Installation instructions V50-...-280
OBO Bettermann GmbH & Co. KG 8
EN
Product description
Lightning current and surge protection device for
equipotential bonding of power supply systems
according to VDE 0100-443 (IEC 60364-4-44)
and for lightning protection equipotential bonding
according to VDE 0185-305 (IEC 62305). For
mounting on hat rails and use in distributor hous-
ings. Arresters (Figure 1) can be connected
individually and are encoded on the rear side, in
order to avoid incorrect connection. They pos-
sess a thermodynamic cut-off unit and have an
arresting capacity of up to 50 kA (8/20) and
12.5 kA (10/350) per pole.
If there is an error, the visual display switches
from grey to red (Figure ).
With snap-on hat rail bracket (Figure 2).
The spark gap C50-0-255 is intended as an ar-
rester between the neutral conductor N and the
protective conductor (PE conductor).
Only V50-..+FS..: With module for remote sig-
nalling through potential-free changeover contact
(Figure ).
Target group
The device may only be mounted and connected
by an electrical technician.
General safety information
• Before working on power cables, ensure that
they are de-energised and secure them against
unintentional switch-on!
• Do not carry out mounting work during a storm!
• Comply with national laws and standards, e.g.
VDE 0100-534 (IEC 60364-5-53)!
Mounting and installation
The device can be installed in any position (e.g.
vertical or horizontal).
Figure : VDE 0100-534 (IEC 60364-5-53)
specifies that,
– in the case of single-branch wiring,
the total
connection length a + b
– or, in the case of V wiring,
the connection
length c
should never exceed 0.5 m.
For V wiring, use the connection terminal, item
no. 5012 010.
Caution! Risk of overloading!
The connection terminal 5012 010 is
approved for a maximum current load ≤ 50
A.
Use a suitable back-up fuse!
EN Surge protection device
Item no. Type Product Protection
path ITotal 8/20 ITotal 10/350 IPE
Circuit
diagram
Figure
5093 508 V50-0-280 Single arrester* – – – – –
5093 500 V50-1-280 Single pole L – PE/N – – < 600 µA 1
5093 511 V50-3-280 Three-pole L – PE/N 120 kA 37,5 kA < 100 μA 3
5093 513 V50-4-280 Four-pole L – PE,
N – PE 160 kA 50 kA < 100 μA
5093 522 V50-1+NPE-280 Single-pole with NPE L – N, N – PE 80 kA 25 kA < 5 μA
5093 524 V50-2+NPE-280 Two-pole with NPE L – N, N – PE 80 kA 37,5 kA < 5 μA
5093 526 V50-3+NPE-280 Three-pole with NPE L – N, N – PE 80 kA 50 kA < 5 μA
5093 502 V50-1+FS-280 Single-pole with FS L – PE/N – – < 600 μA
5093 516 V50-3+FS-280 Three-pole with FS L – PE/N 120 kA 37,5 kA < 100 μA
5093 518 V50-4+FS-280 4-pole with FS L – PE,
N – PE 160 kA 50 kA < 100 μA 4
5093 531 V50-1+NPE+FS-280 Single-pole with NPE/
FS L – N, N – PE 80 kA 25 kA < 5 μA
5093 533 V50-3+NPE+FS-280 Three-pole with NPE/
FS L – N, N – PE 80 kA 37,5 kA < 5 μA 7
5095 609 C50-0-255 Single arrester* – – – –
*Figure