5 mm
Position 15.5 mm
ERIFLEX FLEXIBAR
as shown
M5
86.0
16.1 13.3
NOTE:
1. Tighten screws of all unused galleries to the specified torque above.
2. For multiple phase assemblies, join blocks together before installing on DIN profile.
3. The input must be fixed or maintained at approximately 15cm from the block.
I: 500A
Ui: 1000V AC/DC
Uimp: 12kV
Ipk: 51kA
Icw: 23kA rms 1s
IEC 60947-7-1
(IEC 60947-7-1 Ratings)
®
INSTRUCTION SHEET
UDF500
569060 N
WARNING:
nVent products shall be installed and used only as indicated in nVent product instruction sheets and training materials. Instruction sheets are available at
1.
www.nVent.com
and from your nVent customer service representative.
nVent products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
2.
All instructions must be
completely
followed to ensure proper and safe installation and performance.
3.
Improper installation, misuse, misapplication or other failure to completely follow nVent's instructions and warnings may cause product malfunction, property
4.
damage, serious bodily injury and/or death, and void your warranty.
SAFETY INSTRUCTIONS:
All governing codes and regulations and those required by the job site must be observed.
Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
nVent, nVent CADDY, nVent ERICO Cadweld, nVent ERICO Critec, nVent ERICO, nVent ERIFLEX, and nVent LENTON are owned by
nVent or its global affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change
specifications without prior notice.
© 2004-2018 nVent All Rights Reserved
1 OF 2
IP7805_S
TECHNICAL SUPPORT
www.nVent.com