manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Siemens
  6. •
  7. Controllers
  8. •
  9. Siemens RVP550 User manual

Siemens RVP550 User manual

Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 1/28
74 319 0312 0
G2488
en Installation Instructions Energy Manager / Heating Controller RVP540
RVP550
Installation
Place of installation
•In a dry room, e.g. the boiler room
•Installation choices:
- Control panel (in the panel front, on the inner wall, or
on a DIN rail)
- Control cabinet
- Sloping front of a control desk
•Permissible ambient temperature: 0...50 °C
Electrical installation
•The local regulations for electrical installations must
be complied with
•Cable strain relief must be ensured
•Cables from the controller to the actuators and
pumps carry mains voltage
•Sensor cables should not be run parallel to mains car-
rying cables
•To protect the solar collector sensor from voltage
surges (caused by lightning for example), the separately
available conduit box for overvoltage protection
(AGS2S.200/109) should be installed
Permissible cable lengths
•For all sensors, thermostats and external contacts:
Copper cable 0.6 mm dia. max. 20 m
Copper cable 1.0 mm2max. 80 m
Copper cable 1.5 mm2max. 120 m
•For room units:
Copper cable 0.25 mm2max. 25 m
Copper cable 0.5 mm2max. 50 m
•For the data bus:
0.75...2.5 mm2according to Data Sheets
N2030E and N2032E
Mounting and wiring the base
Wall mounting
1. Separate base from the controller.
2. Hold base against the wall. Marking TOP must be at
the top!
3. Mark fixing holes on the wall.
4. Drill holes.
5. If required, knock out holes on the base for the cable
entry glands.
6. Screw base to the wall.
7. Wire up the base.
DIN rail mounting
1. Fit rail.
2. Separate base from the controller.
3. If required, knock out holes on the base for the cable
entry glands.
4. Fit base to the rail. Marking TOP must be at the top!
5. If required, secure the base (depending on the type of
rail).
6. Wire up the base.
Flush panel mounting
•Panel cutout required: 92 x 138 mm
•Maximum thickness: 3 mm
1. Separate base from the controller.
2. If required, knock out holes on the base for the cable
entry glands.
3. Insert base in the panel cutout from behind until stop
is reached. Marking TOP must be at the top!
4. Push lateral tongues behind the front panel (refer to
illustration below).
2462Z06
Wrong Correct
Place tongues on both sides correctly – they may not be
located inside the cutout!
5. Wire up the base. Make sure the cable lengths are
such that there is sufficient space to open the control
panel door.
Commissioning
Preparatory checks
1. DO NOT switch on power yet.
2. Check wiring according to the plant connection diagram.
3. Ensure correct position and location of the levers by
turning the fixing screws (refer to illustration on the lat-
eral wall of the unit).
2522Z13
4. Insert controller in the base until stop is reached.
Marking TOP must be at the top!
5. Tighten fixing screws alternately.
6. Check the motorized valves: See if
−they are correctly installed (observe direction of flow
as indicated on the valve body)
−the manual lever is disengaged.
7. Note with underfloor and ceiling heating systems:
The limit thermostat must be correctly adjusted. During
the functional test, the flow temperature may not ex-
ceed the maximum permissible level (usually 55 °C). If
it does, proceed immediately as follows:
- Either close the valve manually, or
- Switch off the pump, or
- Close the pump isolating valve
2/28 19.08.2002 74 319 0312 0 a Siemens Building Technologies / HVAC Products
8. Switch on power. The display must show something
(e.g. time of day). If not, the reason may be one of the
following:
- No mains voltage
- Main fuse blown
- Mains isolator or main switch not set to ON
9. If one of the operating mode buttons flashes, a room
unit or contact H1 overrides the controller. Select op-
erating mode on the room unit; switch off contact
H1.
General information about operation
•Setting elements:
−Setting knob
−Display; an operating line is assigned to each setting
−Buttons for selecting and adjusting setting values:
Next operating line below
Next operating line above
Decrease the displayed value
Increase the displayed value
•Adopting a setting value:
The setting value is adopted by selecting the next op-
erating line (or by pressing one of the operating mode
buttons)
•Entering --.- / --:-- / --- (deactivating a function):
Keep or depressed until the required display
appears
•Block jump function:
To select a single operating line quickly, 2 button
combinations can be used:
Press and to select the next line block above.
Press and to select the next line block below.
Setting procedure
1. Make settings on the operating lines according to the
instructions provided by your local Siemens HVAC
Products sales office.
2. Select plant type on operating line 100.
3. Make the required settings on the controller. All func-
tions and operating lines required for the selected type
of plant will be activated and can be set. Operating
lines that are not used will be hidden.
4. Enter the adjusted values in the table!
5. Set the general functions (independent of the type of
plant).
Commissioning and functional check
•Specific operating lines for the functional check:
200 = output test
201 = input test
296 = functional test oil- / gas-fired boiler
345 = functional test solar
395 = functional test wood-fired boiler
545 = functional test d.h.w. storage tank
745 = functional test heating circuit
888 = output test P1
894 = output test Ux
•If Er (ERROR) appears on the display: Refer to operating
line 50 to find the fault
Operating elements
Room temperature setpoint knob
Adjustment of nominal room temperature setpoint
Setting buttons
Parameter settings (+ / -)
Operating line selection buttons (Prog)
Selection of parameters / switching operating lines
Display
Showing actual values and settings
Operating mode buttons heating circuit
Operating mode changes to:
Automatic operation
Continuous operation
Standby
Operating mode button d.h.w.
D.h.w. heating ON / OFF
Manual d.h.w. push
Function button with LED for manual operation
Manual operation ON / OFF
8Green button with signal lamp
Green operation ON / OFF
9Info button
Display of plant values
10 Connection facility for PC tool
Diagnostics and service with OCI69 / ACS69
An illuminated button or signal lamp indicates that the
relevant function is activated.
C
0 4 8 12 16 20 24
1 2 3 4 5 6 7 8 9 10
°C
20
26
14
Info
RVP540
6
5
4
1
78 9
2392Z54a
10
32
Front of RVP540 and RVP550
Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 3/28
Connection diagrams
Markings of connection terminal on the low-voltage side
Termi-
nal
Terminals Termi-
nal
Terminals
M Ground H1 Input H1 (contact or DC 0…10 V)
Ux Output DC 0…10 V B104 Temperature sensor
P1 PWM output B103 Temperature sensor
B109 Temperature sensor M Ground sensors
M Ground sensors B102 Temperature sensor
B108 Temperature sensor B101 Temperature sensor NTC / LG-Ni 1000
with automatic identification
B107 Temperature sensor MD Ground PPS (room unit, BMU)
B106 Temperature sensor A6 Data PPS (room unit, BMU)
M Ground sensors MB Ground bus (LPB)
B105 Temperature sensor DB Data bus (LPB)
Markings of connection terminal on the mains voltage side
Termi-
nal
Terminals Termi-
nal
Terminals
Q110 Multifunctional output Q104 Multifunctional output
Q109 Multifunctional output Q103 Multifunctional output
F3 Phase Q109 / Q110 F1 Phase Q103 / Q104
F7 Phase Q108 E1 AC 230 V input
Q108 Multifunctional output Q102 Multifunctional output
Q107 Multifunctional output F5 Phase Q102
F6 Phase Q107 Q101 Multifunctional output
Q106 Multifunctional output F4 Phase Q101
Q105 Multifunctional output L Live conductor AC 230 V
F2 Phase Q105 / Q106 N Neutral conductor
Electrical connections
2392A03
M
B108
M
B105
H1
B104
B103
M
B106
B101
MD
A6
MB
DB
F2
N
Q105
Q106
F6
Q107
L
F4
Q101
F5
Q102
E1
F1
Q103
B107
Q104
B102
B109
Ux
M
Q108
F7
F3
Q109
Q110
P1
N
N
LPB
D1 D2
4/28 19.08.2002 74 319 0312 0 a Siemens Building Technologies / HVAC Products
Selection
Selecting the plant type:
Select the required type of plant (basic diagram number) on operating line 100 (refer to page 8). The selection activates all
functions that are required for the specific plant and shows the operating lines needed.
In addition, operating parameters 120 through 173 will be set to their default values required for the basic plant.
During the setting procedure, the basic diagram number on the display flashes. The required number must be confirmed by
pressing the + / - buttons twice for 3 seconds. Then, the basic diagram number will stop flashing.
Example:
2392a04
048 12162024
123456789
10
Plant type
The basic plant diagram for the required type of plant and additional setting information will be provided by your local
Siemens Building Technologies / HVAC Products sales office.
Designations of relays and sensors
The relay designations used in the supplied basic diagram have the following meaning:
Relays Function (use) Relays Function (use)
K1 Heat pump stage 1 Y7 Maintained boiler return temperature, oil / gas
OPEN
K2 Heat pump stage 2 Y8 Maintained boiler return temperature, oil / gas
CLOSED
K3 Release of external wood-fired boiler Y9 Maintained boiler return temperature, wood OPEN
K4 Oil- / gas-fired boiler, stage 1 Y10 Maintained boiler return temperature, wood
CLOSED
K5 Oil- / gas-fired boiler, stage 2 Y14 Diverting valve partial storage tank charging
K6 Electric immersion heater for d.h.w. Y¯14 Inverted Y14 signal
K8 Solar collector pump or diverting valve heat exchanger 2 Y15 Diverting valve for return
K¯8 Inverted K8 signal Y¯15 Inverted Y15 signal
K9 Solar bypass valve or heat exchanger pump Q1 Boiler pump of oil- / gas-fired boiler
K¯9 Inverted K9 signal Q2 Heating circuit pump
K10 Alarm output Q3 D.h.w. charging pump
K11 Overtemperature protection Q¯3 Inverted Q3 signal
K¯11 Inverted K11 signal Q4 D.h.w. circulating pump
K12 Solar collector pump or diverting valve heat exchanger 1 Q5 Solar collector pump 1
K13 Output K13 for free time switch program Q9 Heat pump circulator
K14 Release of external oil- / gas-fired boiler Q10 Pump of wood-fired boiler
K15 Release of external heat pump Q11 Storage tank heat transfer pump
K16 Electric immersion heater for buffer storage tank Q12 Oil / gas bypass pump
K17 Flue gas temperature sensor function Q13 D.h.w. storage tank heat transfer pump
K18 Output for solar swimming pool heating Q14 System pump
K¯18 Inverted K18 signal Q15 Pump H1
Y1 Heating circuit mixing valve OPEN Q16 Solar collector pump 2
Y2 Heating circuit mixing valve CLOSED Q17 Additional pump Q17 for heat pump stage 2
Y3 Diverting valve d.h.w. E1 Mains input
Y4 Heat generation lock L Live conductor (mains connection)
Y¯4 Inverted Y4 signal N Neutral conductor (mains connection)
Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 5/28
Sensor designations
The sensor designations used in the supplied basic diagram have the following meaning:
Sensor Function (use) Types of
sensors
Sensor Function (use) Types of sen-
sors
B1 Heating circuit flow sensor LG-Ni 1000 B7 Return sensor oil / gas LG-Ni 1000
B2 Sensor of oil- / gas-fired boiler LG-Ni 1000 B71 Return sensor heat pump LG-Ni 1000
B21 Heat pump flow sensor LG-Ni 1000 B72 Return sensor wood LG-Ni 1000
B22 Sensor of wood-fired boiler LG-Ni 1000 B73 Return sensor heating circuit LG-Ni 1000
B3 D.h.w. sensor 1 LG-Ni 1000 B8 Flue gas sensor Pt 1000
B31 D.h.w. sensor 2 LG-Ni 1000 B9 Outside sensor LG-Ni 1000
NTC 600
B32 D.h.w. sensor 3 LG-Ni 1000 B10 Common flow sensor LG-Ni 1000
B33 D.h.w. sensor 4 LG-Ni 1000 B13 Sensor for solar swimming pool
heating
LG-Ni 1000
B4 Buffer storage tank sensor 1 LG-Ni 1000 M Ground sensors H1, U1, P1 –
B41 Buffer storage tank sensor 2 LG-Ni 1000 H1 Contact or DC 0…10 V input –
B42 Buffer storage tank sensor 3 LG-Ni 1000 U1 DC 0…10 V output –
B43 Buffer storage tank sensor 4 LG-Ni 1000 P1 PWM output –
B6 Solar collector sensor 1 LG-Ni 1000 /
Pt 1000
A6 PPS data –
B61 Solar collector sensor 2 LG-Ni 1000 /
Pt 1000
MD PPS ground –
B62 Solar collector flow sensor DB LPB data
B63 Solar flow sensor for yield measurement LG-Ni 1000 MB LPB ground
B64 Solar return sensor for yield measure-
ment
LG-Ni 1000 –
Parameter list
Settings to be made on the «Enduser» level
Settings that meet individual enduser needs.
Buttons Explanation Line
1Press one of the operating line selection buttons.
This will take you directly to programming mode “Enduser“.
2Press the operating line selection buttons to select the required operating line.
The following parameter list contains all settings that can be made. • • •
3Press the + or – button to set the required value.
The setting will be stored as soon as you leave the programming mode or
change to another line.
4To leave programming mode “Enduser“, press any of the operating mode but-
tons.
èNote:
If no button is pressed for about 8 minutes, the controller will automatically re-
turn to the operating mode selected last.
Continu-
ous
display
6/28 19.08.2002 74 319 0312 0 a Siemens Building Technologies / HVAC Products
Overview of the enduser parameters
Line Function Range Unit Resolution Factory
setting
Setting the clock
1 Time of day 00:00...23:59 h / min .... : .... –
2 Weekday 1...7 Day ...... day –
3 Date 01.01...31.12 Day /
month
.... : .... –
4 Year 2001...2094 Year ...... year –
Time switch program for the heating circuit
5 Weekday – preselection heating circuit
1-7 7-day block
1...7 Individual days
1-7 / 1...7 Day ...... day –
6 Switch-on time 1st period heating circuit 00:00...24:00 h / min .... : ....
h / min
06:00
7 Switch-off time 1st period heating circuit 00:00...24:00 h / min .... : ....
h / min
22:00
8 Switch-on time 2nd period heating circuit 00:00...24:00 h / min .... : ....
h / min
- -:- -
9 Switch-off time 2nd period heating circuit 00:00...24:00 h / min .... : ....
h / min
- -:- -
10 Switch-on time 3rd period heating circuit 00:00...24:00 h / min .... : ....
h / min
- -:- -
11 Switch-off time 3rd period heating circuit 00:00...24:00 h / min .... : ....
h / min
- -:- -
Free time switch program
12 Weekday – preselection free time switch program
1-7 7-day lock
1...7 Individual days
1-7 / 1...7 Day ...... day –
13 Switch-on time 1st period free time switch pr. 00:00...24:00 h / min .... : ....
h / min
06:00
14 Switch-off time 1st period free time switch pr. 00:00...24:00 h / min .... : ....
h / min
22:00
15 Switch-on time 2nd period free time switch pr. 00:00...24:00 h / min .... : ....
h / min
- -:- -
16 Switch-off time 2nd period free time switch pr. 00:00...24:00 h / min .... : ....
h / min
- -:- -
17 Switch-on time 3rd period free time switch pr. 00:00...24:00 h / min .... : ....
h / min
- -:- -
18 Switch-off time 3rd period free time switch pr. 00:00...24:00 h / min .... : ....
h / min
- -:- -
Time switch program for d.h.w. heating
19 Weekday – preselection d.h.w.
1-7 7-day block
1...7 Individual days
1-7 / 1...7 Day ...... day –
20 Switch-on time 1st period d.h.w. 00:00...24:00 h / min .... : ....
h / min
06:00
21 Switch-off time 1st period d.h.w. 00:00...24:00 h / min .... : ....
h / min
22:00
22 Switch-on time 2nd period d.h.w. 00:00...24:00 h / min .... : ....
h / min
- -:- -
23 Switch-off time 2nd period d.h.w. 00:00...24:00 h / min .... : ....
h / min
- -:- -
24 Switch-on time 3rd period d.h.w. 00:00...24:00 h / min .... : ....
h / min
- -:- -
25 Switch-off time 3rd period d.h.w. 00:00...24:00 h / min .... : ....
h / min
- -:- -
Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 7/28
Line Function Range Unit Resolution Factory
setting
D.h.w. values
26 Nominal setpoint of the d.h.w. temperature (TBWw)
TBWR Line 770
TBWmax Line 750EXP
TBWR...TBW
max
°C ...... °C 55
Heating circuit values
27 Reduced setpoint of the room temperature (TRRw)
TRF Line 28
TRN Setpoint knob
TRF...TRN °C ...... °C 16
28 Frost protection setpoint of the room temperature
(TRFw)
TRR Line 27
4...TRR °C ...... °C 10
29 Summer / winter changeover temperature 8...30 °C ...... °C 17
30 Slope of the heating curve 1.0...40 – ...... 15
33 Actual value of the room temperature (TRx) 0...50 °C – –
General
34 Actual value of the outside temperature (TAx)
To set the attenuated outside temperature to Tax, press the + / -
buttons simultaneously for 3 s
-50...+50 °C – –
38 Resetting the enduser parameters
To reset the parameters of the enduser level to their standard
values, press the + / - buttons simultaneously for 3 s
0 / 1 – – 0
39 Resetting the heating circuit and d.h.w. time switch
programs
To reset the time switch programs of the enduser level to their
standard values, press the + / - buttons simultaneously for 3 s
0 / 1 – – 0
Holiday program
40 Preselection of the holiday period 1...8 – ...... 1
41 Beginning of the holiday period
--.-- Inactive
To deactivate the set holiday period, press the + / - buttons si-
multaneously for 3 s
--.-- /
01.01...31.12
Day /
month
.... . ....
day /
month
--.--
42 End of the holiday period
--.-- Inactive
To deactivate the set holiday period, press the + / - buttons si-
multaneously for 3 s
--.-- /
01.01...31.12
Day /
month
.... . ....
day /
month
--.--
General / service
50 Indication of error signals
No display = no fault
10 = fault outside sensor
20 = fault boiler sensor oil / gas B2
25 = fault boiler sensor wood B22
26 = fault common flow sensor B10
28 = fault flue gas sensor B8
30 = fault flow sensor heating circuit B1
33 = fault flow sensor heat pump B21
40 = fault return sensor oil / gas B7
43 = fault return sensor wood B72
44 = fault return sensor heat pump B71
47 = fault common return sensor B73
50 = fault storage tank sensor / thermostat B3
52 = fault storage tank sensor / thermostat B31
55 = fault storage tank sensor / thermostat B32
56 = fault storage tank sensor / thermostat B33
61 = fault room unit
70 = fault storage tank sensor B4
71 = fault storage tank sensor B41
72 = fault storage tank sensor B42
73 = fault collector sensor B6
74 = fault collector sensor B61
75 = fault solar flow sensor B62
76 = fault storage tank sensor B43
79 = fault water / brine sensor B11
81 = short-circuit data bus (LPB)
82 = same bus address exists several times
86 = short-circuit PPS
100 = 2 clock time masters on the data bus (LPB)
127 = legionella temperature not reached
130 = maximum flue gas temperature exceeded
8/28 19.08.2002 74 319 0312 0 a Siemens Building Technologies / HVAC Products
Line Function Range Unit Resolution Factory
setting
134 = fault heat pump at input H1
135 = water / brine temperature too low
137 = fault heat pump at input E1
138 = fault control sensor heat pump (operating line 420)
145 = wrong PPS unit (BMU / room unit)
146 = configuration error (operating line 202)
147 = external heat source missing (PPS / LPB)
150 = fault BMU
171 = alarm signal at input H1
172 = alarm signal at input E1
211 = fault wood-fired boiler
231-239 = fault sensor input B101 - B109
241 = fault flow sensor yield measurement B63
242 = fault return sensor measurement B64
243 = fault swimming pool sensor B13
Oil- or gas-fired boiler
60 Chimney sweep
0 = OFF
1 = ON
Outside the programming level, the + / - buttons can be used to
activate / deactivate the second burner stage
0 / 1 – – 0
Solar collectors
65 24-hour yield solar energy 0...999.9 kWh – 0
66 Total yield solar energy
To reset the total yield to 0, press the + / - buttons simultaneously
for 3 s
0...9999999.9 kWh – 0
Heat pump
75 Acknowledgement of heat pump error messages
135 and 137
To reset the error messages to 0, press the + / - buttons simulta-
neously for 3 s
0 / 1 – – 0
Settings to be made on the «Heating engineer» level
Settings required for the configuration and parameterization by the heating engineer.
Buttons Explanation Line
1Press both operating line selection buttons for at least 3 seconds.
This will take you to programming level “Enduser”.
2Press the operating line selection buttons to select the required operating line.
The parameter list on the next pages contains all operating lines on which set-
tings can be made. • • •
3Press the + or – button to set the required value.
The setting will be stored as soon as you leave the programming mode or
change to another operating line.
4To leave programming level “Heating engineer“, press one of the operating
mode buttons.
èNote:
If no button is pressed for about 8 minutes, the controller will automatically return
to the operating mode selected last.
Continu-
ous
display
Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 9/28
Overview of the heating engineer parameters
Line Function Range Unit Resolution Factory
setting
General / service
Basic diagrams
100 Selection of the basic diagram
0 No basic diagram selected
1...99.998 Basic diagrams
To adopt the selected diagram number, press the + / - buttons simul-
taneously for 3 s
0...99.998 – ...... 0
Configuration
Partial diagrams
120 Selection of partial diagram oil- / gas-fired boiler
0 Partial diagram inactive (OeG0)
1...9 Partial diagrams OeG1 through OeG9
0...9 – ...... 0
121 Selection of partial diagram solar collectors
0 Partial diagram inactive (OeG0)
1...16 Partial diagrams Sol1 through Sol16
0...16 – ...... 0
122 Selection of partial diagram wood-fired boiler
0 Partial diagram inactive (Ho0)
1...5 Partial diagrams Ho1 through Ho5
0...5 – ...... 0
123 Selection of partial diagram heat pump
0 Partial diagram inactive (Wp0)
1...5 Partial diagrams Wp1 through Wp5
0...5 – ...... 0
124 Display of partial diagram buffer storage tank
0 Partial diagram inactive (Sp0)
1...3 Partial diagrams Sp1 through Sp3
0...3 – ...... 0
125 Display of partial diagram d.h.w. storage tank
0 Partial diagram inactive (BwSp0)
1...10 Partial diagrams BwSp1 through BwSp10
0...10 – ...... 0
126 Selection of partical diagram combi storage tank
0 Partial diagram inactive (KoSp0)
1...6 Partial diagrams KoSp1 through KoSp6
0...6 – ...... 0
127 Selection of partial diagram heating circuit
0 Partial diagram inactive (Rh0)
1...3 Partial diagrams Rh1 through Rh3
0...3 – ...... 0
Hiding sensors that are not required
130 Source outside sensor
0 Signal via bus (PPS or LPB)
1 Signal via terminal
0 / 1 – ...... 0
131 Reduction 1st d.h.w. sensor B3
0 Without sensor B3
1 With sensor B3
0 / 1 – ...... 0
132 Reduction 2nd d.h.w. sensor B31
0 Without sensor B31
1 With sensor B31
0 / 1 – ...... 0
133 Reduction 2nd buffer storage tank sensor B41
0 Without sensor B41
1 With sensor B41
0 / 1 – ...... 0
135 Reduction wood-fired boiler return sensor B72
0 Without sensor B72
1 With sensor B72
0 / 1 – ...... 0
136 Reduction heat pump flow sensor B21
0 Without sensor B21
1 With sensor B21
0 / 1 – ...... 0
137 Reduction heat pump return sensor B71
0 Without sensor B71
1 With sensor B71
0 / 1 – ...... 0
138 Reduction water / brine sensor B11
0 Without sensor B11
1 With sensor B11
0 / 1 – ...... 0
10/28 19.08.2002 74 319 0312 0 a Siemens Building Technologies / HVAC Products
Line Function Range Unit Resolution Factory
setting
Auxiliary functions
140 Return diversion Y15 (ZuFu1)
- - - None
101..110 Relay Y15 at relay terminal Q101...110
101...110 – ...... - - -
141 Return diversion valve inverted Y¯15 (ZuFu1)
- - - None
101..110 Relay Y15 at relay terminal Q101...110
101...110 – ...... - - -
142 Return diversion sensor B73 (ZuFu1)
--- None
101..109 Sensor at sensor terminal B101...B109
101...109 – ...... - - -
143 Partial storage tank charging Y14 (ZuFu2)
- - - None
101..110 Relay Y14 at relay terminal Q101...110
101...110 – ...... - - -
144 Partial storage tank charging valve inverted Y¯14
(ZuFu2)
- - - None
101..110 Relay Y¯14 at relay terminal Q101...110
101...110 – ...... - - -
145 Partial storage tank charging sensor B43 (ZuFu2)
- - - None
101..109 Sensor B43 at sensor terminal B101...109
101...109 – ...... - - -
146 Storage tank heat transfer pump Q11 (ZuFu3)
- - - None
101..110 Relay Q11 at relay terminal Q101...110
101...110 – ...... - - -
147 D.h.w. circulating pump Q4 (ZuFu4)
- - - None
101..110 Relay Q4 at relay terminal Q101...110
101...110 – ...... - - -
148 Additional pumpe Q17 for heat pump stage 2
(ZuFu5)
- - - None
101..110 Relay Q17 at relay terminal Q101...110
101...110 – ...... - - -
149 System pump Q14 (ZuFu6)
- - - None
101..110 Relay Q14 at relay terminal Q101...110
101...110 – ...... - - -
150 Pump H1 Q15 (ZuFu7)
- - - None
101..110 Relay Q15 at relay terminal Q101...110
101...110 – ...... - - -
151 Alarm output K10 (ZuFu8)
- - - None
101..110 Relay K10 at relay terminal Q101...110
101...110 – ...... - - -
152 Output overtemperature protection K11 (ZuFu9)
- - - None
101..110 Relay K11 at relay terminal Q101...110
101...110 – ...... - - -
153 Output overtemperature protection inverted K¯11
(ZuFu9)
- - - None
101..110 Relay K¯11 at relay terminal Q101...110
101...110 – ...... - - -
154 Relay for flue gas temperature function K17 (ZuFu10)
- - - None
101..110 Relay K17 at relay terminal Q101...110
101...110 – ...... - - -
155 Flue gas sensor B8 (ZuFu10)
- - - None
101..109 Sensor B8 at sensor terminal B101...109
101...109 – ...... - - -
156 3rd buffer storage tank sensor B42 (ZuFu11)
- - - None
101..109 Sensor B42 at sensor terminal B101...109
101...109 – ...... - - -
157 Common flow sensor B10 (ZuFu12)
- - - None
101..109 Sensor B10 at sensor terminal B101...109
101...109 – ...... - - -
158 Solar flow sensor B62 (ZuFu13)
- - - None
101..109 Sensor B62 at sensor terminal B101...109
101...109 – ...... - - -
159 Solar flow sensor B63 for yield measurement (ZuFu14)
- - - None
101..109 Sensor B63 at sensor terminal B101...109
101...109 – ...... - - -
Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 11/28
Line Function Range Unit Resolution Factory
setting
160 Solar return sensor B64 for yield measurement
(ZuFu14)
- - - None
101..109 Sensor B64 at sensor terminal B101...109
101...109 – ...... - - -
161 Solar heat exchanger diverting valve inverted K¯8
(ZuFu15)
- - - None
101..110 Relay K¯8 at relay terminal Q101...110
101...110 – ...... - - -
162 Solar diverting valve inverted K¯9 (ZuFu16)
- - - None
101..110 Relay K¯9 at relay terminal Q101...110
101...110 – ...... - - -
169 Output K13 for free time switch program (ZuFu23)
- - - None
101..110 Relay K13 to relay terminal Q101...110
101...110 – ...... - - -
170 Electric immersion heater buffer storage tank K16
(ZuFu24)
- - - None
101..110 Relay K16 at relay terminal Q101...110
101...110 – ...... - - -
171 Electric immersion heater d.h.w. storage tank K6
(ZuFu25)
- - - None
101..110 Relay K6 at relay terminal Q101...110
101...110 – ...... - - -
172 D.h.w. diverting valve inverted Q¯3 (ZuFu26)
- - - None
101..110 Valve / pump Q¯3 at relay terminal Q101...110
101...110 – ...... - - -
173 Heat generation lock Y4 (ZuFu27)
- - - None
101..110 Relay Y4 to relay terminal Q101...110
101...110 – ...... - - -
174 Heat generation lock inverted Y¯4 (ZuFu27)
- - - None
101..110 Relay Y¯4 at relay terminal Q101...110
101...110 – ...... - - -
175 Solar swimming pool heating K18 (ZuFu28)
- - - None
101..110 Relay K18 at relay terminal Q101...110
101...110 – ...... - - -
176 Solar swimming pool heating inverted K¯18 (ZuFu28)
- - - None
101..110 Relay K¯18 at relay terminal Q101...110
101...110 – ...... - - -
177 Solar swimming pool heating sensor B13 (ZuFu28)
- - - None
101..109 Sensor B13 at sensor terminal B101...109
101...109 – ...... - - -
Miscellaneous
193 D.h.w. heating with charging pump or diverting valve
(Q3)
0 Charging pump
1 Diverting valve
0 / 1 – ...... - - -
194 Setpoint and time switch program for d.h.w. heating
with BMU
0 No
1Yes
0 / 1 – ...... 0
195 Function of system pump Q14
1 For heating circuit only
2 For heating circuit and d.h.w.
3 With external heat demand
1...3 – ...... 1
General
Diagnosis configuration
200 Display of relay terminal assignment
Query with the + / - buttons
101...110 – – –
201 Display of sensor terminal assignment
Query with the + / - buttons
101...109 – – –
12/28 19.08.2002 74 319 0312 0 a Siemens Building Technologies / HVAC Products
Line Function Range Unit Resolution Factory
setting
202 Display of configuration errors
No display = no error
1-10 = terminals Q101 - Q110 used beyond capacity
11-19 = terminals B101 - B109 used beyond capacity
24 = B73, Y15 or Y¯15 missing
26 = B43, Y14 or Y¯14 missing
33 = B62 incompatible with partial diagram "Solar"
34 = d.h.w. heating BMU incompatible with partial diagram “D.h.w. /
combi storage tank"
38 = external heat source incompatible with partial diagram "Oil / gas"
39 = inadmissible reduction B72
40 = B13 or K18 / K¯18 missing
41 = B8 missing for function with K17
42 = Q17 incompatible with partial diagram "Heat pump"
43 = Q¯3 incompatible with partial diagram "D.h.w. / combi storage
tank"
45 = K¯9 incompatible with partial diagram "Solar"
51 = inadmissible reduction of B21 and B71
54 = d.h.w. heating BMU incompatible with partial diagram "Oil / gas"
55 = inadmissible reduction of B3 without d.h.w. heating BMU
1...99 – – –
203 Display of plant diagram identification number part 1 0...99‘999‘999 – – –
204 Display of plant diagram identification number part 2 0...99‘999‘999 – – –
205 Display of plant diagram identification number part 3 0...99‘999‘999 – – –
206 Display of plant diagram identification number part 4 0...99‘999‘999 – – –
Terminal test
210 Output test (relay test)
--- Control mode according to the operating state
0 All outputs deactivated
1 Q101 ON
2 Q102 ON
3 Q103 ON
4 Q104 ON
5 Q105 ON
6 Q106 ON
7 Q107 ON
8 Q108 ON
9 Q109 ON
10 Q110 ON
0...10 – – –
211 Input test (sensor test)
1 Sensor at B101
2 Sensor at B102
3 Sensor at B103
4 Sensor at B104
5 Sensor at B105
6 Sensor at B106
7 Sensor at B107
8 Sensor at B108
9 Sensor at B109
10 Room sensor (PPS room unit)
11 Input H1 (ontact or DC 0…10 V)
12 Input E1 (AC 230 V)
1...12 – – –
212 Display of PPS communication
Query with the + / - buttons
- - - No communication
1...12 PPS device address
0...255 Identification code
--- / 1..12 /
0..255
–– –
Setpoint / actual value of common flow
220 Display of the common flow temperature setpoint
--- No value available
0.0...140.0 °C – –
221 Actual value of the common flow temperature
--- No value available
0...140 °C – –
Flue gas temperature
222 Actual value of the flue gas temperature B8
--- No value available
–50...350 °C – –
223 Maximum value of the flue gas temperature display B8
--- No value available
To reset the maximum value to the actual value, press the + / - but-
tons simultaneously for 3 s
–50...350 °C – 0
Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 13/28
Line Function Range Unit Resolution Factory
setting
224 Maximum limitation of the flue gas temperature
--.- Function deactivated
--.- / 0...350 °C ...... °C --.-
225 Switch-on temperature flue gas sensor function
(ZuFu10)
0...350 °C ...... °C 60
226 Switch-off temperature flue gas sensor function
(ZuFu10)
0...350 °C ...... °C 40
Oil- / gas-fired boiler
Setpoints / actual values
250 Display of the boiler temperature setpoint (TKw)
(internal or external PPS-BMU)
--- No values available
0...140 °C – –
251 Actual value of the boiler temperature (TKx)
B2 or external PPS-BMU
--- No values available
–50...350 °C – –
252 Setpoint minimum limitation of the return temperature Line 280EXP
...95 °C ...... 8
253 Actual value of the return temperatur B7
--- No value present
–50...350 °C – –
Burner hours run counter / start counter
256 Burner operating hours stage 1 or PPS-BMU
Output K4 or PPS
To make a reset to 0, press the - / + buttons simultaneously for 3 s
0...999‘999 h – 0
257 Burner operating hours stage 2
Output K5
To make a reset to 0, press the - / + buttons simultaneously for 3 s
0...999‘999 h – 0
258 Number of burner starts stage 1
Output K4
To make a reset to 0, press the - / + buttons simultaneously for 3 s
0...999‘999 – – 0
259 Number of burner starts stage 2
Output K5
To make a reset to 0, press the - / + buttons simultaneously for 3 s
0...999‘999 – – 0
Functions
270 Minimum limitation of the boiler temperature (TKmin) 250EXP...
251EXP
(max. 95°C)
°C ......°C 40
271 Frost protection for the plant with the boiler pump
0 General frost protection for the plant does not act on this pump
1 General frost protection for the plant acts on this pump
0 / 1 – ...... 1
Diagnosis
295 Display of BMU error code 0...255 – – –
296 Function test oil- / gas-fired boiler
--- No test
0 Everything OFF
1 Boiler pump ON (Q1)
2 In addition, burner stage 1 ON (Q1+K4)
3 In addition, burner stage 2 ON (Q1+K4+K5)
4 Maintained boiler return temperaturre fixed ON
(Q1+K4+K5+Q12/Y7)
5 Maintained boiler return temperature fixed OFF
(Q1+K4+K5+Q12+Y8)
--- / 0...5 – – - - -
Solar collectors
Setpoints / actual values
300 Actual value of collector temperature B6
--- No value available
–50...350 °C – –
301 Actual value of collector temperature B61
--- No value available
–50...350 °C – –
302 Actual value of collector flow temperature B62
--- No value available
–50...350 °C – –
303 Maximum value of collector temperature 1 (B6)
To make a reset to the actual value, press the + / - buttons simulta-
neously for 3 s
–50...350 °C – 0
304 Maximum value of collector temperature 2 (B61)
To make a reset to the actual value, press the + / - buttons simulta-
neously for 3 s
–50...350 °C – 0
14/28 19.08.2002 74 319 0312 0 a Siemens Building Technologies / HVAC Products
Line Function Range Unit Resolution Factory
setting
Temperature differential collector / heat exchanger
305 Display of the temperature differential collector 1 / heat
exchanger 1
--- No value available
–50...350 K – –
306 Display of the temperature differential collector 1 / heat
exchanger 2
--- No value available
–50...350 K – –
307 Display of temperature differential collector 2 / heat ex-
changer 1
--- No value available
–50...350 K – –
308 Display of temperature differential collector 2 / heat ex-
changer 2
--- No value available
–50...350 K – –
309 Temperature differential collector 1 / swimming pool
--- No value available
–50...350 K – 1
310 Temperature differential collector 2 / swimming pool
--- No value available
–50...350 K – 1
Hours run counter
311 Operating hours collector pump 1 (output Q5)
To make a reset to 0, press the - / + buttons simultaneously for 3 s
0...999‘999 h – 0
312 Operating hours collector pump 2 (output Q16)
To make a reset to 0, press the - / + buttons simultaneously for 3 s
0...999‘999 h – 0
313 Operating hours pump K12
To make a reset to 0, press the - / + buttons simultaneously for 3 s
0...999‘999 h – 0
314 Operating hours diverting valve K8
To make a reset to 0, press the - / + buttons simultaneously for 3 s
0...999‘999 h – 0
315 Operating hours swimming pool heating K188
To make a reset to 0, press the - / + buttons simultaneously for 3 s
0...999‘999 h – 0
Swimming pool heating
317 Setpoint temperature swimming pool 0...line 321 °C ...... °C 25
318 Actual value of swimming pool temperature B13
--- No value available
–50...350 °C – –
319 Temperature differential swimming pool ON Line 320...40 K ...... K 8
320 Temperature differential swimming pool OFF 0...line 319 K ...... K 4
321 Maximum swimming pool charging temperature 20...95 °C ...... °C 35
322 Heat exchanger pump operation for swimming pool
1 Alternatively
2 Parallel
1 / 2 – ...... 1
323 Measured value correction swimming pool sensor B13 –10.0...10.0 K ...... K 0.0
Functions
324 Selection of collector sensor B6 / B61
1 LG-Ni 1000
2 Pt 1000
1...2 – ...... 1
325 Measured value correction of collector sensor 1 B6 –10.0...10.0 K ...... K 0.0
326 Measured value correction of collector sensor 2 B61 –10.0...10.0 K ...... K 0.0
327 Measured value correction of collector flow sensor B62 –10.0...10.0 K ...... K 0.0
328 Heat exchanger pump operation partial diagram Sol5
1 Alternative operation
2 Parallel operation
1...2 – ...... 2
329 Temperature differential ON heat exchanger 1 Line 330...40 °C ...... °C 8
330 Temperature differential OFF heat exchanger 1 0...line 329 °C ...... °C 4
331 Temperature differential ON heat exchanger 2 Line 332...40 °C ...... °C 8
332 Temperature differential OFF heat exchanger 2 0...line 331 °C ...... °C 4
333 Priotity with 2 heat exchangers
1 No priority
2 Relative priority buffer storage tank (het exchanger 1)
3 Absolute priority buffer storage tank (heat exchanger 1)
4 Relative priority d.h.w. storage tank (heat exchanger 2)
5 Absolute priority d.h.w. storage tank (heat exchanger 2)
1...5 – ...... 4
Solar yield / recooling measurement
338 Type of antifreeze agent used
1 None (only water)
2 Ethylenglycol
3 Propylenglycol
4 Mixture of Ethylen- and Propylenglycol
1...4 – ...... 1
Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 15/28
Line Function Range Unit Resolution Factory
setting
339 Concentration of antifreeze agent 1...100 % ...... % 30
340 Pulse value flow meter
(supports 1, 2.5, 10, 25, 100 liters / pulse)
1.0 / 2.5 / 10 /
25 / 100
– ...... 10.0
341 Volumetric flow solar pump 10...1500 Liters/h ......
Liters/h
200
342 Selection of sensor for solar yield measurement
(B63 and B64)
1 LG-Ni 1000
2 Pt 1000
1 / 2 – ...... 2
343 Actual value of solar flow temperature B63
--- No value available
–50...350 °C – –
344 Actual value of solar return temperature B64
--- No value available
–50...350 °C – –
Speed-controlled pump
345 Display of speed of solar pump Q5 / K9 0...100 % – –
346 Minimum speed of the solar pump 0...line 347 % ...... % 40
347 Maximum speed of the solar pump Line 346
...100
% ...... % 100
Diagnosis
349 Functional test solar
--- No test
0 Everything OFF
1 Q5 ON
2 Q5/K12 + Q16 ON
3 Q5/K12 + Q16 + K9 ON
4 Q5/K12 + Q16 + K9 + K8 ON
--- / 0...4 – – - - -
Wood-fired boiler
Setpoints / actual values
350 Display of the boiler temperature setpoint 0...140 °C – –
351 Display of actual value of boiler temperature B22
--- No value available
–50...350 °C – –
352 Display of the boiler return temperature setpoint 0...140 °C – –
353 Display of actual value of return temperature B72
--- No value available
–50...350 °C – –
Hours run counter
354 Operating hours pump of wood-fired boiler
(output Q10)
To make a reset to 0, press the - / + buttons simultaneously for 3 s
0...999‘999 h – 0
355 Operating hours wood-fired boiler (output K3)
To make a reset to 0, press the - / + buttons simultaneously for 3 s
0...999‘999 h – 0
356 Number of releases of wood-fired boiler (output K3)
To make a reset to 0, press the - / + buttons simultaneously for 3 s 0...999‘999 – – 0
Functions
369 Minimum temperature differential of the wood-fired
boiler
0...20 K ...... K 4
370 Minimum temperature of the wood-fired boiler for re-
lease of the pump
20...80 °C ...... °C 60
371 Switching differential for minimum temperature of the
wood-fired boiler for release of the pump
1...30 K ...... K 12
372 Pump overrun time
--- No pump overrun time
--- / 4...120 min ...... min 20
373 Strategy of wood-fired boiler
0 Constant
1 Depending on demand
0 / 1 – ...... 1
376 Wood-fired boiler locks all other heat sources
0 No
1 Yes
0 / 1 – ...... 1
378 Frost protection for the plant with pump of the wood-
fired boiler
0 General frost protection for the plant does not act on this pump
1 General frost protection for the plant acts on this pump
0 / 1 – ...... 1
16/28 19.08.2002 74 319 0312 0 a Siemens Building Technologies / HVAC Products
Line Function Range Unit Resolution Factory
setting
Residual heat function
385 Maximum duration of the residual heat function
--- Function deactivated
--- / 5...60 min ...... min - - -
386 Perform residual heat function once / several times
0Once
1 Several times
0 / 1 – ...... 0
387 Residual heat function with buffer stratification protec-
tion
0No
1Yes
0 / 1 – ...... 0
388 Residual heat function directly for the consumers
0No
1Yes
0 / 1 – ...... 0
Speed-controlled pump
390 Display of speed of pump Q10 of the wood-fired boiler 0...100 % – –
391 Minimum speed of pump of the wood-fired boiler 0...line 392 % ...... % 50
392 Maximum speed of pump of the wood-fired boiler Line 91...100 % ...... % 100
Diagnosis
395 Functional test of the wood-fired boiler
--- No test
0 Everything OFF
1 Boiler pump ON (Q10)
2 In addition, burner ON (Q10 + K3)
3 In addition, maintained boiler return temperature ON (Q10 + K3
+ Y10)
4 In addition, maintained boiler return temperature OFF (Q10 +
K3 + Y9)
--- / 0...4 – – - - -
Heat pump
Setpoints / actual values
400 Display of setpoint of the heat pump flow temperature 0...140 °C – –
401 Actual value of heat pump flow temperature B21
--- No value available
–50...350 °C – –
402 Display of setpoint of the heat pump return temperature 0...140 °C – –
403 Actual value of heat pump return temperature B71
--- No value available
–50...350 °C – –
404 Actual value of water / brine flow temperature B11
--- No value available
–50...350 °C – –
Hours run counter
410 Operating hours stage 1 (output K1)
To make a reset to 0, press the - / + buttons simultaneously for 3 s
0...999‘999 h – 0
411 Operating hours stage 2 (output K2)
To make a reset to 0, press the - / + buttons simultaneously for 3 s
0...999‘999 h – 0
412 Number of starts of stage 1 (output K1)
To make a reset to 0, press the - / + buttons simultaneously for 3 s
0...999‘999 – – 0
413 Number of starts of stage 2 (output K2)
To make a reset to 0, press the - / + buttons simultaneously for 3 s
0...999‘999 – – 0
Functions
420 Control sensor for the heat pump:
1 Flow sensor (B21)
2 Return sensor (B71)
3 Common flow sensor (B10)
4 Mean value ((B21+B71)/2)
5 ON with flow sensor (B21) / OFF with return sensor (B71)
6 ON with flow sensor (B21) / OFF with buffer sensor
(B42 / B41 / B4)
7 ON with common flow sensor (B10) / OFF with buffer sensor
(B42 / B41 / B4)
8 ON with return sensor (B71) / OFF with buffer sensor
(B42 / B41 / B4)
9 On with buffer sensor (B4)
OFF with return sensor (B71)
1...9 – ...... 2
421 Heat pump switching differential ON (SDWp) 1...20 K ...... K 2
422 Heat pump switching differential OFF (SDWp) 1...20 K ...... K 2
423 Flow / return temperature differential at –10 °C 1...30 K ...... K 8
424 Compensation of mixing valve boost
--- Function deactivated
--- / 0...50 K ...... K - - -
426 Frost protection for the heat pump circulator
0 Frost protection does not act on this circulator
1 Frost protection acts on this circulator
0 / 1 – ...... 1
Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 17/28
Line Function Range Unit Resolution Factory
setting
427 Additional pump kick for water / brine pump
0No
1Yes
0 / 1 – ...... 0
428 Control of the heat pump circulator 0 / 1 – ...... 1
Diagnosis
445 Functional test of the heat pump
--- No test
0 Everything OFF
1 Q8 ON (solar pump),
2 Q8+Q9 ON (plus heat pump circulator)
3 Q8+Q9+K1 ON (plus 1st stage),
4 Q8+Q9+K1+K2 ON (plus 2nd stage)
--- / 0...4 – – ---
Buffer storage tank
Setpoints / actual values
450 Actual value of buffer storage tank temperature B4 at
the top
--- No value available
–50...350 °C – –
451 Actual value of buffer storage tank temperature B41 at
the bottom
--- No value available
–50...350 °C – –
452 Actual mean value of buffer storage tank temperature
B42
--- No value available
–50...350 °C – –
453 Actual value of buffer storage tank temperature B43 for
partial charging
--- No value available
–50...350 °C – –
454 Maximum value of buffer storage temperature B4
To make a reset to the actual value, press the + / - buttons simulta-
neously for 3 s
–50...350 °C – 0
455 Display of actual value of return temperature B73
--- No value available
–50...350 °C – –
456 Display of setpoint of the buffer storage tank tempera-
ture
To adjust the setpoint of the buffer storage tank temperature to the
current heat demand, press the + / - buttons simultaneously for 3 s
0...140 °C – 0
Functions
470 Recharge control buffer storage tank with the wood-
fired boiler
0 With sensor B4 (switching differential)
1 With sensors B4 / B41 (start / stop)
0 / 1 – ...... 0
471 Minimum buffer storage tank level when charging with
the collector (TPmin)
0...line 472 °C ...... °C 0
472 Maximum buffer storage tank charging temperature Line 471...
line 450EXP
°C ...... °C 80
473 Automatic heat generation lock
--- OFF
0 With B4
1 With B4 and B41 / B42
--- / 0...1 – ...... 0
474 ∆T between buffer storage tank and heat demand of the
heating circuit (for automatic heat generation lock)
–20...20 K ...... K -2
475 Forced charging of buffer storage tank with heat pump
0 None
1 Slave pointer / B4,
2 Slave pointer / B41 or B42,
3 Max. buffer storage tank charging temperature / B4,
4 Max. buffer storage tank charging temperature / B41 or B42
0...4 – ...... 0
Return diversion (ZuFu 1)
480 Return diversion temperature differential ON Line 481...40 K ...... K 10
481 Return diversion temperature differential OFF 0...Zeile 480 K ...... K 5
482 Operating action of return diversion
1 As return temperature setback
2 As return temperature boost
1...2 – ...... 1
483 Storage tank sensor for return diversion
1 Sensor B4
2 Sensor B41
3 Sensor B42
1...3 – ...... 2
18/28 19.08.2002 74 319 0312 0 a Siemens Building Technologies / HVAC Products
Line Function Range Unit Resolution Factory
setting
Electric immersion heater
484 Release outside temperature for electric immersion
heater buffer storage tank
--- Function deactivated
--- / –30...30 °C ...... °C –5
485 Selection of control sensor for electric immersion heater
of the buffer storage tank
0 Common flow sensor B10
1 Buffer storage tank sensor B4
0 / 1 – ...... 1
Overtemperature protection
489 Differential of maximum storage tank temperature
(MSP) and buffer storage tank safety temperature
1...50 K ...... K 5
490 Hysteresis for buffer storage tank cooling function with
priority 1
1...20 °C ...... °C 5
491 Priority buffer storage tank cooling with heat transfer
pump
--- Function deactivated
1 Priority 1
2 Priority 2
--- / 1...2 – ...... - - -
492 Priority buffer storage tank cooling with collector pump
--- Function deactivated
1 Priority 1
2 Priority 2
--- / 1...2 – ...... - - -
493 Priority buffer storage tank cooling with heat source
pump
--- Function deactivated
1 Priority 1
2 Priority 2
--- / 1...2 – ...... - - -
494 Priority buffer storage tank cooling with overtempera-
ture protection output
--- Function deactivated
1 Priority 1
2 Priority 2
--- / 1...2 – ...... - - -
495 Priority buffer storage tank cooling by delivering heat for
space heating
--- Function deactivated
1 Priority 1
2 Priority 2
--- / 1...2 – ...... - - -
Storage tank temperature
Functions
520 D.h.w. heating with electric immersion heater K6
1 Frost protection for the storage tank
2 Only in summer operation
3 Always
1...3 – ...... 2
521 Recharge control d.h.w. storage tank
0 With sensor B3 (switching differential)
1 With sensors B3 and B31 (start / stop)
2 D.h.w. heating like setting 0, legionella function like setting 1
0...2 – ...... 0
522 Minimum d.h.w. storage tank level when charging with
collector (TBmin)
0...line 523 °C ...... °C 0
523 Maximum d.h.w. storage tank charging temperature Line 522...
line 500EXP
°C ...... °C 80
Heat transfer d.h.w. storage tank
530 Heat transfer with d.h.w. sensor
0 With sensor B3
1 With sensor B31
0 / 1 – ...... 0
531 Automatic heat transfer from the buffer to the d.h.w.
storage tank
--- Function deactivated
1 With Q3
2 With Q11
--- / 1...2 – ...... 1
532 Heat transfer strategy in the summer
0 Only for frost protection
1 According to d.h.w. release
2 Always
0...2 – ...... 2
533 Heat transfer strategy in the winter
0 Only for frost protection
1 According to d.h.w. release
2 Always
0...2 – ...... 2
Siemens Building Technologies / HVAC Products 74 319 0312 0 a 19.08.2002 19/28
Line Function Range Unit Resolution Factory
setting
534 Temperature differential ON heat transfer Line 535...40 °C ...... °C 6
535 Temperature differential OFF heat transfer 0...line 534 °C ...... °C 4
Overtemperature protection d.h.w. storage tank
539 Differential of maximum storage tank temperature
(MSB) and d.h.w. storage tank safety temperature
1...50 K ...... K 5
540 Hysteresis of the d.h.w. cooling function with priority 1 1...20 °C ...... °C 5
541 Priority of d.h.w. storage tank cooling with transfer
pump
--- Function deactivated
1 Priority 1
2 Priority 2
--- / 1...2 – ...... - - -
542 Priority of d.h.w. storage tank cooling with collector
pump
--- Function deactivated
1 Priority 1
2 Priority 2
--- / 1...2 – ...... - - -
544 Priority of d.h.w. storage tank cooling with overtem-
perature protection output K11
--- Function deactivated
1 Priority 1
2 Priority 2
--- / 1...2 – ...... - - -
Diagnosis
545 Functional test of d.h.w. storage tank
--- No test
0 Everything off
1 Charging pump ON (Q3)
2 In addition, diverting valve ON (Q3 + Y3)
3 Transfer pump ON (Q11)
--- / 0...3 – ...... - - -
Combi storage tank
570 B4 delivers temperature for functionality B31
0No
1Yes
0 / 1 – ...... 0
Bivalent operation
Heat source sequence
620 Lead heat source
1 Oil- / gas-fired boiler
2 Heat pump
3 Wood-fired boiler
1...3 – ...... –
621 Switch-on delay lag heat source 1...255 min ...... min 10
622 Release limit for lag heat source 0...500 K*min .....K*min 200
623 Reset limit for lag heat source 0...500 K*min .....K*min 50
Release according to the outside temperature
630 Release of oil- / gas-fired boiler below the outside tem-
perature threshold
--- Boiler always released
--- / –30...30 °C ...... °C - - -
631 Release of heat pump above the outside temperature
threshold
--- Heat pump always released
--- / –30...30 °C ...... °C - - -
632 Release of wood-fired boiler below the outside tem-
perature threshold
--- Boiler always released
--- / –30...30 °C ...... °C - - -
D.h.w. heating
640 Heat source strategy for d.h.w. heating
1 D.h.w. according to the current heat source sequence.
2 D.h.w. with lag heat source, lead heat source maintains the
room temperature setpoint during d.h.w. heating.
3 D.h.w. with lag heat source, lead heat source is shut down
during d.h.w. heating.
4 D.h.w. with lag heat source if released, lead heat source
maintains the room temperature setpoint during d.h.w. heating.
5 D.h.w. with lag heat source if released, lead heat source is shut
down during d.h.w. heating.
1...5 – ...... 1
20/28 19.08.2002 74 319 0312 0 a Siemens Building Technologies / HVAC Products
Line Function Range Unit Resolution Factory
setting
Heating circuit / space heating
Setpoints / actual values
700 Display of the nominal room temperature setpoint
Nominal setpoint plus readjustment made on the room unit
0.0...35.0 °C – –
701 Display of the room temperature setpoint (TRw) 0.0...35.0 °C – –
702 Display of heatign circuit flow temperature setpoint TVw 0...140 °C – –
703 Display of actual value of heating circuit flow tempera-
ture TVx B1
--- No value available
--- / -50...350 °C – –
704 Attenuated outside temperature (TAged) –50.0...50.0 °C – 0
705 Composite outside temperature (TAgem) –50.0...50.0 °C – –
706 Measured value correction of outside sensor B9 –10.0...10.0 K ...... K 0
Functions
720 Parallel displacement of heating curve -4.5...+4.5 K ...... K 0.0
721 Room influence
0 Inactive
1 Active
0 / 1 – ...... 1
722 Switching differential of the room temperature (SDR)
- - . - Inactive
0.5...4.0 Active
- - . - /
0.5...4.0
K ...... K - - . -
723 Min. limitation of the flow temperature setpoint (TVmin)
Tvmax Line 724
8...TVmax °C ...... °C 8
724 Max. limitation of the flow temperature setpoint (TVmax)
Tvmin Line 723
TVmin...95 °C ...... °C 80
725 Type of building construction
0 Heavy
1 Light
0 / 1 – ...... 1
726 Adaption of the heating curve
0 Inactive
1 Active
0 / 1 – ...... 1
727 Maximum forward shift of optimum start control 00:00...06:00 hh:mm .... : ....
hh:mm
00:00
728 Maximum forward shift of optimum stop control 00:00...06:00 hh:mm .... : ....
hh:mm
00:00
730 Locking signal gain heating circuit 0...200 % ...... % 100
732 Frost protection for the plant with the heating circuit
0 General frost protection for the plant does not act on this pump
1 General frost protection for the plant acts on this pump
0 / 1 – ...... 1
733 Outside temperature for start of the room temperature
setpoint boost
Line 734...10 °C 1 - - -
734 Outside temperature for end of the room temperature
setpoint boost
–30... line 733 °C 1 -10
Floor curing function
738 Floor curing dates
0OFF
1 Functional heating
2 Floor curing heating
3 Functional and floor curing heating
0...3 – ...... 0
739 Floor curing data 0...32 / 0...95 Day /
°C
––
Speed-controlled pump
740 Display of speed heating circuit pump Q2 0...100 % – –
741 Minimum speed of the heating circuit pump 0...line 742 % ...... % 100
742 Maximum speed of the heating circuit pump Line 741
...100
% ...... % 100
743 Speed reduction heating circuit pump
0 According to the heating circuit operating level
1 According to the characteristic
0 / 1 – ...... 1

This manual suits for next models

1

Other Siemens Controllers manuals

Siemens Simatic S7-300 User manual

Siemens

Siemens Simatic S7-300 User manual

Siemens S7-1200 TELECONTROL Instruction Manual

Siemens

Siemens S7-1200 TELECONTROL Instruction Manual

Siemens AEROGYR RWI65.02 User manual

Siemens

Siemens AEROGYR RWI65.02 User manual

Siemens Powermite 599 Series Owner's manual

Siemens

Siemens Powermite 599 Series Owner's manual

Siemens SINUMERIK 802D sl User manual

Siemens

Siemens SINUMERIK 802D sl User manual

Siemens SIMATIC S5 User manual

Siemens

Siemens SIMATIC S5 User manual

Siemens Simatic S7-1500 User manual

Siemens

Siemens Simatic S7-1500 User manual

Siemens RAJA+ 3TE7131-1HC14-1A Operating instructions

Siemens

Siemens RAJA+ 3TE7131-1HC14-1A Operating instructions

Siemens ST950 User manual

Siemens

Siemens ST950 User manual

Siemens Ertec 400 User manual

Siemens

Siemens Ertec 400 User manual

Siemens SITRANS LUT400 User manual

Siemens

Siemens SITRANS LUT400 User manual

Siemens SIMATIC S7-1200 CP 1243-8 IRC User manual

Siemens

Siemens SIMATIC S7-1200 CP 1243-8 IRC User manual

Siemens DOL 3TW7291-1A Guide

Siemens

Siemens DOL 3TW7291-1A Guide

Siemens N 567/01 User manual

Siemens

Siemens N 567/01 User manual

Siemens Simatic S7-300 User manual

Siemens

Siemens Simatic S7-300 User manual

Siemens LMV27.100x2 Operator's manual

Siemens

Siemens LMV27.100x2 Operator's manual

Siemens LOGO! PROM User manual

Siemens

Siemens LOGO! PROM User manual

Siemens SSA911.01TH User manual

Siemens

Siemens SSA911.01TH User manual

Siemens Simatic S7-1500 User manual

Siemens

Siemens Simatic S7-1500 User manual

Siemens N 526E02 Service manual

Siemens

Siemens N 526E02 Service manual

Siemens RVP36 User manual

Siemens

Siemens RVP36 User manual

Siemens SIPART PS2 User manual

Siemens

Siemens SIPART PS2 User manual

Siemens SIMATIC NET S7-1200 User manual

Siemens

Siemens SIMATIC NET S7-1200 User manual

Siemens SIMOTION D410 Quick start guide

Siemens

Siemens SIMOTION D410 Quick start guide

Popular Controllers manuals by other brands

Berker 8526 51 00 operating instructions

Berker

Berker 8526 51 00 operating instructions

Mitsubishi Electric MELSEC iQ-R Series user manual

Mitsubishi Electric

Mitsubishi Electric MELSEC iQ-R Series user manual

Synapse DIM10-087-06-FW installation guide

Synapse

Synapse DIM10-087-06-FW installation guide

Rohde ST 410 operating instructions

Rohde

Rohde ST 410 operating instructions

Dungs FRM 100065 instructions

Dungs

Dungs FRM 100065 instructions

Uponor Smatrix Base PRO X-147 installation manual

Uponor

Uponor Smatrix Base PRO X-147 installation manual

KBR F144-MS-1V1C1TI6DO-3 Technical reference

KBR

KBR F144-MS-1V1C1TI6DO-3 Technical reference

VALPES VRX 300 manual

VALPES

VALPES VRX 300 manual

Mitsubishi Electric MELSEC iQ-F Series user manual

Mitsubishi Electric

Mitsubishi Electric MELSEC iQ-F Series user manual

Eltako FSHA-230V quick guide

Eltako

Eltako FSHA-230V quick guide

Vector TCI-W11-H overview

Vector

Vector TCI-W11-H overview

D-Box G5 quick start guide

D-Box

D-Box G5 quick start guide

Genave LR900 Node Hardware manual

Genave

Genave LR900 Node Hardware manual

digitalview ALR-1920-120 instructions

digitalview

digitalview ALR-1920-120 instructions

Hobby-Wing Platinum 60A V4 user manual

Hobby-Wing

Hobby-Wing Platinum 60A V4 user manual

Buspro HDL SB-DN-HVAC user manual

Buspro

Buspro HDL SB-DN-HVAC user manual

NovaStar VX2U user manual

NovaStar

NovaStar VX2U user manual

HYDACELECTRONIC HPG 3000-000 operating instructions

HYDACELECTRONIC

HYDACELECTRONIC HPG 3000-000 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.