYCHEM HWAT-ECO V5 User manual

HWAT-ECO V5(EU)
(Firmware version 1.1.3or higher)
Installation, operation and maintenance manual
HWAT-ECO V5

EN
DE
CZ
NL
FR
PL
DK
IT
ZH
1. Product overview 3
2. Installation instructions 4
3. Installation notes 9
4. Operation 11
5. Parameter settings (default) 16
6. Technical specifications 16
Appendix 21
Deutsch 22
Dansk 38
Češka 52
Français 66
Italiano 81
Nederlands 96
Polski 111
中文 126
Electrical schemes 138
2
|
nVent.com/RAYCHEM

EN
CZ
NL
DE
FR
PL
DK
IT
ZH
3. INSTALLATION NOTES
The installation and, if necessary, the maintenance and the
disassembling must be carried out by a qualified electrical installer.
The installation must be compatible with local regulations. Check the
maximum circuit length for your circuit breaker in the next table:
Maximum circuit length at VAC and for °C start-up temperature
C-characteristic circuit breaker
Multiple units on multiple power points can be used if longer heating
cables are required. We recommend to use nVent RAYCHEM HWAT-SBS
panels to operate 3, 6, 9or 12 heating circuit
Fig. 1HWAT-L HWAT-M HWAT-R
Circuit breaker (Yellow) (Orange) (Red)
C 10 A 80 m 50 m 50 m
C 13 A 110 m 65 m 65 m
C 16 A 140 m 80 m 80 m
C 20 A 180 m 100 m 100 m
The nVent RAYCHEM HWAT-ECO has a removable top lid. Both top and
bottom of the box have electronic parts and are connected to each other
by an Ethernet connector cable. The unit is delivered with top lid and
back part dismantled.
Warning: For over voltage protection (e.g. in case of thunderstorm) we
recommend the use of an external over voltage protection device.
Care and maintenance
Clean the HWAT-ECO with a soft damp cloth only, do not use any
solvents. Do not pour water directly on the device. Do not use a water
hose or a high pressure cleaner.
Description
The HWAT-ECO control unit has been developed for operation with the
self-regulating heating cables: nVent RAYCHEM HWAT-R, HWAT-M and
HWAT-L. The hot water temperature maintenance system is a comfort
system providing instant hot water at the tap. A self-regulatinga heating
cable is positioned on the pipe and compensates for any temperature
loss of the warm water.
The HWAT-ECO control unit combines the following features:
• The operating temperature of the heating cable can be limited to a
desired temperature. Combined with the integrated “power off” timer
function, this offers important energy savings.
• Energy can be saved upon activation of the “trace boiler” function
and installation of the boiler sensor. The maintain temperature of
the heating cable will automatically be lowered in case the boiler
temperature is reduced, preventing the heating cable from using too
much energy for heating the water in the pipes.
• On big warm water systems it is sufficient to programme one
HWAT-ECO unit in a nVent RAYCHEM SBS panel to manage multiple
heating circuits. The HWAT-ECO controller can be delivered in
different prefabricated panels, depending on the quantity of heating
circuits (3, 6, 9).
• An alarm terminal makes remote reading of errors possible.
• A pipe sensor (to be ordered separately) can be installed as reference
point to track and monitor pipe temperature in a large hot water
distribution network.
• The unit can be pre-programmed in power-off mode by external
power bank (to be ordered separately) connected via A-A-USB cable
and USB connection.
nVent.com/RAYCHEM
|
9

EN
DE
CZ
NL
FR
PL
DK
IT
ZH
Technical data
Product specification HWAT-R/-M/-L heating cables only
Electrical properties
Supply voltage 180-253 VAC, 50/60 Hz
Power consumption 3,5VA max
Power output relay
(heating cable) 20 A / 230 VAC
Power supply terminals 3x 6mm² max
Heating cable terminals 3x 6mm² max
Alarm terminals 3x 1,5mm² max
Sensor terminal - Boiler 2x 1,5mm² max
Sensor terminal - Pipe 2x 1,5mm² max
Alarm relay
Single pole double throw relay, volt-free,
Max. switching capacity (resistive load only)
1A/30 VDC 0.5A/125 VAC,
Max.: 60 VDC/125 VAC
Circuit breaker Max. C 20 A (C-Characteristic)
Real time clock Automatic Summer/Winter time and
Leap year correction
Clock backup 10 days
Clock accuracy A variation of ± 10 minutes per year is possible
Settings All settings are stored in non-volatile memory
Operating temperature 0°C to 40°C ambient
Selectable temperature 37°C up to 65°C in 24 blocks per day
Pre-programmes 7built-in building specific programmes, can
be edited
Enclosure
Material Polycarbonate
Dimensions 210 mm x 110 mm x 85 mm
Ingress protection class IP 54
Weight 990 g
Mounting DIN-Rail mountable 35 mm
Entries 2x M25 and 2x M20
Storage temperature –20°C to +50°C
Flammability class D category (DIN EN 60730/VDE 0631-1)
Sensor
Temperature sensor type Standard NTC 2,0KOHM at 25°C, 2wires
Sensor tip dimensions Ø 5mm; length 20 mm
Sensor cable length 3m; extendable up to 100 m , 2x 1,5mm²
Temperature range 0°C to 90°C
Sensor data 40°C 1211 Ω
45°C 1033 Ω
50°C 884 Ω
55°C 762 Ω
60°C 658 Ω
65°C 571 Ω
10
|
nVent.com/RAYCHEM

EN
CZ
NL
DE
FR
PL
DK
IT
ZH
Approval
Approval
CE, UKCA, EMC According to EN 50081-1/2
for emission and EN 50082-1/2for immunity
Temperature for bal pressure +100°C test (DIN
EN 60730/VDE 0631-1)
Rated impulse voltage: Overvoltage category III
(DIN EN 60730/ VDE 0631-1)
4. OPERATION
The HWAT-ECO version 5has a resistive touchscreen user interface:
The unit will go in dim mode after 2minutes with no interaction.
The unit will switch to the main screen after 2minutes of no-interaction
on the parameter input screens.
Quick install
When the unit is powered up for the first time, a quick setup must be
executed before the unit is ready to start. The Quick start helps to set all
important settings, the unit will go in main screen mode automatically
when done. Quick start is sufficient for normal operations. More settings
are available in the Setup menu for special installation conditions.
Programme start
Quick
start
Language
selection
Select your language from the language
menu.
Connection check
The unit is automatically executing a
connection check. It will check the heating
cable connection, boiler sensor and pipe
sensor connection.
A connection of the unit to an external
relay needs to be confirmed by the user.
Boiler sensor and pipe sensor are optional
connections. If connected, they will
automatically switch on.
Fine-tune the sensor inputs in the parameter
settings.The unit also operates in mode
without sensors.
Country
selection
Select a country in this menu. Your selection
will define the default values for time format,
pipe diameter and insulation thickness.
Date input Use the up/down arrow keys to select the
year.
Time input Use the up/down arrow keys to set
the hour and minute.
Building type
programme
The HWAT-ECO has 7default timer
programmes. Select a programme by tapping
on the corresponding box (box will turn red).
Select cable type Select the installed HWAT heating cable.
Plumbing
settings
Default values are set for selected plumbing
set values. Change the default values by
clicking on the arrow sign for each value and
enter a new value.
Heating
cable
selection
Select the type of cable used in your
installation (HWAT-L,HWAT-M,HWAT-R).
nVent.com/RAYCHEM
|
11

EN
DE
CZ
NL
FR
PL
DK
IT
ZH
Quick
start
Language
selection
Select your language from the language
menu.
Pipe
diameter
Selection range DN 15 up to DN 125.
Ambient
temperature
The ambient temperature is the temperature
inside the room where the heating cable is
installed. Use the +/– keys to select a
temperature from 10°C to 25°C. Clicking on
the “back” icon will store the value and show
it in plumbing settings. Range: from 10°C to
30°C.
Maintain
temperature
The maintain temperature is the water
temperature that you set for normal use. The
minimum temperature is 37°C or the economy
temperature, whichever is higher.
The maximum temperature depends on cable
type, pipe thickness, insulation thickness and
ambient temperature.
Economy temperature
The economy temperature is the water
temperature for periods in which the amount
of hot water used is low (at night) or high
(peak period).
Select the temperature using the +/– keys.
The minimum temperature is 37°C in the
programme Kindergarten and 41°C in the
Apartments programme. The maximum
temperature is the selected maintain
temperature.
Test
programme start
The test programme runs for 30minutes,
during which all parameters will be ignored to
check heating cable and connection on site.
You can stop the test programme at any time.
MAIN SCREEN
NOW
HOT WATER MAINTENANCE
BOILER
ECONOMY TEMP
AT 17:00
NEXT
INFO, RESET, SERVICE, TEST....
CABLE TYPE, PIPE DAIMETER,...
COUNTRY, LANGUAGES, UNITS,...
APPARTMENT, MAINTAIN, ECONOMY,....
SETTING
SYSTEM
HEATING CABLE & PIPE
GENERAL SETTINGS
WATER TEMP. & PROGRAM
INFO
TEST PROGRAM
RESET
SERVICE
STATUS
SYSTEM
SELECT LANGUAGE
SELECT COUNTRY
SELECT DATE
SELECT TIME
SELECT ALARM
GENERAL SETTING
SELECT SAVING TIME
ENGLISH
GERMANY
01.10.2017
14 : 17
OFF
ON
14 : 17
14 : 17
14 : 17
14 : 17
14 : 14
SELECT WATER TEMPERATURE
SELECT PROGRAM
PROGRAM TIMER
WATER TEMP. & PROGRAM
55°C / 50°C
14 : 17
HOTEL
SELECT CABLE TYPE
SELECT PIPE DIAMETER
SELECT INSULATION THICKNESS
SELECT AMBIENT TEMPERATURE
SELECT BOILER SENSOR
SELECT BOILER CUT-OFF TEMPS.
HWAT-M
DN 25
40 MM
20°C
ON
35/85°C
HEATING CABLE & PIPE
grey area
white area
red area
Contains 3areas:
1. Actual Maintain temperature (red area)
2. Next event temperature (grey area)
3. Hot water storage temperature
(white area- if boiler sensor is connected and active)
Additional icons for settings, relay (ON/OFF), key lock or warning will be
displayed.When Lock is “on” a password is needed to access the parameter
menus. After the correct 4number password is entered, each parameter in the
setup can be changed. The unit locks again after a 10 min. time out (no keys
pressed).
12
|
nVent.com/RAYCHEM

EN
CZ
NL
DE
FR
PL
DK
IT
ZH
SETTINGS
NOW
HOT WATER MAINTENANCE
BOILER
ECONOMY TEMP
AT 17:00
NEXT
INFO, RESET, SERVICE, TEST....
CABLE TYPE, PIPE DAIMETER,...
COUNTRY, LANGUAGES, UNITS,...
APPARTMENT, MAINTAIN, ECONOMY,....
SETTING
SYSTEM
HEATING CABLE & PIPE
GENERAL SETTINGS
WATER TEMP. & PROGRAM
INFO
TEST PROGRAM
RESET
SERVICE
STATUS
SYSTEM
SELECT LANGUAGE
SELECT COUNTRY
SELECT DATE
SELECT TIME
SELECT ALARM
GENERAL SETTING
SELECT SAVING TIME
ENGLISH
GERMANY
01.10.2017
14 : 17
OFF
ON
14 : 17
14 : 17
14 : 17
14 : 17
14 : 14
SELECT WATER TEMPERATURE
SELECT PROGRAM
PROGRAM TIMER
WATER TEMP. & PROGRAM
55°C / 50°C
14 : 17
HOTEL
SELECT CABLE TYPE
SELECT PIPE DIAMETER
SELECT INSULATION THICKNESS
SELECT AMBIENT TEMPERATURE
SELECT BOILER SENSOR
SELECT BOILER CUT-OFF TEMPS.
HWAT-M
DN 25
40 MM
20°C
ON
35/85°C
HEATING CABLE & PIPE
SYSTEM
NOW
HOT WATER MAINTENANCE
BOILER
ECONOMY TEMP
AT 17:00
NEXT
INFO, RESET, SERVICE, TEST....
CABLE TYPE, PIPE DAIMETER,...
COUNTRY, LANGUAGES, UNITS,...
APPARTMENT, MAINTAIN, ECONOMY,....
SETTING
SYSTEM
HEATING CABLE & PIPE
GENERAL SETTINGS
WATER TEMP. & PROGRAM
INFO
TEST PROGRAM
RESET
SERVICE
STATUS
SYSTEM
SELECT LANGUAGE
SELECT COUNTRY
SELECT DATE
SELECT TIME
SELECT ALARM
GENERAL SETTING
SELECT SAVING TIME
ENGLISH
GERMANY
01.10.2017
14 : 17
OFF
ON
14 : 17
14 : 17
14 : 17
14 : 17
14 : 14
SELECT WATER TEMPERATURE
SELECT PROGRAM
PROGRAM TIMER
WATER TEMP. & PROGRAM
55°C / 50°C
14 : 17
HOTEL
SELECT CABLE TYPE
SELECT PIPE DIAMETER
SELECT INSULATION THICKNESS
SELECT AMBIENT TEMPERATURE
SELECT BOILER SENSOR
SELECT BOILER CUT-OFF TEMPS.
HWAT-M
DN 25
40 MM
20°C
ON
35/85°C
HEATING CABLE & PIPE
Info General info about the unit, name, commissioning date,
firmware version, nVent contact info per country.
Test
Programme
The test programme runs for 30 minutes, during which
all parameters will be ignored to check the heating
cable and the connection on site. You can stop the test
programme at any time.
Reset
Select “Yes” to activate the Quick install menu and return
all settings to factory settings.
Quick start process restarts automatically.
Service Access for nVent SERVICE TEAM
Status
Info on current status of the control unit:
Pipe temperature
Boiler temperature
Maintain temperature
Supply voltage
Duty cycle
Power output
Max power output
Load current
Key lock
When key lock is “On”, the setup and timer menus are
protected by password. To unlock the unit, enter the
predefined password (3000). The unit will automatically
lock itself after 10 mins of inactivity or when Lock “On”
key is pressed. To deactivate the Key lock, press “OFF”.
nVent.com/RAYCHEM
|
13

EN
DE
CZ
NL
FR
PL
DK
IT
ZH
HEATING CABLE & PIPE
NOW
HOT WATER MAINTENANCE
BOILER
ECONOMY TEMP
AT 17:00
NEXT
INFO, RESET, SERVICE, TEST....
CABLE TYPE, PIPE DAIMETER,...
COUNTRY, LANGUAGES, UNITS,...
APPARTMENT, MAINTAIN, ECONOMY,....
SETTING
SYSTEM
HEATING CABLE & PIPE
GENERAL SETTINGS
WATER TEMP. & PROGRAM
INFO
TEST PROGRAM
RESET
SERVICE
STATUS
SYSTEM
SELECT LANGUAGE
SELECT COUNTRY
SELECT DATE
SELECT TIME
SELECT ALARM
GENERAL SETTING
SELECT SAVING TIME
ENGLISH
GERMANY
01.10.2017
14 : 17
OFF
ON
14 : 17
14 : 17
14 : 17
14 : 17
14 : 14
SELECT WATER TEMPERATURE
SELECT PROGRAM
PROGRAM TIMER
WATER TEMP. & PROGRAM
55°C / 50°C
14 : 17
HOTEL
SELECT CABLE TYPE
SELECT PIPE DIAMETER
SELECT INSULATION THICKNESS
SELECT AMBIENT TEMPERATURE
SELECT BOILER SENSOR
SELECT BOILER CUT-OFF TEMPS.
HWAT-M
DN 25
40 MM
20°C
ON
35/85°C
HEATING CABLE & PIPE
Selection of
parameters
Every parameter line shows the actual value /attribute for
each parameter.
HWAT cable Select the type of cable used in your installation
(HWAT-L, HWAT-M, HWAT-R).
Pipe
diameter
Set the pipe diameter. You can change the value from DN
15 mm up to DN 125.
Insulation
thickness
Set the insulation thickness. You can change the value
from 9to 130 mm, with the pipe diameter as the limiting
value.
Boiler sensor
Activate/deactivate a connected boiler sensor by clicking
on ON/OFF. The external temperature sensor measures
the boiler temperature. The trace boiler setting is
included to ensure that the heating cable temperature
does not exceed the boiler temperature. The HWAT-ECO
memorizes the highest measured temperature over
the last 24 hours. If the boiler temperature is too low,
the maximum temperature is lowered to the boiler
temperature minus the trace temperature. In this case
the green trace boiler LED will be on.
Boiler low
temperature
limit
You can determine the low temperature limit. If the
boiler temperature reaches this value, the unit will
switch off the heating system in order to fulfil hygienic
requirements and avoid energy waste.
Boiler high
temperature
limit
You can determine the high temperature limit.
If this value is reached the unit will switch off
the heating system to avoid scalding.
Pipe sensor
Activate/deactivate a connected pipe sensor by pressing
ON/OFF. The pipe sensor monitors the pipe temperature
and needs to be installed close to the furthest point in
the pipe distribution network.
Pipe sensor
low
temperature
limit
You can determine the low temperature limit.
When the value is reached a warning will appear on the
screen but will not interrupt the unit’s functioning. The
info status screen will show the actual pipe temperature.
Pipe sensor
high
temperature
limit
You can determine the high temperature limit. A warning
will appear on the screen when the value is reached but
will not interrupt the unit’s functioning.
14
|
nVent.com/RAYCHEM

EN
CZ
NL
DE
FR
PL
DK
IT
ZH
GENERAL SETTINGS
NOW
HOT WATER MAINTENANCE
BOILER
ECONOMY TEMP
AT 17:00
NEXT
INFO, RESET, SERVICE, TEST....
CABLE TYPE, PIPE DAIMETER,...
COUNTRY, LANGUAGES, UNITS,...
APPARTMENT, MAINTAIN, ECONOMY,....
SETTING
SYSTEM
HEATING CABLE & PIPE
GENERAL SETTINGS
WATER TEMP. & PROGRAM
INFO
TEST PROGRAM
RESET
SERVICE
STATUS
SYSTEM
SELECT LANGUAGE
SELECT COUNTRY
SELECT DATE
SELECT TIME
SELECT ALARM
GENERAL SETTING
SELECT SAVING TIME
ENGLISH
GERMANY
01.10.2017
14 : 17
OFF
ON
14 : 17
14 : 17
14 : 17
14 : 17
14 : 14
SELECT WATER TEMPERATURE
SELECT PROGRAM
PROGRAM TIMER
WATER TEMP. & PROGRAM
55°C / 50°C
14 : 17
HOTEL
SELECT CABLE TYPE
SELECT PIPE DIAMETER
SELECT INSULATION THICKNESS
SELECT AMBIENT TEMPERATURE
SELECT BOILER SENSOR
SELECT BOILER CUT-OFF TEMPS.
HWAT-M
DN 25
40 MM
20°C
ON
35/85°C
HEATING CABLE & PIPE
Language Choose your language from the language menu.
Country
Select a country in this menu. Your selection defines
the default values used for time format, pipe diameter
and insulation thickness.
Date
Use the up/down arrow keys to select the year.
After a power break of more than 15 days you need to
re-enter the date.
Time
Use up/down arrow keys to set hour and minute.
After a power break of more than 15 days you need to
re-enter the time.
Alarm tone
An alarm will go off inside the unit indicating an error
condition. Activate/deactivate the alarm by pressing ON/
OFF. Note: Alarm messages and an alarm signal will be
created any time in case of a malfunction.
WATER TEMP. & PROGRAMMING
NOW
HOT WATER MAINTENANCE
BOILER
ECONOMY TEMP
AT 17:00
NEXT
INFO, RESET, SERVICE, TEST....
CABLE TYPE, PIPE DAIMETER,...
COUNTRY, LANGUAGES, UNITS,...
APPARTMENT, MAINTAIN, ECONOMY,....
SETTING
SYSTEM
HEATING CABLE & PIPE
GENERAL SETTINGS
WATER TEMP. & PROGRAM
INFO
TEST PROGRAM
RESET
SERVICE
STATUS
SYSTEM
SELECT LANGUAGE
SELECT COUNTRY
SELECT DATE
SELECT TIME
SELECT ALARM
GENERAL SETTING
SELECT SAVING TIME
ENGLISH
GERMANY
01.10.2017
14 : 17
OFF
ON
14 : 17
14 : 17
14 : 17
14 : 17
14 : 14
SELECT WATER TEMPERATURE
SELECT PROGRAM
PROGRAM TIMER
WATER TEMP. & PROGRAM
55°C / 50°C
14 : 17
HOTEL
SELECT CABLE TYPE
SELECT PIPE DIAMETER
SELECT INSULATION THICKNESS
SELECT AMBIENT TEMPERATURE
SELECT BOILER SENSOR
SELECT BOILER CUT-OFF TEMPS.
HWAT-M
DN 25
40 MM
20°C
ON
35/85°C
HEATING CABLE & PIPE
Maintain /
Economy
temperature
The maintain temperature is the water temperature that
you set for normal use. The minimum temperature is
37°C or the economy temperature, whichever is higher.
The maximum temperature depends on cable type, pipe
thickness, insulation thickness and ambient temperature.
The economy temperature is the water temperature for
periods in which the amount of hot water used is low
(at night) or high (peak period). Select the temperature
using the +/– keys. The minimum temperature is 37°C in
the programme Kindergarten and 41°C in the Apartments
programme. The maximum temperature is the selected
maintain temperature.
Building type
programme
The HWAT-ECO has 7default timer programmes. Select
by tapping on the programme of choice (box will turn
red).
See figure 6.1for the schedule of each programme.
The building programme reflects the tapping profiles.
nVent.com/RAYCHEM
|
15

EN
DE
CZ
NL
FR
PL
DK
IT
ZH
Timer
schedule
Graphically programme the Timer in 1hour time blocks.
You can set a block to OFF, Economy temp,
Maintain temp, or HEAT-UP*
OFF MAINTAIN HEAT- UPECONOMY
(*HEAT-UP=100% power, only when using the HWAT-R
cable. This is the legionella prevention mode and it is not
pre-programmed. Activate this preferably during night
hours to avoid scalding.
Use the modes button to overwrite the timer schedule.
Select a temperature mode to assign to the time bock
of choice.
5. PARAMETER SETTINGS (DEFAULT)
Language English
Country Not pre-defined; to be selected
Date 01/01/2017 or last saved date
Time 00:00; or last saved time
Building programme Not pre-defined; to be selected
Heating cable type Not pre-defined/ to be selected
Pipe diameter DN25
Insulation thickness 30 mm
Ambient temperature 20°C
Maintain temperature 55°C
Economy temperature 50°C
Low temperature limit 40°C
High temperature limit 65°C
Low temperature alarm OFF
High temperature alarm ON
Alarm sound ON
Key lock OFF
6. TECHNICAL SPECIFICATIONS
Building programme schedule
Apartments
HEAT-UP
TIME IN HOUR
APARTMENT WEEKDAY
MON
09:31
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
16
|
nVent.com/RAYCHEM

EN
CZ
NL
DE
FR
PL
DK
IT
ZH
Hospital Weekday & Weekend
HEAT-UP
TIME IN HOUR
HOSPITAL WEEKDAY 10:30
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
HEAT-UP
TIME IN HOUR
SPORT CENTER WEEKDAY 10:29
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
TIME IN HOUR
NURSING HOSPITAL WEEKDAY 10:31
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
TIME IN HOUR
OFFICE WEEKDAY 10:29
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
20
17
06 08 10
TIME IN HOUR
CONSTANT WEEKDAY 10:31
00 01 02 03 04
21 22 2312 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
HEAT-UP
TIME IN HOUR
HOTEL WEEKDAY 10:29
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
HEAT-UP
TIME IN HOUR
OFFICE WEEKEND 10:29
00 01 02 03 04 05 06 07 08 09 10 11
12 13 14 15 16 17 18 19 20 21 22 23
HEAT-UP
TIME IN HOUR
PRISON WEEKDAY 10:30
00 01 02 03 04
21 22 23
12 13 14 15 18 19
05 07 09 11
2017
06 08 10
16
Hotel Weekday & Weekend
HEAT-UP
TIME IN HOUR
HOSPITAL WEEKDAY 10:30
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
HEAT-UP
TIME IN HOUR
SPORT CENTER WEEKDAY 10:29
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
TIME IN HOUR
NURSING HOSPITAL WEEKDAY 10:31
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
TIME IN HOUR
OFFICE WEEKDAY 10:29
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
20
17
06 08 10
TIME IN HOUR
CONSTANT WEEKDAY 10:31
00 01 02 03 04
21 22 2312 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
HEAT-UP
TIME IN HOUR
HOTEL WEEKDAY 10:29
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
HEAT-UP
TIME IN HOUR
OFFICE WEEKEND 10:29
00 01 02 03 04 05 06 07 08 09 10 11
12 13 14 15 16 17 18 19 20 21 22 23
HEAT-UP
TIME IN HOUR
PRISON WEEKDAY 10:30
00 01 02 03 04
21 22 23
12 13 14 15 18 19
05 07 09 11
2017
06 08 10
16
Nursing home Weekday & Weekend
HEAT-UP
TIME IN HOUR
HOSPITAL WEEKDAY 10:30
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
HEAT-UP
TIME IN HOUR
SPORT CENTER WEEKDAY 10:29
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
TIME IN HOUR
NURSING HOSPITAL WEEKDAY 10:31
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
TIME IN HOUR
OFFICE WEEKDAY 10:29
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
20
17
06 08 10
TIME IN HOUR
CONSTANT WEEKDAY 10:31
00 01 02 03 04
21 22 2312 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
HEAT-UP
TIME IN HOUR
HOTEL WEEKDAY 10:29
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
HEAT-UP
TIME IN HOUR
OFFICE WEEKEND 10:29
00 01 02 03 04 05 06 07 08 09 10 11
12 13 14 15 16 17 18 19 20 21 22 23
HEAT-UP
TIME IN HOUR
PRISON WEEKDAY 10:30
00 01 02 03 04
21 22 23
12 13 14 15 18 19
05 07 09 11
2017
06 08 10
16
Office Weekday
HEAT-UP
TIME IN HOUR
HOSPITAL WEEKDAY 10:30
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
HEAT-UP
TIME IN HOUR
SPORT CENTER WEEKDAY 10:29
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
TIME IN HOUR
NURSING HOSPITAL WEEKDAY 10:31
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
TIME IN HOUR
OFFICE WEEKDAY 10:29
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
20
17
06 08 10
TIME IN HOUR
CONSTANT WEEKDAY 10:31
00 01 02 03 04
21 22 2312 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
HEAT-UP
TIME IN HOUR
HOTEL WEEKDAY 10:29
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
HEAT-UP
TIME IN HOUR
OFFICE WEEKEND 10:29
00 01 02 03 04 05 06 07 08 09 10 11
12 13 14 15 16 17 18 19 20 21 22 23
HEAT-UP
TIME IN HOUR
PRISON WEEKDAY 10:30
00 01 02 03 04
21 22 23
12 13 14 15 18 19
05 07 09 11
2017
06 08 10
16
nVent.com/RAYCHEM
|
17

EN
DE
CZ
NL
FR
PL
DK
IT
ZH
Weekend
HEAT-UP
TIME IN HOUR
HOSPITAL WEEKDAY 10:30
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
HEAT-UP
TIME IN HOUR
SPORT CENTER WEEKDAY 10:29
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
TIME IN HOUR
NURSING HOSPITAL WEEKDAY 10:31
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
TIME IN HOUR
OFFICE WEEKDAY 10:29
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
20
17
06 08 10
TIME IN HOUR
CONSTANT WEEKDAY 10:31
00 01 02 03 04
21 22 2312 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
HEAT-UP
TIME IN HOUR
HOTEL WEEKDAY 10:29
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
HEAT-UP
TIME IN HOUR
OFFICE WEEKEND 10:29
00 01 02 03 04 05 06 07 08 09 10 11
12 13 14 15 16 17 18 19 20 21 22 23
HEAT-UP
TIME IN HOUR
PRISON WEEKDAY 10:30
00 01 02 03 04
21 22 23
12 13 14 15 18 19
05 07 09 11
2017
06 08 10
16
Prison
HEAT-UP
TIME IN HOUR
HOSPITAL WEEKDAY 10:30
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
HEAT-UP
TIME IN HOUR
SPORT CENTER WEEKDAY 10:29
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
TIME IN HOUR
NURSING HOSPITAL WEEKDAY 10:31
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
TIME IN HOUR
OFFICE WEEKDAY 10:29
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
20
17
06 08 10
TIME IN HOUR
CONSTANT WEEKDAY 10:31
00 01 02 03 04
21 22 2312 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
HEAT-UP
TIME IN HOUR
HOTEL WEEKDAY 10:29
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
HEAT-UP
TIME IN HOUR
OFFICE WEEKEND 10:29
00 01 02 03 04 05 06 07 08 09 10 11
12 13 14 15 16 17 18 19 20 21 22 23
HEAT-UP
TIME IN HOUR
PRISON WEEKDAY 10:30
00 01 02 03 04
21 22 23
12 13 14 15 18 19
05 07 09 11
2017
06 08 10
16
Sport center Weekday & Weekend
HEAT-UP
TIME IN HOUR
HOSPITAL WEEKDAY 10:30
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
HEAT-UP
TIME IN HOUR
SPORT CENTER WEEKDAY 10:29
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
TIME IN HOUR
NURSING HOSPITAL WEEKDAY 10:31
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
TIME IN HOUR
OFFICE WEEKDAY 10:29
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
20
17
06 08 10
TIME IN HOUR
CONSTANT WEEKDAY 10:31
00 01 02 03 04
21 22 2312 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
HEAT-UP
TIME IN HOUR
HOTEL WEEKDAY 10:29
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
HEAT-UP
TIME IN HOUR
OFFICE WEEKEND 10:29
00 01 02 03 04 05 06 07 08 09 10 11
12 13 14 15 16 17 18 19 20 21 22 23
HEAT-UP
TIME IN HOUR
PRISON WEEKDAY 10:30
00 01 02 03 04
21 22 23
12 13 14 15 18 19
05 07 09 11
2017
06 08 10
16
Constant mode
HEAT-UP
TIME IN HOUR
HOSPITAL WEEKDAY 10:30
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
HEAT-UP
TIME IN HOUR
SPORT CENTER WEEKDAY 10:29
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
TIME IN HOUR
NURSING HOSPITAL WEEKDAY 10:31
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
TIME IN HOUR
OFFICE WEEKDAY 10:29
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
20
17
06 08 10
TIME IN HOUR
CONSTANT WEEKDAY 10:31
00 01 02 03 04
21 22 2312 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
HEAT-UP
TIME IN HOUR
HOTEL WEEKDAY 10:29
00 01 02 03 04
21 22 23
12 13 14 15 16 18 19
05 07 09 11
2017
06 08 10
HEAT-UP
TIME IN HOUR
OFFICE WEEKEND 10:29
00 01 02 03 04 05 06 07 08 09 10 11
12 13 14 15 16 17 18 19 20 21 22 23
HEAT-UP
TIME IN HOUR
PRISON WEEKDAY 10:30
00 01 02 03 04
21 22 23
12 13 14 15 18 19
05 07 09 11
2017
06 08 10
16
18
|
nVent.com/RAYCHEM

EN
CZ
NL
DE
FR
PL
DK
IT
ZH
Error/Alarms and Troubleshooting
Error
No.
Warning
message Problem causes Corrective actions
E:1FOLLOW
BOILER
Hotwater storage
temperature
decreases by 5K vs.
maintain
temperature
Connect sensor to HWAT-ECO
or set
programme water
heater sensor to OFF.
Check sensor
connections.
Replace sensor.
E:2.1BOILER
SENSOR OPEN
Sensor not
connected or broken See E.1.
E:2.2
BOILER
SENSOR
SHORT
Sensor short See E.1.
E:2.3PIPE SENSOR
OPEN
Sensor not
connected or broken See E.1.
E:2.4PIPE SENSOR
SHORT Sensor short See E.1.
E:3.1PIPE TEMP
HIGH
Water pipe
temperature
too high
Will pop up if
Temperature sensor
is higher than the
maximum exposure
temperature of the
HWAT cable: HWAT-M
(65°C), HWAT-R
(85°C)
Water heater sensor
failure. Sensor has not
been installed. Sensor
or sensor cable defect
(only when water
heater sensor “On” is
selected)
Check Sensor and Boiler
temperature
E:3.2BOILER TEMP
HIGH
Water heater
temperature too high
Will pop up if
Temperature sensor
is higher than the
maximum exposure
temperature of the
HWAT cable: HWAT-M
(65°C), HWAT-R
(85°C)
Check Sensor and Boiler
temperature
E:4.1BOILER TEMP
LOW
Water heater
temperature is lower
than maintain
temperature set point
of the HWAT-ECO
Check water heater
temperature (also indicated in
INFO of HWAT-ECO menu) Check
maintain temperature setting at
HWAT-ECO. Check temperature
sensor mounting
E:4.2PIPE TEMP
LOW
Water heater
temperature is lower
than maintain
temperature set point
of the HWAT-ECO
Check water heater temperature
(also indicated in INFO of
HWAT-ECO menu).
Check maintain temperature
setting at HWAT-ECO. Check
temperature sensor mounting
nVent.com/RAYCHEM
|
19

EN
DE
CZ
NL
FR
PL
DK
IT
ZH
Error
No.
Warning
message Problem causes Corrective actions
E:5
HEATING
CABLE
DISCONNECT
Low or no current.
alarm No current
measured when the
circuit should be on.
Confirm that heating cable is
connected to the controller.
E:6.1INTERNAL
ERROR Internal error
Disconnect HWAT-ECO controller
and replace unit. When reporting
this error, provide the exact error
number, cable type, cable length
and the setpoint temperature.
E:6.2INTERNAL
ERROR Internal error
Disconnect HWAT-ECO controller
and replace unit. When reporting
this error, provide the exact error
number, cable type, cable length
and the setpoint temperature.
E:6.3INTERNAL
ERROR Internal error
Disconnect HWAT-ECO controller
and replace unit. When reporting
this error, provide the exact error
number, cable type, cable length
and the setpoint temperature.
E:6.4INTERNAL
ERROR Internal error
Disconnect HWAT-ECO controller
and replace unit. When reporting
this error, provide the exact error
number, cable type, cable length
and the setpoint temperature.
E:6.5INTERNAL
ERROR Internal error
Disconnect HWAT-ECO controller
and replace unit. When reporting
this error, provide the exact error
number, cable type, cable length
and the setpoint temperature.
E:6.6INTERNAL
ERROR Internal error
If you are using low noise,
humfree contactor, replace it with
the non-humfree contactor. If this
does not help, then disconnect
HWAT-ECO controller and replace
unit. When reporting this error,
provide the exact error number,
cable type, cable length and the
setpoint temperature.
E:7PLAUSIBILITY
CHECK Check parameter settings
Water
temperature
too low
Water heating cable
temperature is too
low
Installed heating
cable is different
from the programme
selected
Insulation thickness
deviates from the
required insulation
thickness.The
ambient temperature
value entered is too
high
Check water heater temperature
and timer programme.
Change heating cable type in
HWAT-ECO (can only be done in
Quick start).
Adjust power correction factor.
Change value of ambient
temperature.
See 4.2
20
|
nVent.com/RAYCHEM
Table of contents
Languages:
Other nVent RAYCHEM Controllers manuals

nVent RAYCHEM
nVent RAYCHEM 460 User manual

nVent RAYCHEM
nVent RAYCHEM Raystat V5 User manual

nVent RAYCHEM
nVent RAYCHEM TCONTROL-CONT-03 Specification sheet

nVent RAYCHEM
nVent RAYCHEM PCN 1244-021970 User manual

nVent RAYCHEM
nVent RAYCHEM Elexant 450c User manual

nVent RAYCHEM
nVent RAYCHEM Elexant 450c User manual

nVent RAYCHEM
nVent RAYCHEM 465 User manual

nVent RAYCHEM
nVent RAYCHEM NGC-40-SLIM User manual