nvent RAYCHEM Raystat V5 User manual

Raystat
Version 5 (EU)
PART 1 INSTALLATION MANUAL 3
EN ENERGY-SAVING FREEZE PROTECTION CONTROLLER
DE ENERGIESPARENDES STEUERGERÄT FÜR
FROSTSCHUTZANWENDUNGEN
PART 2 OPERATION MANUAL

8 | nVent.com nVent.com | 9
16
RCD / FI 30 mA - C 20 A : ON
3. INSTALLATION NOTES
The installation and, if necessary, the maintenance and the disassembling must be
carried out by a qualied electrical installer.
The installation must be compatible with local regulations.
Check the maximum circuit length for your circuit breaker in the next table:
Maximum circuit length at 230 VAC and for 20°C start-up temperature
C-characteristic circuit breaker
Multiple units on multiple power points can be used if longer heating cables are
required. We recommend to use nVent RAYCHEM SV-SBS panels to operate 3, 6, 9 or
12 heating circuits
10XL2-LH 15XL2-LH 26XL2-LH 31XL2-LH
Circuit breaker (Plum) (Green) (Blue) (Purple)
C 10A 140 m 90 m 80 m 67m
C 13A 195 m 120 m 110 m 88m
C 16A 215 m 135 m 135 m 110m
C 20A 215 m 160 m 135 m 118m
The nVent RAYCHEM Raystat V5 has a removable top lid. Both top and bottom of the box
have electronic parts and are connected to each other by an Ethernet connector cable.
The unit is delivered with top lid and back part dismantled.
Warning: For over voltage protection (e.g. in case of thunderstorm) we recommend
the use of an external over voltage protection device.
Care and maintenance
Clean the Raystat V5 with a soft damp cloth only, do not use any solvents. Do not
pour water directly on the device. Do not use a water hose or a high pressure cleaner.
3.1. Description
nVent RAYCHEM Raystat V5 is an electronic control thermostat with display,
advanced alarm facilities and the capability of switching large currents (20 A). The
Raystat V5 is designed to control nVent heating cable systems. Heating cable can be
controlled (switched ON/OFF) either directly by the Raystat V5 or via a contactor.
Direct switching of heating cables is possible for heating loads up to 20 A.
For heating loads above 20 A indirect switching via a suitably rated contactor con-
trolled by a Raystat V5 is necessary.
Installation and all wiring must be in accordance with applicable regulations.
The device must be installed in non hazardous areas only. nVent offers other controls
for use in hazardous areas.
The sensor must be installed. Attention: The sensor position on pipe or in Air
needs to match the operation mode Line or PASC (ambient temperature
measurement control). A wrong assignment can led to a frozen pipe.
An alarm terminal makes remote signalling of errors possible. The unit can be
pre-programmed in power-off mode by external power bank (to be ordered separately)
connected via A-A-USB cable and USB connection.
3.2. Technical data
Product application nVent RAYCHEM Pipe freeze protection heating
cables only
Electrical properties
Supply voltage 180-253 VAC; 50/60Hz
Power consumption 5,3 W max
Power output relay
(heating cable) 25 A / 230 VAC
Power supply terminals 3 x 6 mm² max
Heating cable terminals 3 x 6 mm² max
Alarm terminals 3 x 1,5 mm² max
Sensor terminal - Pipe 2 x 1,5 mm² max
Alarm relay
Single pole double throw relay, volt-free; Max.
switching capacity (resistive load only)
1 A/30 VDC 0.5 A/125 VAC, Max.: 60 VDC/125
VAC
Circuit breaker Max. C 20 A (C-Characteristic)
Settings All settings are stored in non-volatile memory
Operating temperature –40°C to +40°C ambient
Selectable temperature 0° C to +85°C
Enclosure
Material Polycarbonate
Dimensions 210 mm x 90 mm x 85 mm
Ingress protection class IP 65
Weight 990 g
Mounting DIN-Rail mountable 35 mm
Entries 2 x M25 and 2 x M20
Storage temperature –40°C to +50°C
Flammability class D category (DIN EN 60730/VDE 0631-1)
Sensor
Temperature sensor type Standard NTC 2,0 kOhm at 25°C, 2 wires
Sensor tip dimensions Ø 5 mm; length 20 mm
Sensor cable length 5 m; extendable up to 150 m , 2 x1,5 mm²
Temperature range –40°C to +90°C
EN

10 | nVent.com nVent.com | 11
Sensor data Temperature Resistance in kOhm
–40°C 32,34
–35°C 24,96
–30°C 19,48
–25°C 15,29
–20°C 12,11
–15°C 9,655
–10°C 7,763
–5°C 6,277
0°C 5,114
+5°C 4,188
+10°C 3,454
+15°C 2,862
+20°C 2,387
+30°C 1,684
+40°C 1,211
+50°C 0,8854
+60°C 0,6587
+70°C 0,4975
+80°C 0,3807
Approval VDE approval pending-VDE according to
EN60730 EMC According to EN 50081-1/2
for emission and EN50082 - 1/2 for immunity
Temperature for bal pressure +100°Ctest
(DIN EN 60730/VDE 0631-1)
Rated impulse voltage: Overvoltage category III
(DIN EN 60730/ VDE 0631-1)
4. OPERATION
The Raystat V5 has a LED user screen interface:
The unit will switch to the main screen after 2 minutes of non-interaction on the
parameter input screens.
4.1 Quick install
When the unit is powered up for the rst time, a quick setup must be executed before
the unit is ready to start. The Quick start helps to set all important settings, the
unit will go in main screen mode automatically when done. Quick start is sucient
for normal operations. More settings are available in the Setup menu for special
installation conditions.
The Quick start will only start if no pre-setting is done.
The parameters can be changed by pressing the check mark button for 6 sec.
The controller can be protected by a keylock. If this keylock function is active, the
code (see SP 12 in parameter list) needs to be entered to unlock the unit. Resetting
the Raystat V5 to factory settings is done by simultaneously pressing the arrow up,
down arrow and OK buttons for 6 seconds.
Parameter overview :
PARAMETER
Operation
Mode:
LINE
Operation
Mode:
PASC
Description Factory
settings
SP1 SET Temperature +3°C
SP2 Operation mode selection -----
SP3 Lowest ambient
temperature -20°C
SP4 Average pipe diameter
level
2
>= DN 25 / 1”
SP5 Heater operation in
sensor failure mode ON
SP6 Heater operation via
external contactor No
SP7 Hysteresis 1 K
SP8 Low temperature alarm 0°C
SP9 Higher temperature alarm +65°C
SP10 Alarm sound status ON
SP11 TEST program OFF
SP12 KEY LOCK – Pass code OFF
Error codes :
Error
Code
Error
description Remedy
Er 2.1 Sensor open
1. Check sensor cable connection
2. Verify operation of unit
3. Replace unit if cable ok & error still exists
Er 2.2 Sensor short
1. Check sensor connection
2. Replace sensor
3. Replace unit if sensor ok & error still exists
Er 3.1
Low
temperature
alarm
1. Verify heating system and sensor position
2. Verify menu settings of high temperature alarm
Er 3.2
High
temperature
alarm
1. Verify heating system and sensor position
2. Verify menu settings of high temperature alarm
Er 5.0 Heating cable
disconnected Verify heating cable connection
Er 6.0 Internal error Replace unit

12 | nVent.com nVent.com | 13
3. INSTALLATIONSHINWEISE
Die Installation und, sofern erforderlich, die Wartung und das Öffnen der Einheit
müssen von einer Elektrofachkraft vorgenommen werden. Daneben muss die Installa-
tion die örtlichen Bestimmungen erfüllen.
Ermitteln Sie die maximale Heizkreislänge für den von Ihnen verwendeten
Leitungsschutzschalter anhand der nachstehenden Tabelle :
Leitungsschutzschalter (C-Charakteristik) bei einer maximalen Heizkreislänge und
230 V AC sowie einer Einschalttemperatur von 20 °C.
Sofern größere Heizkreislängen erforderlich sind, müssen mehrere Einheiten mit
jeweils eigener Stromversorgung verwendet werden. Wir empfehlen die Verwendung
von Schaltschränken des Typs nVent RAYCHEM SV-SBS, um 3, 6 oder 9 Heizkreise
zu betreiben.
10XL2-LH 15XL2-LH 26XL2-LH 31XL2-LH
Schutzschalter (braun) (grün) (blau) (violett)
C 10A 140 m 90 m 80 m 67m
C 13A 195 m 120 m 110 m 88m
C 16A 215 m 135 m 135 m 110m
C 20A 215 m 160 m 135 m 118m
Der nVent RAYCHEM Raystat V5 hat ein abnehmbares Oberteil. Das Oberteil und das
Unterteil des Gehäuses enthalten elektronische Bauteile und sind über ein Ethernet-Kabel
miteinander verbunden. Bei Auslieferung sind Ober- und Rückteil demontiert.
Achtung: Als Überspannungsschutz (z. B. bei Gewitter) wird der Einsatz von externen
Überspannungsschutzkomponenten empfohlen.
Pege und Wartung
Reinigen Sie das Gehäuse des RAYSTAT v5 mit einem weichen, leicht angefeuchteten
Tuch und vermeiden Sie jegliche Lösungsmittel.
Vermeiden Sie, dass Wasser unmittelbar auf das Gerät gelangt. Verwenden Sie
keinen Wasserschlauch oder ein Hochdruckreinigungsgerät!
3.1. Beschreibung
nVent RAYCHEM Raystat V5 ist ein elektronischer Regelthermostat mit Anzeige,
fortschrittlichen Alarmeinrichtungen und der Möglichkeit, große Ströme (20 A) zu
schalten. Der Raystat V5 wurde zur Steuerung von nVent Begleitheizungssystemen
entwickelt. Das Heizband kann entweder direkt vom Raystat V5 oder über ein Schütz
gesteuert (EIN/AUS geschaltet) werden.
Für Heizlasten bis 20 A ist ein direktes Schalten der Heizbänder möglich.
Bei Heizlasten mit über 20 A Schaltstrom ist eine indirekte Schaltung über ein gee-
ignetes, von einem Raystat V5 gesteuertes Schütz erforderlich.
Die Installation und alle Verkabelungen müssen den geltenden Vorschriften entsprechen.
Das Gerät darf nur in nicht explosionsgefährdeten Bereichen installiert werden. nVent
bietet andere Steuerungen für den Einsatz in explosionsgefährdeten Bereichen.
Der Sensor muss installiert werden. Achtung: Die Sensorposition am Rohr oder
in der Luft muss mit der Betriebsart Linie oder PASC (Umgebungstemperatur
übereinstimmen Messsteuerung). Eine falsche Zuordnung kann zu einem
eingefrorenen Rohr führen. Eine Alarmklemme ermöglicht die Fernmeldung von
Fehlern. Der Raystat V5 kann im stromlosen Zustand vorprogrammiert werden durch
Anschluss eines externen Charger/Batterie ( z.Bsp. Raychem- PB Powerbank) über
die USB-Schnittstelle.
3.2. Technische Daten
Produktanwendung Nur für nVent RAYCHEM
Rohrleitungsfrostschutz Heizbänder
Elektrische Daten
Betriebsspannung 230 VAC –15 /+10%; 50 Hz
Leistungsaufnahme 5,3 W max
Stromversorgungsrelais
(Heizband) 25 A / 230 VAC
Anschlussklemmen 3 x 6 mm² max
Heizbandklemmen 3 x 6 mm² max
Alarmklemmen 3 x 1,5 mm² max
Fühlerklemme - Rohrleitung /
Umgebungstemperatur 2 x 1,5 mm² max
Alarmrelais
Einpoliger, potenzialfreier Wechselschalter
Spannungsfrei; Max. Schaltkapazität
1 A/30 VDC 0.5 A/125 VAC, Max.: 60 VDC/125
VAC
Leitungsschutzschalter Max. C 20 A (C-Charakteristik)
Einstellungen Alle Einstellungen werden in einem nichtüchti-
gen Speicher abgelegt
Betriebstemperatur –40°C bis +40°C
Einstellbare Haltetemperatur 0° C bis +85°C
Gehäuse
Material Polycarbonat
Maße 210 mm x 90 mm x 85 mm
Schutzart IP 65
Gewicht 990 g
Montage Montage auf DIN-Schiene (35 mm)
Kabelverschraubung 2 x M25 und 2 x M20
Lagertemperatur –40°C bis +50°C
Entammbarkeitsklasse Kategorie D (DIN EN 60730/VDE 0631-1)
Fühler
Temperaturfühler-Typ Standard NTC 2,0 kOhm bei 25°C, zweiadrig
Maße Fühlerspitze Ø 5 mm; Länge 20 mm
Fühlerkabellänge 5 m; verlängerbar auf 150 m , 2 x1,5 mm²
Temperaturbereich –40°C bis +90°C
DE

14 | nVent.com nVent.com | 15
Fühlerdaten Temperatur Widerstand in KΩ
–40°C 32,34
–35°C 24,96
–30°C 19,48
–25°C 15,29
–20°C 12,11
–15°C 9,655
–10°C 7,763
–5°C 6,277
0°C 5,114
+5°C 4,188
+10°C 3,454
+15°C 2,862
+20°C 2,387
+30°C 1,684
+40°C 1,211
+50°C 0,8854
+60°C 0,6587
+70°C 0,4975
+80°C 0,3807
Zulassungen VDE - Genehmigung noch ausstehend - VDE
gemäß EN 60730 EMV gemäß EN 50081-1/2
für Störaussendungen und EN 50082-1/2 für
Störfestigkeit Temperatur für Kugeldruckprü-
fung: +100 °C (DIN EN 60730/VDE 0631-1)
Bemessungsstoßspannung:
Kategorie III (DIN EN 60730/VDE 0631-1)
4. BETRIEB
Der Raystat V5 wird über einen LED Screen mit 3 Eingabetasten bedient.
Ist die LED-Anzeige für die Parametereingabe geöffnet, wechselt dieser nach 2
Minuten Inaktivität zum Hauptbildschirm zurück.
4.1 Schnellinbetriebnahme
Bei der Erstinbetriebnahme des Temperaturstellers muss zuerst eine
Schnellinbetriebnahme vorgenommen werden, bevor das System betriebsbereit ist.
Diese Schnellinbetriebnahme unterstützt Sie bei allen wichtigen Einstellungen.
Nach deren Beendigung wechselt der Temperatursteller automatisch zum
Hauptbildschirm. Für den Normalbetrieb ist eine Schnellinbetriebnahme in der Regel
ausreichend. Für spezischere Installationen können weitere Einstellungen im
Parameter-Menü vorgenommen werden.
Die Schnellinbetriebnahme startet nur, wenn keine Voreinstellung vorgenommen
wurde.
Die Parameter können durch Drücken der Häkchen-Taste für 6 Sekunden geändert
werden. Die Steuerung kann durch eine Tastemsperre geschützt werden. Wenn
diese Tastensperrfunktion aktiv ist, muss die Zahlenkombination (siehe SP 12 in der
Parameterliste) eingegeben werden, um das Gerät zu entsperren. Ein Zurücksetzen
des Raystat V5 auf Werkseinstellungen erfolgt mit dem gleichzeitigen Drücken der
Tasten Pfeil oben, Pfeil unten und OK Taste für 6 Sekunden.
Parameterübersicht :
Sollwert-
PARAMETER
Betriebsart:
Anlegefühler
LINE
Betriebsart:
Umgebungs-
temperatur
PASC
Beschreibung Werks-
einstellungen
SP1 Sollwert Temperatur +3°C
SP2 Betriebsart auswählen -----
SP3 Sollwert für niedriegste
Umgebungstemperatur -20°C
SP4 Durchschnittlicher
Rohrleitungsdurchmesser
2
>= DN 25 / 1”
SP5 Heizungsstatus im Fühler-
Fehlerfall ON
SP6 Steuerung über externen
Schaltschütz No
SP7 Hysterese 1 K
SP8 Sollwert
Untertemperaturalarm 0°C
SP9 Sollwert
Übertemperaturalarm +65°C
SP10 Alarmton status ON
SP11 Testprogramm OFF
SP12 Tastensperre OFF
Fehler Codes :
Fehler
Code Fehlerbeschreibung Fehlerbehebung
Er 2.1 Fühler offen
1. Fühleranschlüsse überprüfen
2. Fühlerwerte überprüfen
3. Steuergerät ersetzen, wenn Fühler in Ordnung ist
und Fehler weiterhin angezeigt wird
Er 2.2 Fühler Kurzschluss
1. Fühleranschlüsse überprüfen
2. Fühlerwerte überprüfen
3. Steuergerät ersetzen, wenn Fühler in Ordnung ist
und Fehler weiterhin angezeigt wird
Er 3.1 Untertemperatur
Alarm
1. Überprüfung des Begleitheizsystems und der
Fühlerposition
2. Überprüfe der Sollwerteinstellungen für
Untertemperturalarm
Er 3.2 Übertemperatur
Alarm
1. Überprüfung des Begleitheizsystems und der
Fühlerposition
2. Überprüfe der Sollwerteinstellungen für
Übertemperturalarm
Er 5.0 Heizband nicht
angeschlosen Heizbandanschluß überprüfen
Er 6.0 Interner Fehler Steuergerät austauschen

16 | nVent.com nVent.com | 17
ZH 区段测试
RU Тест
LT Segmento testas
1.2 Quickstart
RAYSTAT
1 sec
RAYSTAT
3 sec
EN Unit name Raystat Version 5
DE Gerätename Raystat Version 5
FR Nom de l’unité Raystat Version 5
SV Enhetsnamn Raystat version 5
NO Enhetsnavn Raystat Versjon 5
DK Enhedsnavm Raystat Version 5
NL Naam toestel Raystat versie 5
PL Nazwa jednostki: Raystat wersja 5
CZ Název jednotky Raystat verze 5
ZH 单元名称 Raystat Version 5
RU Нименование устройства Raystat версия 5
LT Įrenginio pavadinimas Raystat Version 5
PART 2 OPERATIONAL MANUAL
Program start
1.0 QUICK START:
1.1 Quickstart
RAYSTAT
Power supply, Stromkabel, Câble d’alimentation,
Anslutningskabel, Tilkoblingskabel, tilslutningskabel,
Voedingskabel, Kabel zasilający, Vstupní napětí, 电力电缆,
кабель питания, Maitinimo kabelis
Heating cable, Heizband, Ruban chauffant, Värmekabel,
Varmekabel, Varmekabel, Verwarmingskabel, Przewód
grzejny, Topný kabel, 伴热电缆, нагревательный кабель,
Šildymo kabelis
Line sensing, Fühlermodus, Anlegerfühler, Détection de
la température de la ligne, Temperaturavkänning på röret,
Temperaturføler på røret, Rørføler, Lijnstemperatuurvoeler,
Pomiar temperatury na rurociągu, Čidlo na potrubí, 管线感应 ,
терпературе поверхности, Vamzdyno temperatūros jutiklis
Ambient sensing, Umgebungsfühler, Détection de
la température ambiante, Temperaturavkänning
i luften, Omgivelsestemperatur, Luftføler,
Omgevingstemperatuurvoeler, Pomiar temperatury otoczenia,
Čidlo vzduchu, 环境感应, или окружающей среды, Aplinkos
temperatūros jutiklis
Alarm, Alarme, Larm, 报警, Тревога, Aliarmas
~ 4 sec
RAYSTAT
2 sec
EN Segment Test
DE Display Anzeige
FR Essai segment
SV Segment test
NO Segment test
DK Segment test
NL Test segment
PL Test wyświetlacza
CZ Test segmentů

18 | nVent.com nVent.com | 19
ZH 快速启动:选择管线温度感应或环境温度感应(PASC比例环境感应控制)的运
行模式
RU
Быстрый запуск: Выберите режим измерения температуры по
терпературе поверхности или окружающей среды
(PASC –пропорциональное регулирование по температуре
окружающей среды)
LT Greitas paleidimas: pasirinkite daviklio ar aplinkos temperatūros režimą
(PASC - proporcingas aplinkos temperatūrai valdymas)
1.5 Quickstart
Parameter
LINE:
0 °C... +90 °C
PASC:
0 °C... +30 °C
DEFAULT: 3°C
RAYSTAT
EN Quick start: Choose Setpoint Temperature
DE Schnellstart: Eingabe Soll-Temperaturwert
FR Démarrage rapide: choisir température de consigne
SV Snabbstart: Välj börvärde temperatur
NO Quick start: velg setpunkt temperatur
DK Hurtig start: vælg temperature setpunkt
NL Snel start : Selecteer gewenste temperatuur
PL Szybkie uruchomienie: Wybierz nastawę temperatury
CZ Rychlý start: Nastavte požadovanou teplotu
ZH 快速启动:选择设定点温度
RU Быстрый старт: Выберите уставку температуры
LT Greitas paleidimas: nustatykite norimą temperatūrą
1.3 Quickstart
RAYSTAT
3 sec
EN Firmware Revision number
DE Firmware Revisionsnummer
FR Version du logiciel
SV Firmware revisionsnummer
NO Firmware revisjonsnummer
DK Firmware revisionsnummer
NL Versienummer software
PL Nr rewizji rmware
CZ Číslo revize rmware
ZH 固件改版编号
RU Программное обеспечение Номер прошивки
LT Programinės įrangos versijos numeris
1.4 Quickstart
Parameter
DEFAULT: - - - -
LINE
PASC
RAYSTAT
EN Quick start: Select Operation Mode for line or ambient temperatures sensing
(PASC - Proportional Ambient Control sensing)
DE Schnellstart: Wählen Sie den Fühlermodus Anlegerfühler (linE) oder
Umgebungsfühler (PASC) aus
FR Démarrage rapide: choisir mode d’operation pour emplacement sonde
(PASC – contrôle proportionel avec sonde ambiante)
SV Snabbstart: Välj driftläge för temperaturgivare på rör eller i luft
(PASC – Proportionerlig reglering mot omgivningstemperaturen)
NO Quick start: velg driftsmodus for temperaturføler på rør eller luft
(PASC – Proporsjonerlig regulering mot omgivelsestemperaturen)
DK Hurtig start: Vælg driftindstilling for føler på rør eller
omgivelsestemperatur (PASC)
NL Snel start: Selecteer functiemodus voor lijn- of omgevingstemperatuurvoeler
(PASC – Proportional Ambient Control Sensing)
PL Szybkie uruchomienie: Wybierz Tryb Pracy z powierzchniowym pomiarem
temperatury lub pomiarem temperatury otoczenia (PASC – Sterowanie
proporcjonalne względem temperatury otoczenia)
CZ Rychlý start: Zvolte režim spínání dle čidla teploty na potrubí (LinE), nebo dle
okolní teploty vzduchu (PASC proporcionální řízení dle teploty vzduchu)

20 | nVent.com nVent.com | 21
RU Настройка SP4 (только для PASC): Выбор диаметра трубопровода
LT (tik PASC): Vidutinis vamzdžio skersmuo
1.8 Quickstart
Parameters
YES/NO
DEFAULT: NO
RAYSTAT
EN Heater operation via external contactor (only if no load is connected)
DE Heizungsbetrieb über externen Schütz ( Abfrage erscheint nur wenn keine
Last direkt angeschlossen ist)
FR Alimentation traçage par contacteur
SV Värmeelement via extern kontaktor
NO Varmeelement via ekstern kontaktor
DK Varme via ekstern relæ
NL Aansluiting verwarmingslint via externe contactor
PL Załączanie ogrzewania przez zewnętrzny stycznik
CZ Provozní režim spínání stykačem
ZH 伴热线通过外部接触器运行
RU Управление обогревом через внешний контактор
LT Šildymas per išorinį kontaktorių
1.6 Quickstart
Parameters
DEFAULT: -20°C
: -30 - 0°C
RAYSTAT
EN (PASC ONLY): Lowest ambient temperature
DE (nur für PASC gültig): Minimale Umgebungstemperatur
FR (uniquement pour PASC): Temperature ambiante minimale
SV (endast PASC): Lägsta omgivningstemperatur
NO (kun PASC): Laveste omgivelsestemp
DK (kun PASC): Laveste temperatur
NL (enkel PASC): Laagste omgevingstemperatuur
PL (tylko tryb PASC): Najniższa temperatura otoczenia
CZ (pouze PASC): Nejnižší teplota vzduchu
ZH (仅PASC感应):最低环境温度
RU (только для PASC): Минимально возможная температура окр. воздуха
LT (tik PASC): Žemiausia aplinkos temperatūra
1.7 Quickstart
Parameters
01 = Ø < DN 25 / 1”
02 = Ø ≥ DN 25 / 1”
03 = Ø ≥ DN 50 / 2”
DEFAULT: 01
RAYSTAT
EN (PASC only): Average pipe diameter level
DE (nur für PASC gültig) Durchschnittlicher Rohrdurchmesser Level
FR (PASC uniquement) Moyenne de diamètre de la tuyauterie
SV (endast PASC): Nivå på medelvärde rördiameter
NO (kun PASC): Gjennomsnittlig rørdiameter
DK (kun PASC): Gennemsnit rørdiameter
NL (enkel PASC): Gemiddelde buisdiameter
PL (tylko tryb PASC): Poziom średniej średnicy rurociągu
CZ (pouze PASC): Průměrná hodnota všech průměrů potrubí
ZH 设定点SP4(仅PASC感应):平均管道直径等级

22 | nVent.com nVent.com | 23
2.2 PARAMETER LIST
2.2.0 Parameters
RAYSTAT
5 sec
EN Press Check button for 5 sec.to go in Parameter mode
DE Bestätigungstaste 5 Sek. gedrückt halten um zu den Sollwerteinstellungen
zu gelangen
FR Appuyer sur le bouton valider pendant 5 sec. pour entrer dans le menu
SV Tryck på godkännandeknappen i 5 sek. för att gå in i Parameter läge
NO Press godkjenningsknappen i 5sek. for å gå til parameter modus
DK Tryk på godkend-knappen i 5 sekunder for at gå i parametertilstand
NL Druk gedurende 5 sec op de bevestigingsknop om in het menu te gaan.
PL Wciśnij przycisk Zatwierdź przez 5 sek. aby przejść do trybu Parametry
CZ Stiskněte tlačítko na 5 sec. pro vstup do nastavení parametrů
ZH 长按确认按键5秒进入参数模式
RU Нажмите кнопку проверки на 5 сек для перехода в режим настройки
параметров
LT Paspauskite ir palaikykite patvirtinimo mygtuką 5 sekundes, kad pasiek-
tumėte parametrų meniu
2.1. DISPLAY
2.1.1 Display
RAYSTAT
2 sec
RAYSTAT
EN Main display: actual temperature (xxC), setpoint temperature
alternating ( txxC)
DE Hauptanzeige: Aktuelle Fühlerttemperatur(xxC) und Sollwerttemperatur
(txxC) alternierend angezeigt
FR Ecran principal: température actuelle (xxC) et température de consigne (txxC)
en alternance
SV Huvudmeny: Aktuell temperatur (xxC) och börvärde (txxC) alternerande
NO Hovedmeny: Aktuell temperatur(xxC), setpunkt temperatur
alternerende (txxC)
DK Hovedmeny: Nuværende temperatur (xxC) og setpunkt (txxC)
NL Hoofdscherm : afwisselend huidige temperatuur (xxC) en gewenste
temperatuur (txxC)
PL Wyświetlacz główny: Temperatura aktualna (xxC) naprzemiennie z nastawą
temperatury (txxC)
CZ Hlavní displej: skutečná teplota (xxC), nastavená teplota (txxC), střídají se.
ZH 主显示:实际温度(xxC),设定点温度交替(txxC)
RU Основной дисплей: текущая температура (ххС), температура
поддержания (txxC)
LT Pagrindinis ekranas: faktinė temperatūra (xxC), keičiama temperatūros
vertė (txxC)

24 | nVent.com nVent.com | 25
NL Instelpunt SP1 : Gewenste temperatuur
PL Nastawa SP1: Nastawa temperatury
CZ Menu SP1: Požadovaná teplota
ZH 设定点SP1:设定点温度
RU Настройка SP1: Настройка Температуры
LT Nustatymas SP1: nustatytoji temperatūra
2.2.3 Parameters
Parameters
LINE
PASC
RAYSTAT
RAYSTAT
RAYSTAT
EN Setpoint SP2: Operation mode (possible to change previously selected
parameter with up/down button)
DE Sollwert SP2: Betriebsmodus Für Anlegerfühler ( LinE) oder Umgebungstem-
peraturgesteuert ( PASC).Empfehlung für Rohranlegefühler: bei Kaltwasser-
leitungen : 3°C ; bei fetthaltigen Abwasserleitungen: 40°C
FR Consigne SP2: Mode d‘opération
SV Börvärde SP2: Driftläge
NO Setpunkt SP2: Drift modus
DK Setpunkt SP2: Drifttilstand
NL Instelpunt SP2 : Sensormodus
PL Nastawa SP2: Tryb pracy
CZ Menu SP2: Provozní režim
ZH 设定点SP2:运行模式
RU Настройка SP2: Выбор режима измерения
LT Nustatymas SP2: darbo režimas
2.2.1 Parameters
RAYSTAT
EN Escape from parameter settings
DE SP1 bis SP 12 Parameter erscheinen, über ESC -Verlassen der Sollwert-Ein-
stellungen
FR Quitter le paramètrage
SV Gå ur Parameter inställningar
NO Gå ut fra parameter innstillinger
DK Forlad parameter indstilling
NL Verlaat de instellingen
PL Wyjście z trybu Parametrów
CZ Ukončit nastavení parametrů
ZH 退出参数设置
RU Выход из режима настроек параметров
LT Išeiti iš parametrų meniu
2.2.2 Parameters
Parameters
DEFAULT: 3°C
LINE: 0 °C ... +90 °C
PASC: 0 °C ... -30 °C
RAYSTAT
RAYSTAT
EN Setpoint SP1: Setpoint Temperature
DE Sollwert SP1: Soll-Temperaturwert
FR Consigne SP1: température de consigne
SV Börvärde SP1: Börvärde temperatur
NO Setpunkt SP1: Setpunkt temperatur
DK Setpunkt SP1: Setpunkt temperatur

26 | nVent.com nVent.com | 27
FR Consigne SP4 (PASC uniquement) Moyenne de diamètre de la tuyauterie
SV Börvärde SP4 (endast PASC): Nivå på medelvärde rördiameter
NO Setpunkt SP4(kun PASC): Gjennomsnittlig rørdiameter
DK Setpunkt: SP4 ( kun PASC) Gennemsnit rørdiameter
NL Instelpunt SP4 (alleen PASC) : Gemiddelde buisdiameter
PL Nastawa SP4 (tylko tryb PASC): Poziom średniej średnicy rurociągu
CZ Menu SP4 (pouze PASC): Průměrná hodnota všech průměrů potrubí
ZH 设定点SP4(仅PASC感应):平均管道直径等级
RU Настройка SP4 (только для PASC): Выбор диаметра трубопровода
LT Nustatymas SP3 (tik PASC): Vidutinis vamzdžio skersmuo
2.2.6 Parameters
Parameters
DEFAULT: ON
ON/OFF
RAYSTAT
RAYSTAT
EN Setpoint SP5: Heater operation in sensor failure mode
DE Sollwert SP5: Heizungsbetrieb bei Fühlerfehler (EIN: ON oder AUS: OFF)
FR Consigne SP5: Activation du traçage en cas de défaut sonde
SV Börvärde SP5: Driftläge på värme vid fel på temperaturgivare
NO Setpunkt SP5: Driftmodus på varme ved feil på føler
DK Setpunkt SP5: Varmekabel indstilling ved følerfejl
NL Instelpunt SP5 : Werking van verwarmingslint bij sensorfout
PL Nastawa SP5: Załączenie ogrzewania w trybie awarii czujnika
CZ Menu SP5: Provozní režim při poruše čidla
ZH 设定点SP5:伴热线在感应故障模式下运行
RU Настройка SP5: Вариант работы в режиме отказа датчика
LT Nustatymas SP5: Šildymo režimas jutiklio gedimo metu
2.2.4 Parameters
Parameters
: –30°C ….0°C
RAYSTAT
RAYSTAT
EN Setpoint SP3 (PASC only): Lowest ambient temperature
DE Sollwert SP3: (nur für PASC gültig) Minimale Umgebungstemperatur
FR Consigne SP3: Température ambiante minimale
SV Börvärde SP3 (endast PASC): Lägsta omgivningstemperatur
NO Setpunkt SP3(kun PASC) Laveste omgivelsestemp
DK Setpunkt SP3 ( kun PASC) Laveste temperatur
NL Instelpunt SP3 (alleen PASC) : Laagste omgevingstemperatuur
PL Nastawa SP3 (tylko tryb PASC): Najniższa temperatura otoczenia
CZ Menu SP3 (pouze PASC): Nejnižší teplota vzduchu
ZH 设定点SP3(仅PASC感应):最低环境温度
RU Настройка SP3 (только для PASC):
Минимально возможная температура окр. воздуха
LT Nustatymas SP3 (tik PASC): Žemiausia aplinkos temperatūra
2.2.5 Parameters
Parameters
DEFAULT: 01
01 = Ø < DN 25 / 1”
02 = Ø ≥ DN 25 / 1”
03 = Ø ≥ DN 50 / 2”
RAYSTAT
RAYSTAT
EN Setpoint SP 4 (PASC only): Average pipe diameter level
DE Sollwert SP4: (nur für PASC gültig) Durchschnittlicher Rohrdurchmesser Level

28 | nVent.com nVent.com | 29
2.2.8 Parameters
Parameters
1-5
DEFAULT: 1C
RAYSTAT
RAYSTAT
EN Setpoint SP7 (Line only): Hysteresis
DE Sollwert SP7 (nur für Anlegerfühler Modus) : Hysterese
FR Consigne SP7 (Sonde sur tuyauterie uniquement): Hysteresis
SV Börvärde SP7 (Endast givare på rör): Hysteres
NO Setpunkt SP7(Kun føler på rør): Hysterese
DK Setpunkt SP7: ( kun ved føler på rør) Hysterese
NL Instelpunt SP7 (alleen lijnsensor) : Hysteresis
PL Nastawa SP7 (Tylko w przypadku czujnika na rurze): Histereza
CZ Menu SP7 (pouze čidlo na potrubí): Hystereze
ZH 设定点SP7(仅管线感应):迟滞
RU Настройка SP7 (только для управления по термпературе поверхности)
Гистерезис
LT Nustatymas SP7 (tik daviklio rėžimui): Histerezė
2.2.7 Parameters
Parameters
YES/NO
DEFAULT: NO
RAYSTAT
RAYSTAT
EN Setpoint SP6: Heater operation via external contactor
DE Sollwert SP6: Heizungsbetrieb über externen Schütz
FR Consigne SP6: Alimentation traçage par contacteur
SV Börvärde SP6: Värmeelement via extern kontaktor
NO Setpunkt SP6: Varmeelement via ekstern kontaktor
DK Setpunkt SP6: Varme via ekstern relæ
NL Instelpunt SP6 : Aansluiting verwarmingslint via externe contactor
PL Nastawa SP6: Załączanie ogrzewania przez zewnętrzny stycznik
CZ Menu SP6: Provozní režim spínání stykačem
ZH 设定点SP6:伴热线通过外部接触器运行
RU Настройка SP6: Управление обогревом через внешний контактор
LT Nustatymas SP6: Šildymas per išorinį kontaktorių

30 | nVent.com nVent.com | 31
2.2.10 Parameters
Parameters
OFF/65°C
DEFAULT: 65°C
RAYSTAT
RAYSTAT
: 2 - 90°C
EN Setpoint SP9 (Line only): Higher temperature alarm
DE Sollwert SP9 (nur für Anlegerfühler-Modus) : Oberer Temperaturalarm
Empfehlung: Heizungsleitungen: max. 65°C; Fetthaltige Abwasserleitungen:
max. 85°C
FR Consigne SP9 (Sonde sur tuyauterie uniquement) : Alarme température élevée
SV Börvärde SP9 (Endast för givare på rör): Larm för hög temperatur
NO Setpunkt SP9(Kun føler på rør) Alarm for høy temperatur
DK Setpunkt SP9: ( kun ved føler på rør) Høj temperatur alarm
NL Instelpunt SP9 (alleen lijnsensor): Alarm hoge temperatuur
PL Nastawa SP9 (Tylko w przypadku czujnika na rurze): Alarm wysokiej temperatury
CZ Menu SP9 (pouze čidlo na potrubí): Alarm vysoké teploty
ZH 设定点SP9(仅管线感应):高温报警
RU Настройка SP9 (только для управления по термпературе поверхности)
Сигнализация повышенной температуры
LT Nustatymas SP9 (tik daviklio rėžimui): per aukštos temperatūros aliarmas
2.2.9 Parameters
Parameters
OFF/-40C
DEFAULT: 0°C
RAYSTAT
RAYSTAT
: -40 - +78°C
EN Setpoint SP8 (Line only): Low temperature alarm
DE Sollwert SP8 (nur für Anlegerfühler-Modus) : Unterer Temperaturalarm
FR Consigne SP8 (Sonde sur tuyauterie uniquement) : Alarme température basse
SV Börvärde SP8 (Endast för givare på rör): Larm för låg temperatur
NO Setpunkt SP8(Kun føler på rør): Lav temperatur alarm
DK Setpunkt SP8: (kun ved føler på rør) Lav temperatur alarm
NL Instelpunt SP8 (alleen lijnsensor) : Alarm lage temperatuur
PL Nastawa SP8 (Tylko w przypadku czujnika na rurze): Alarm niskiej temperatury
CZ Menu SP8 (pouze čidlo na potrubí): Alarm nízké teploty
ZH 设定点SP8(仅管线感应):低温报警
RU Настройка SP8 (только для управления по термпературе поверхности)
Сигнализация низкой температуры
LT Nustatymas SP8 (tik daviklio rėžimui): per žemos temperatūros aliarmas

32 | nVent.com nVent.com | 33
DE Sollwert SP11: Testprogram starten für eine Zeitdauer von 30 min
FR Consigne SP11: Le programme de test démarre, max. durée de 30 min
SV Börvärde SP11: Testprogram startar, varar i max 30 min.
NO Setpunkt SP11: Test program starter, max. 30min lengde
DK Setpunkt SP11: Testprogram starter, maks. 30 min
NL Instelpunt SP11 : Testprogramma start, duurt max. 30 min
PL Nastawa SP11: Rozpoczyna się program testowy, czas trwania maks. 30 min.
CZ Menu SP11: Start programu test, max. doba je 30 min.
ZH 设定点SP11: 测试程序启动,最长持续30分钟
RU Настройка SP11: Тестю длится не менее 30 мин
LT Nustatymas SP11: Testinė programa prasideda, maks. 30 min trukmė
2.2.13 Parameters
Parameters
Code Nr: 036
DEFAULT: 000
RAYSTAT
RAYSTAT
EN Setpoint SP12: Activate/deactivate Key Lock / code: 036
DE Sollwert SP12: Tastemsperre aktivieren/deaktivieren. Eingabe code ist: 036
FR Consigne SP12: Activer/désactiver le verrouillage. Code: 036
SV Börvärde SP12: Aktivera/ deaktivera låsning. Kod: 036
NO Setpunkt SP12: Aktiver/deaktiver lås. Kode: 036
DK Setpunkt SP12: Aktivere/deaktivere key lock. Kode: 036
NL Instelpunt SP12: Vergrendeling in-/uitschakelen. Code: 036
PL Nastawa SP12: Aktywuj/deaktywuj blokadę klawiszy. Kod: 036
CZ Menu SP12: Aktivace / deaktivace zámku kláves. Kód: 036
ZH 设定点SP12: 激活/取消按键锁定. 代码: 零三六
RU Настройка: SP12: Вкл./Выкл. Режима Блокировки. код: 036
LT Nustatymas SP12: Įjungti / išjungti mygtukų užrakinimą. Kodas: 036
2.2.11 Parameters
Parameters
ON/OFF
DEFAULT: ON
RAYSTAT
RAYSTAT
EN Setpoint SP10 Alarm sound status
DE Sollwert SP10 Alarmton
FR Consigne SP10 Signal sonore
SV Börvärde SP10 Larmsignal
NO Setpunkt SP10 Alarmsignal
DK Setpunkt SP10: Alarmsignal
NL Instelpunt SP10 Geluidsalarm
PL Nastawa SP10 Stan alarmu dźwiękowego
CZ Menu SP10 Alarm - zvuk bzučáku
ZH 设定点SP10 报警声音状态
RU Настройка SP10 Звук Сигнализации
LT Nustatymas SP10 Garsinio signalo statusas
2.2.12 Parameters
Parameters
YES/NO
DEFAULT: NO
RAYSTAT
RAYSTAT
EN Setpoint SP11: Test program starts, max. 30 min duration

Worldwide Headquarters
Tel 800-545-6258
Fax 800-527-5703
België / Belgique
Tel. +32 16 21 35 02
Fax +32 16 21 36 04
Česká Republika
Tel. +420 602 232 969
China
Tel. +86.21.2412.1688
Denmark
Tel. +45 70 11 04 00
Deutschland
Tel. 0800 1818205
Fax 0800 1818204
España
Tel. +34 911 59 30 60
Fax +34 900 98 32 64
France
Tél. 0800 906045
Fax 0800 906003
Italia
Tel. +39 02 577 61 51
Fax +39 02 577 61 55 28
Казахстан
Тел.: +7 7122 325 554
Факс: +7 7122 586 017
Nederland
Tel. 0800 0224978
Fax 0800 0224993
Norge
Tel. +47 66 81 79 90
Österreich
Tel 0800 29 74 10
Fax 0800 29 74 09
Polska
Tel. +48 22 331 29 50
Fax +48 22 331 29 51
Россия
Тел. +7 495 926 18 85
Факс +7 495 926 1886
Schweiz / Suise
Tel. +41 (41) 766 3080
Fax +41 (41) 766 3081
Suomi
Puh. 0800 11 67 99
Sverige
Tel. +46 31 335 58 00
Türkiye
Tel. +90 560 977 6467
Fax +32 16 21 36 04
United Kingdom
Tel. 0800 969 013
Fax 0800 968 624
Lietuva
Tel. +370 52136634
nVent.com
©2019 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its aliates.
All other trademarks are the property of their respective owners. nVent reserves the right to change
specications without notice.
RAYCHEM-IM-EU1535-RaystatV5-ML-1910 PCN 1244-022473
Table of contents
Other nvent Controllers manuals

nvent
nvent RAYCHEM T2000 Installation guide

nvent
nvent JBS-100-EC User manual

nvent
nvent RAYCHEM HWAT-ECO User manual

nvent
nvent RAYCHEM ECW-GF User manual

nvent
nvent RAYCHEM Elexant 4010i User manual

nvent
nvent raychem tcontrol-cont-03 Specification sheet

nvent
nvent RAYCHEM HWAT-ECO-16 User manual

nvent
nvent 910 Series Assembly instructions
Popular Controllers manuals by other brands

NEC
NEC PF5820 installation guide

Xylem
Xylem LOWARA FF128DP Series Installation, operation and maintenance manual

Viessmann
Viessmann 5232 Operation manual

Mitsubishi
Mitsubishi MELSEC iQ-F FX5-4AD-TC-ADP Hardware manual

Danfoss
Danfoss vlt aqua Design guide

Motorola
Motorola MaraTrac Advanced Control Head operating instructions