ODA MX Series User manual

www.odacore.com
Switching Type Programmable DC Power Supply
MX Series
User Manual
Manual Part NO. 018MX-1.0

Legal notice
© ODA Technologies Co., Ltd. 2018
No part of this document may be photocopied, reproduced, or translated to another language without
the prior another language without the prior agreement and written consent of ODA agreement and
written consent of ODA Technologies.,Co.Ltd. as governed by Korea and international copyright laws.
Warranty Certification
The material contained in this document is provided “as is,” and is subject to being changed, without
notice, in future editions. Further, to the maximum extent permitted by applicable law, ODA disclaims
all warranties, either express or implied, with regard to this manual and any information contained
herein, including but not limited to the implied warranties of merchantability and fitness for a particular
purpose. ODA shall not be liable for errors or for incidental or be liable for errors or for incidental or
consequential damages in connection with the furnishing, use, or performance of this document or of
any information contained herein. Should ODA and the user have a separate written agreement with
warranty terms covering the material in this document that conflict with these terms, the warranty terms
in the separate agreement shall control.
Assistance
This product comes with the standard product warranty. Warranty options, extended support contacts,
product maintenance agreements and customer assistance agreements are also available.
Contact your nearest ODA Technologies. Sales and Service office for further information on
ODA Technologies. full line of Support Programs. Refer to below information.
www.odacore.com
+82-2-1800-8644
Waste Electrical and Electronic Equipment
The affixed product label (see right) indicates that you must not discard
this electrical/electronic product in domestic household waste. Do not
dispose in domestic household waste. To return unwanted products,
contact our local ODA distributors, or call us for more information.
Manual Editions
Manual Part Number: 018MX-1.0
Edition 2, February, 2018 Printed in ROK
Reprints of this manual containing minor corrections and updates may have the same printing date.
Revised editions are identified by a new printing date.

Safety Notices
The following general safety precautions must be observed during all phases of operation of this
instrument. Failure to comply with these precautions or with specific warnings or instructions elsewhere
in this manual violates safety standards of design, manufacture, and intended use of the instrument.
ODA Technologies assumes no liability for the customer's failure to comply with these requirements.
In Case of Damage
Instruments that appear damaged or defective
should be made inoperative and secured against
CAUTION
A CAUTION notice denotes a hazard. It calls
attention to an operating procedure, practice, or
Verify that all safety precautions are taken. the like that, if not correctly performed or adhere
Make all connections to the unit before
applying power. Note the instrument's of important data. Do not proceed beyond a
external markings described under "Safety Symbols"
CAUTION notice until the indicated conditions
are fully understood and met.
Fuses
The instrument contains an internal fuse, which WARNING
is not customer accessible.
attention to an operating procedure, practice,
Do Not Operate in an Explosive Atmosphere or the like that, if not correctly performed or
Do not operate the instrument in the presence
of flammable gases or fumes.
death. Do not proceed beyond a WARNING
notice until the indicated conditions are fully
Do Not Remove the Instrument Cover
understood and met.
Only qualified, service-trained personnel who
are aware of the hazards involved should Location of parts
remove instrument covers. Always disconnect
Do not place power cord, equipment inlet,
the power cable and any external circuits before main switch, etc. to make it difficult to operate
removing the instrument cover. the equipment.
for service and repair to ensure that safety
instructions.
(provided with a protective earth terminal).
features of this product may be impaired if it is
the product to an ODA Sales and Service Office
used in a manner not specified in the operation
General
Do Not Modify the Instrument
Do not use this product in any manner not
Do not install substitute parts or perform any
specified by the manufacturer. The protective
unauthorized modification to the product. Return
packaging, warranty may not be assured.
features are maintained.
When returning, be sure to use the box that was
Ground the Instrument
originally packaged.
If there's any damage occurred from using other
This product is a Safety Class 1 instrument
To minimize shock hazard, the instrument
chassis and cover must be connected to an
electrical ground. The instrument must be
connected to the ac power mains through
A WARNING notice denotes a hazard. It calls
adhered to, could result in personal injury or
a grounded power cable, with the ground
interruption of the protective (grounding)
conductor or disconnection of the protective
wire firmly connected to an electrical ground
(safety ground) at the power outlet. Any
Before Applying Power
hazard that could result in personal injury.
earth terminal will cause a potential shock
qualified service personnel.
unintended operation until they can be repaired b
Keep the vents unobstructed.
Ventilation precautions
to, could result in damage to the product or loss

Safety Symbol
Direct current
Alternating current
Both direct and alternating current
Three phase alternating current
Off supply
Earth (ground) terminal
Protective earth ground terminal.
On supply
Frame or chassis terminal
Terminal is at earth potential.
Out position of a bi-stable
push switch
Caution, risk of electric shock
Standby supply. Unit is not
completely disconnected
from ac mains when switch is off
In position of a bi-stable push switch
Neutral conductor on permanently
installed equipment
Line conductor on
permanently installed equipment.
Caution, hot surface
Caution, refer to accompanying
documents
- 1 -

CONTENTS
1. General Information
-------------------------------------------------------------
6
1-1. Feature
-------------------------------------------------------------
6
General Feature
Remote Interface Characteristics
Calibration
Factory Function
Self Test Function
1-2. Accessories and Options
----------------------------------------------
7
Accessories
Options
1-3. Inspecting the Unit 8
Mechanical Check
Electrical Check
1-4. Operating Conditions 8
1-5. Check Before Power On 9
Power Cord Check
Rack Mounting
1-6. Check After Power On 10
Display Procedure on the LCD
Default Setting Values
1-7. Installation
-----------------------------------------------------------------
11
Cooling
Bench Operation
2. Front Panel, Rear Panel Composition & Function 12
2-1. Front-Panel Setting
------------------------------------------
18
18
2-3. Output Check
20
Voltage Output Check
Current Output Check
3. Front-Panel Operating 21
Over view 21
22
23
---------------------------------------------------------------
- 2 -
2-2. Rear Panel Composition
3-1. Constant Voltage (CV) Operating
3-2. Constant Current (CC) Operation

3-3. Remote Voltage Sensing 24
CV Regulation
Output Rating
Output Noise
Stability
Remote Voltage Sensing Connection
3-4. Programming Over Voltage Protection(OVP)
-----------------------
26
3-5. Programming Over Current Protection(OCP)
----------------------
29
3-6. Programming Under Voltage Limit(UVL) 31
3-7. Programming Over Voltage Limit(OVL) 32
3-8. Programming Under Current Limit(UCL) 33
3-9. Programming Over Current Limit(OCL) 34
35
36
RS232C Setting
RS232C Configuration
RS485 Setting
RS232C,RS485 Connection Drawing
TCP/IP Setting(Option)
Delimiter
Response
45
3-13. Store 46
3-14. Recall 47
3-15. Output ON/OFF 48
3-16. Error Message Display 49
4. CALIBRATION 50
4-1. Characteristics 50
4-2. Preparation for Calibration 50
4-3. Equipments required for Calibration
51
4-4. Technic of Calibration 51
Instruments Connection Drawing
Electronic Load
Current-Monitoring Resistor(shunt)
DVM(Digital Volt Meter)
Programming
Measuring Point
3-11. IO/Local
---------------------------------------------------------
3-12. Limit Display
---------------------------------------------------------
---------------------------------------------------------
3-10. Key Lock
-----------------------------------------------------
- 3 -
-----------------------------------------------------
----------------------
----------------------
----------------------
------------------------------------------------------------------
---------------------------------------------------------
----------------------
-----------------------------------------------------------
--------------------------------------------------------

53
Calibration Key Structure
Voltage Calibration
Current Calibration
4-6. Calibration by Remote Interface
----------------------
57
Instruments Connection
Command Procedure of Remote Calibration
Voltage Calibration
Current Calibration
5. FACTORY
-----------------------------------------------------------
59
5-1. Characteristic 59
5-2. Factory Key Structure 59
5-3. USER-MEM CLEAR 60
User-Memory Clear Operating
5-4. LAST STATE 61
LAST STATE Operating
5-5. AUTO CURSOR MV 62
AUTO CURSOR MV Operating
5-6. AUTO KEY LOCK 63
AUTO KEY LOCK Operating
5-7. OVP USE
64
OVP USE Operating
5-8. OCP USE 65
OCP USE Operating
5-9. ADC SAMPLING 66
ADC SAMPLING Operating
5-10. CAL-RESTORE 67
CAL-RESTORE Operating
5-11. CAL-BACKUP
67
CAL-BACKUP Operating
5-12. CAL-DEFAULT 68
CAL-DEFAULT Operating
5-13. LOAD DEFAULT 68
LOAD DEFAULT Operating
6. SCPI Command 69
6-1. Commands Syntax 69
- 4 -
--------------------------------------------------------
---------------------------------------------------
--------------------------------------------------
---------------------------------------------------
---------------------------------------------------
---------------------------------------------------
---------------------------------------------------
---------------------------------------------------
--------------------------------------------------------
-------------------------------------------------
-------------------------------------------------
4-5. Calibration Using Front Panel
-----------------------------------------------------
--------------------------------------------------------------
---------------------------------------------------
---------------------------------------------------------
---------------------------------------------

6-2. Commands 69
Output Setting Commands
Measurement Commands
Calibration Commands
Factory Commands
System Commands
6-3. Apply Command
71
6-4. Output V/I Setting & Oprating Commands 71
6-5. Measure Commands 76
6-6. Calibration Commands 77
77
80
7. Error Messages 83
7-1. Operating Error 83
7-2. Hardware Error
83
83
85
7-5. Non-volatile Memory Check Error 85
7-6. Interface Commands Error 86
8. Specifications
87
9. Cautions 88
--------------------------------------------------------
-------------------------------------------------------------
- 5 -
--------------------------------------------------------
-------------------------------------------------------
--------------------------------------------
--------------------------------------------
6-7. Factory Commands
--------------------------------------------
6-8. System Commands
--------------------------------------------
--------------------------------------------------------
--------------------------------------------------------
--------------------------------------------------------
7-3. Remote Calibration Error
---------------------------
7-4. Calibration Error
---------------------------
-----------------
--------------------------------------

1. General Information
1-1. Features
General Features
▌Easy settings by using encoders.
▌Output Voltage/Current Breaking and Restoration of Function (Output ON/OFF)
▌Front Panel Key Lock Function
▌Alarms for Various Events
▌Excellent Precision and High Resolution
▌Built-in Remote Sensing for Load Voltage (V-Sensing)
▌Over Voltage Protection (O.V.P.) / Over Current Protection (O.C.P.) / Over Temperature Protection (O.T.P.) Trip /
Fan RPM Trip / Power Module Trip / Voltage-Current Trip / V-Sensing Error / AC Input Trip / Pfc Ca
▌Under Voltage Limit (U.V.L.)/Over Voltage Limit (O.V.L.), Under Current Limit (U.C.L.)/Over Current Limit (O.C.L.)
▌Excellent Load Regulation and Line Regulation
▌Storing and Recalling up to 10 Operating Settings (Voltage, Current, OVP, OCP)
▌Save and Confirm up to 10 Error Messages
▌Highly Efficient Output of 80%~90%
Remote Interface
▌Supports Various Interfaces such as RS232C, RS485, and TCP/IP
▌Compatible with SCPI (Standard Commands for Programmable Instruments)
▌High-Speed Setting & Measurement
▌Many Built-In Commands
▌Easy Interface Settings by Using the Front Control Panel's I/O config
▌Technical Realization of Products Insulation & Floating Logic
▌Built-In Error Checking Function for SCPI Programming Grammar
Calibration
▌Software Calibration by manual with PC (no need to open cover of instrument for calibration)
▌Easy calibration by using independent or PC interface
Factory Functions
▌Initialization Function of 10 User Memories
▌Save and Recall Last State of the Instrument Before Turning Off
▌“Auto Key Lock & Auto Cursor Move” Function to Prevent Operator Mistakes
▌OVP & OCP Disable Settings Available
▌Fast or Precise Value Reading by Using “Adc” (Analog to Digital Conversion)
▌Calibration Recall Function
▌Calibration Back-up Function
Self-Testing
▌Front Panel Test ▌ADC H/W Error Test
▌Remote Interface Test ▌Unregulated State Test
▌Memory Data Verification Test ▌ADC/DAC Calibration Verification Test
- 6 -
MX Series Single Output products are high-performance, high-efficiency programmable DC power
supply with 5KW~15KW capacity. It supports RS-232C and RS-485 interfaces based on SCPI (Standard
Commands for Programmable Instruments) or Modbus protocols. Refer to the Modbus Manual when
using the Modbus protocol.
Level Settings

1-2. Accessories and Options
Accessories
▌1 User's Manual
▌Demo Software (Windows Application Manual Included) Available for Download at the Homepage
http://www.odacore.com
Options
▌RS232C Cable 1M, 2M, 4M
▌RS485 Cable 2/4/8-Channel 1M, 2M, 4M, 10M
▌TCP/IP
▌Analog Input 0~10V or 0~5V
▌Analog Output 0~10V or 0~5V
▌AC Input Cable (special order type)
▌Output Cable (special order type)
- 7 -

1-3. Inspecting the Unit
Mechanical Checklist
▌Check the key, encoder switch, and power switch for damages.
▌Check the panel surfaces for dents or scratches.
▌Check the rear output terminals for damages.
▌Check the unit's body for dents or scratches.
▌Check the LCD for cracks and scratches.
Electrical Checklist
▌Check for an alarm sound after connecting power to the unit.
An alarm sounding at this step is probably indication of an error during self-testing.
You can read the error code by pressing the error key.
For more details regarding errors, refer to “7.Error Messages.”
For the self-testing, refer to 『1-6. Check after Power On』
▌The LCD displays the company logo and model name during the initial self-testing phase.
▌If the "**OUTPUT OFF**” message is displayed without any problems, refer to the specifications
while checking the unit.
Service Center: 82-32-623-5454
Homepage: www.odacore.com
1-4. Operating Conditions
This instrument is designed to be used under the following environmental conditions:
▌Environmental Temperature: 0 ∼ 50℃
▌Relative Humidity: ≤80%
▌Operating Altitude: ≤2,000m
▌Zero vibrations
▌Away from electromagnetic fields
- 8 -
Note
After opening the delivered power supply, please check for issues described below. If any
problems occur, you can request A/S from a nearby service center or the head office. You
must send the unit in its original package box for smooth service. You can also contact ODA
Technologies regarding questions or get technical advice by referring to the Q&A in the
company homepage or calling.

1-5. Checking Before Connecting Power
Checking the AC Input Cable
Checking the Input Power
▌This product is designed for 3Phase 342Vac ~ 440Vac / 50-60Hz.
▌To protect the unit from severe damage caused by overloading,
it has built-in fast fuses. If the unit does not turn on even after turning on power switch,
you can request A/S from a nearby service center or the head office.
▌The AC input cable provided in the package is a 4-Wire (R,S,T,G) cable.
For custom cables, use cable appropriate for power supply's capacity.
Likewise, connect power line's earth and the unit’s GND before use.
- 9 -

1-6. Checking After Connecting Power
Procedure Checklist
▌The logo of the manufacturer, “ODA Technologies,” is displayed.
▌The model name, “MX-Series,” is displayed.
▌The frontal ERR, LMT, RMT, and LOCK lamps are all turned on and off, starting from the left.
Does not apply for CV and CC annunciators.
▌During the display, the unit is initialized by receiving various data
from the internal non-volatile memory.
▌The unit starts self-testing as well. The criteria for self-testing are shown below.
Connection status with the front panel
Remote Interface Test Remote interface board for PC connection
Memory Data Verification Test
Unit profile and settings data
ADC H/W Error Test
ADC control condition status
Unregulated State Test Output voltage floating status
ADC/DAC Calibration Verification Test ADC and DAC calibration data status
If an error occurs, the alarm rings, and the error code is saved to the volatile memory.
You can read the error code by pressing the error key.
For more details regarding errors, refer to “7.Error Messages”
Default Setting Values
(If the Last State Mode is Disabled)
▌OVP: OVP is set for the maximum value,
▌Remote Interface: Set to maintain the previous settings
OVP is set to ON
▌OCP: OCP is set for the maximum value,
▌State after self-testing: "**OUTPUT OFF**"
OCP is set to ON
▌UVL: 0V
▌Cursor location: Default voltage select
▌OVL: Maximum value
Voltage: 1V
▌UCL: 0A Current: 100mA if current is below 5A
▌OCL: Maximum value In case of under 50A: 1A
▌Output Voltage: 0V In case of under 100A: 10A
▌Output Current: Maximum value ▌KEY LOCK: OFF
The default remote interface is RS232C with baud-rate setting of 9,600bps.
When the unit’s power switch is turned on, the unit starts operating with the initial settings and
self-testing. In addition, the unit maintains the remote interface settings while setting the
output voltage for 0V and the output current for the maximum value (This is the initial factory
settings when the last state is disabled). The OVP & OCP are set to the maximum output value
of the unit’s capacity, and monitoring begins (initial factory settings).
Note1
Note2
Front Panel Test
The last state is disabled at the time of shipping from the factory. To reset various settings
such as voltage/current to the state before you turn off the unit, you can change the settings
in Factory Mode.
- 10 -

1-7. Installation
Cooling
▌This unit can operate without performance loss within the temperature range of 0℃ ~ 50℃,
<Figure 1-4 Bottom view>
Bench Operation
▌There must be enough space for airflow in the front and rear of this unit.
The bottom has no air vent, so you can operate the unit without taking this into consideration.
so this must be taken into consideration when installing the unit.
If the temperature is between 50℃ ~ 55℃, decrease the output current to
0~70%.
When installing the unit on a rack, take care about the airflow. Using a rack
bracket will not impede the airflow.
- 11 -

2. Front/Rear Panel Composition & Function
112
213
314
415
516
617
718
8
9
10
11
Ventilation Slit
16char-Type LCD Display
Error Lamp
Limit Display Lamp
Key Lock Lamp
Memory Saving State Reset or Factory Key
Output Voltage/Current ON/OFF Key
IO/Local Settings and Error Display Key
Protection Settings and Front-panel Lock Key
Voltage/Current Settings Value Display Key
Save Current State or Calibration Key
Curr Cursor or Menu Change Key
CV Mode Lamp
Remote Interface Lamp
CC Mode Lamp
Voltage Settings Encoder
Current Settings Encoder
Voltage Cursor or Menu Change Key
- 12 -

1. Ventilation Slit
The air from the front and sides of the unit are taken in and exhausted from the rear.
2. 16char-Type LCD Display
Voltage/Current value, settings, and various menus are displayed here.
3. CV Mode Lamp
Turned on when the unit is currently in CV (Constant Voltage) Mode.
4. CC Mode Lamp
Turned on when the unit is currently in CC (Constant Current) Mode.
5. Limit Display Lamp
LED is lit when the voltage/current is being set.
LED is turned off if the current voltage/current output is displayed.
6. Remote Interface Lamp
LED is turned on when the remote interface is active.
In this case, the front panel cannot be used.
7. Key Lock Lamp
The front panel is locked and cannot be used if this lamp is on.
8. Error Lamp
LED is lit when various errors occur and turned off when all errors have been confirmed.
9. Voltage Settings Encoder
Used for adjusting the voltage limit settings or values in the menu.
10. Current Settings Encoder
Used for adjusting the current limit settings or values in the menu.
11. Voltage Cursor or Menu Change Key
Cursor key exclusive for voltage. The cursor moves left for each press of the button,
and it is used to move the menu.
12. Current Cursor or Menu Change Key
Cursor key exclusive for current. The cursor moves right for each press of the button,
and it is used to move the menu.
13. Output Voltage/Current ON/OFF
Used for disabling the output voltage/current.
- 13 -

14. Voltage/Current Settings Value Display Key
Used for checking the voltage/current settings. May be different from the actual output value.
Pressing the key turns on the LMT Lamp and displays the set voltage/current value.
Pressing the key once more displays the actual output voltage/current value.
If the previous state was Output OFF, the "**OUTPUT OFF**" message is displayed.
15. IO/Local Settings and Remote Key
Default remote interface setting key available to choose between RS232C and RS485.
Acts as the local mode changing key in remote interface control mode.
Acts as an error display confirming key when errors occur.
Set to act automatically as IO/Local key after checking all errors.
16. Protection Settings and Front-panel Lock Key
Can set various protection functions such as OVP/OCP/UVL/OVL/UCL/OCL.
Pressing the key for 1 second turns on the LOCK Lamp
and locks the front panel. Pressing the key once more disables the lock.
17. Save Current State or Calibration Key
Saves the current voltage, current, protection, and output ON/OFF state.
Turning on power of the unit while holding this key enables switching to calibration mode,
which lets you calibrate the voltage/current.
18. Memory Saving State Reset or Factory Key
- 14 -
You can apply the saved voltage, current, protection, and output ON/OFF settings.
Turning on power of the unit while holding this key enables switching to factory mode.
This initializes the memory, Last State, Auto Cursor Move, Auto Key Lock, OVP Disable, OCP
Disable, ADC Sampling, and Calibration, Various menus such as calibration backup or
initializing calibration factory default values are available.

2-1. Front-Panel Setting of Voltage and Current
You can set the voltage and current limit values using the following method:
1. After connecting power to power supply, check if “**OUTPUT OFF**” is displayed on the LCD.
2. Press the Limit Display Key to switch to Limit Mode.
3. The left cursor key increases the voltage settings value,
and the right cursor key decreases the current settings value.
4. The left encoder changes the voltage settings,
and the right encoder changes the current settings.
5. Rotate the voltage or current encoder clockwise to increase the limit value.
To decrease the limit value, rotate the encoders counter-clockwise.
6. Check if the set values have changed on the LCD display.
7. Press the Output On/Off Key to begin the output of your set voltage and current.
If an error occurs during the『Self-test』, you can check the error by pressing the Error Key.
To check the error codes, refer to “7.Error Messages”
If you are using the remote interface, the front panel's key and encoder switch do not work.
After stopping the remote interface, press the front IO/Local Key to switch to Local mode.
Note1
- 15 -
Note3

2-2. Rear Panel Composition
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
19
23
24
25
AC 「T」 Phase Input
「+」 Positive Output
Voltage Sensing Terminal Block
「-」 Negative Sensing
「+」 Negative Sensing
Signal I/O Terminal Socket (Option)
AC Input Terminal Block
AC 「R」 Phase Input
RS232C/RS485 In Connection Port
RS485 Out Connection Port
Inputs R Phase
Inputs S Phase
Positive Output Port
Positive Sensing Port
RS232C, RS485 Connection IN/OUT Socket
AC Ground Input
Built-In RS232C, RS485 Connection
RS485 Parallel Connection Out Port
RS485 Terminating Resistor Connection Switch
TCP/IP Connection
RS485 Termination Switch
Analog Output Voltage Terminal
Block
Gnd
Option Port’s Gnd
20
Optional Port
3Phase 342Vac~440Vac Power Input Terminal
Analog Input Current Control
Terminal Block
Terminal Block for Controlling the Current in
Proportion to Input of 0~5V or 0~10V
21
Inputs T Phase
Control Port for Operating 2 or More MX-Series Units
Option Port’s Gnd
Parallel Control Terminal Block
Gnd
TCP/IP Connection Port (Option)
Negative Sensing Port
Output Voltage Sensing Terminal Block
Inputs Distributor’s Ground (Earth)
18
Analog Input Voltage Control
Terminal Block
Terminal Block for Controlling the Voltage in
Proportion to Input of 0~5V or 0~10V
「-」 Negative Output
Negative Output Port
AC 「S」 Phase Input
Connection Ports
- 16 -
Outputs 0~5v or 0~10v Voltage in
Proportion to the Output Voltage
22
Analog Output Current Terminal
Block
Outputs 0~5v or 0~10v Voltage in
Proportion to the Output Current
External Output On/Off Port
Controls power Supply Output’s On/Off Through the 0 to
5v Method or Contact Method.
26
Ventilation Slit
Ventilation Slit for Exhausting Air Inlet from the Front

Details for Each Component
1. Positive, Negative Output Bus Bar
Bus Bar for Output Voltage and Current
2. Voltage Sensing Terminal Block
Voltage sensing terminal block. Rewards up to +5% of power supply’s maximum output voltage value.
A warning message is displayed on the LCD if the reward value exceeds 5%.
If the value exceeds 10%, power supply’s output is disabled.
3. RS232C/RS485 Connection Port
The IN connection port has a built-in RS232C,RS485 connection,
and the OUT port is for parallel RS485 connection.
4. RS485 Termination Switch
On/Off switch for using terminating resistors when using RS485 connection.
Turns on the 120 Ohm resistor for the RS485 data connection line when turned on.
5. AC Input Terminal Block
Terminal block for connecting the AC input. The 3Phase + Ground input is the default setting.
Input voltage: 3Phase 342Vac ~ 440Vac 60Hz
6. Signal I/O Terminal Socket
Refer to the MX-Series Option Manual.
7. Parallel Control Terminal Block
Terminal block for parallel current in case of using over 30kW.
2-3. Output Check
- 17 -
Table of contents
Other ODA Power Supply manuals