Omntec Proteus Series Owner's manual

SYSTEM PROGRAMMING
MANUAL
PART NO. OEL8000III-B, OEL8000III-K, & OEL8000III-X
SOFTWARE RELEASE 9.0 / 9.1
1. Open the camera app
2. Focus the camera on
the QR code by gently
tapping the code
3. Follow the instructions
on the screen to view
PDF file
PROTEUS
®
Series
TANK GAUGING SYSTEM
Revision 1.1
Document No. DOC00007 rev1.1
OMNTEC Mfg., Inc. has been certified
by DQS Inc. to ISO 9001:2015
OMNTEC Mfg., Inc. | 2420 Pond Road | Ronkonkoma | NY 11779 | (631) 981-2001 | Email: [email protected]m | www.omntec.com

OMNTEC Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DOC00007 rev1.1.docx 2 of 37 Rev Date: 12-14-2021
Programming Manual
OEL8000III Series
Table of Contents
Section # Page #
1. Navigating to Setup ............................................................................................................................................3
2. System Units .......................................................................................................................................................5
3. Printer Settings (PROTEUS K & X only) ...............................................................................................................6
4. Shift Time Settings ..............................................................................................................................................7
5. Misc. Settings......................................................................................................................................................8
6. Tank Parameters...............................................................................................................................................10
7. Tank Alarm Settings ..........................................................................................................................................12
8. Tank Table (Strapping)......................................................................................................................................13
9. Tank Drop and Other ........................................................................................................................................14
10. Tank Colors & Orientation ................................................................................................................................16
11. Copy Tank Parameters......................................................................................................................................17
12. BX-Sensor Control.............................................................................................................................................18
13. BX-Sensor Parameters ......................................................................................................................................19
14. Comm Ports ......................................................................................................................................................20
15. Modbus.............................................................................................................................................................21
16. Network Properties (PROTEUS K & X only).......................................................................................................22
17. DataCheck Settings ...........................................................................................................................................23
18. Interface Boards & Relays (PROTEUS K & X only) .............................................................................................23
19. Clear Logs..........................................................................................................................................................27
20. VLD – Leak System Settings ..............................................................................................................................28
21. VLD – Leak Tank Settings ..................................................................................................................................29
22. CITLD – Leak System Settings ...........................................................................................................................30
23. Email Account (PROTEUS K & X only) ...............................................................................................................31
24. Email Setup (PROTEUS K & X only) ...................................................................................................................32
25. Diagnostics........................................................................................................................................................33

OMNTEC Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DOC00007 rev1.1.docx 3 of 37 Rev Date: 12-14-2021
Programming Manual
OEL8000III Series
1. Navigating to Setup
Home Screen: The SETUP MENU is
located under UTILITIES. (See Figure
1.1)
Utilities Screen: To enter setup press
SETUP MENU.(See Figure 1.2)
Enter Password: Enter the
manufacturer default password
“000000” when prompted by the unit
to proceed to the SETUP MENU. (See
Figure 1.3)
To change the password: Go to Section 5,
Miscellaneous Settings.
Figure 1.1
Figure 1.2
Figure 1.3

OMNTEC Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DOC00007 rev1.1.docx 4 of 37 Rev Date: 12-14-2021
Programming Manual
OEL8000III Series
Setup Menu (Page 1):
Used to navigate to
corresponding system
setup options. (See
Figure 1.4)
Setup Menu (Page 2):
Used to navigate to
additional system setup
options. (See Figure 1.5)
a) Backup System Parameters: Backs up programming to
SD Card.
b) Restore System Parameters: Restores programming
from SD Card to PROTEUS ATG.
c) Print System Parameters: Prints entire system
programming. Each prompt will have a confirmation
message for “YES” or “NO.” (See Figure 1.5)
*SD Card features and printing for PROTEUS® K & X only*
Figure 1.4
Figure 1.5

OMNTEC Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DOC00007 rev1.1.docx 5 of 37 Rev Date: 12-14-2021
Programming Manual
OEL8000III Series
2. System Units
Site Units of Measurement: The
default unit settings are displayed using
the imperial system, press the unit you
would like to change for the list of
options. You may also change the date
view between MM/DD/YYYY and YYYY-
MM-DD. (See Figure 2.1)
Set Units of Measurement: Select units
desired for volume, level, and
temperature. (See Figure 2.2)
Figure 2.1
Figure 2.2

OMNTEC Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DOC00007 rev1.1.docx 6 of 37 Rev Date: 12-14-2021
Programming Manual
OEL8000III Series
3. Printer Settings (PROTEUS® K & X only)
Print Line Headers: Information
printed on the system status report
header.
Printer Settings: Selects on-board
printer or network printer. (See Figure
3.1)
a) Print Line Headers: The headers are used to program site specific information that
will print on the header of the system status report. Examples of the information to
be entered here would be site name, site address, site phone number, and
manager’s name.
b) Printer Settings: Selecting internal printer will use the PROTEUS® printer; selecting
TCP/IP printer will use printer linked to the same network as the PROTEUS® ATG.
Put the printer’s IP address and port number in the fields provided.
Figure 3.1

OMNTEC Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DOC00007 rev1.1.docx 7 of 37 Rev Date: 12-14-2021
Programming Manual
OEL8000III Series
4. Shift Time Settings
Shift Time Settings: Setup for
generating daily shift reports.(See
Figure 4.1)
a) Number of Shifts: Number of shift reports to be generated daily.
b) Auto Print: Will enable or disable an automatic printout at each shift end time.
c) Shift End Times: End times for the number of shifts that were selected. If multiple
shifts are selected, the end time of the last shift will be the open time of the next
shift.
Figure 4.1

OMNTEC Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DOC00007 rev1.1.docx 8 of 37 Rev Date: 12-14-2021
Programming Manual
OEL8000III Series
5. Misc. Settings
Miscellaneous Settings: Settings for
remote horns and alarm, as well as
auto print options for other settings.
SETUP MENU password can be
changed here as well. (See Figure 5.1)
a) Remote Horn Timeout: Amount of time the horn will sound before automatically
silencing.
b) Remote Horn Timeout Enable: Used to enable or disable the horn timeout.
c) Remote Alarm ACK Timeout: Amount of time before re-sounding the horn after it is
silenced (Remote horn settings for PROTEUS® K & X only).
d) Ullage %: The percent used to calculate ullage on printouts.
e) Setup Password: To change the password press the box and enter new password.
When finished press the save button.
f) Alarm Auto Printout: Used to enable or disable an automatic printout of Alarm
report.
g) Drop Auto Printout:Used to enable or disable the automatic printout of Drop report.
h) Shift Auto Printout:Used to enable or disable the automatic printout of Shift report.
i) VLD Auto-print:Used to enable or disable the automatic printout of VLD report.
j) Interstitial Auto Print:Used to enable or disable the automatic printout of an
interstitial sensor report (Printing for PROTEUS® K & X only).
Figure 5.1

OMNTEC Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DOC00007 rev1.1.docx 9 of 37 Rev Date: 12-14-2021
Programming Manual
OEL8000III Series
Miscellaneous Settings (page 2):
Additional settings to adjust
Homepage and page change to
delivery in progress. (See Figure 5.2)
a) Delivery Page Change: Automatically wakes up the display to show a tank with
delivery in progress.
b) Backlight Timeout: Can be changed to dim the display between 1-255 minutes. Can
also be set to zero which leaves the display always ON (Inventory and Homepage
only).
c) Home Screen: Choose which page you would like to set as the Home Screen.
Choose from System Status, 4 Tank Inventory, Single Tank Inventory, Single Tank
Zoomed Inventory, or CLD (Containment Leak Detection) Mode. NOTE: you must
have a PROTEUS CLD system in order to operate the CLD Mode function.
d) Home Screen Tank #: If a single tank inventory page is chosen, this will select which
tank is shown.
e) Door Ajar Horn: New to Version 9, used for PROTEUS® ATG’s in an enclosure. The
system will chirp via the display horn if the enclosure door is left open and this
feature is on. Options are OFF, MCU-INPUT-2, 4IO-INPUT 1, 4IO-INPUT 2, 4IO-INPUT
3, 4IO-INPUT 4, (if the system has an XB-4IO board). The input is where a magnetic
switch (or equivalent) is connected to within the ATG unit.
f) Information: Will show and explain what each parameter does within miscellaneous
settings.
Figure 5.2

OMNTEC Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DOC00007 rev1.1.docx 10 of 37 Rev Date: 12-14-2021
Programming Manual
OEL8000III Series
6. Tank Parameters
Setup-Tank Parameters: Various
parameters that are needed to obtain
proper and accurate functionality. (See
Figure 6.1)
a) Tank Number: Selects a tank for setup.
b) Product Type: Product type label (up to 17 characters).
c) Product Null: Amount subtracted from gauging probe product level measurement to
match actual product level measurement (Enter product height from stick reading).
d) Water Null: Amount subtracted from gauging probe water level measurement to match
actual water level measurement (Enter water height from stick reading).
e) Enable/Disable: Enable or disable the corresponding tank.
f) Tank Capacity: Total volume of tank (obtained from tank chart).
g) Tank Diameter: Height of tank (highest point on tank chart).
h) Probe Length: Overall probe length (last 3 digits from CAT # on the head of the probe).
i) Wire Speed: Factory defined wire speed (obtained from probe label).
j) Volume Correction:Brings you to the Volume Correction page where you can choose
from COEFFICIENT THERMAL EXPANSION, API GRAVITY, RELATIVE DENSITY or DENSITY.
(See next page for additional Volume Correction details.)
k) Probe Type: Shows how many temperature thermistors are in the probe. (Obtained
from CAT# on the head of the probe). **If using a “redhead” probe, enter 4.**
l) Volume Offset: Amount added to volume reading for further calibration.
Enter corresponding values on each box then press the “NEXT PAGE” icon to continue
programming alarm parameters on the same tank.
Figure 6.1

OMNTEC Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DOC00007 rev1.1.docx 11 of 37 Rev Date: 12-14-2021
Programming Manual
OEL8000III Series
Volume Correction (cont. from 6j): After
selecting volume correction you can
select which correction method you will
use (See Figure 6.2). Select the
Correction Method button and set either
the Coefficient Thermal Expansion, API
Gravity, Relative Density, or Density
option fields (middle column). Use the
data format shown (right column) to
input to the Coeff., Gravity or Density
field (top right column). Thermal
coefficient of expansion x 10-5 (obtained
from thermal coefficient table (ex.
Gasoline = 70, Diesel = 45, etc.).
You may also remove the water volume
from the temperature compensated
measurement by pressing the check box
(will show as net volume) in the bottom
left column.
Figure 6.2

OMNTEC Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DOC00007 rev1.1.docx 12 of 37 Rev Date: 12-14-2021
Programming Manual
OEL8000III Series
7. Tank Alarm Settings
Tank Alarms and Set Points:
Parameters used to control how the
alarms will function. (See Figure 7.1)
a) Tank Number: Selects a tank for setup.
b) High Product:Percentage of volume that will trigger a high-level alarm (max 95%).
c) Overfill:Percentage of volume that will trigger an overfill alarm, set for the same
percentage as High Product. Triggers during delivery in progress (101 disabled).
d) High Warning:Percentage of volume that will trigger a high warning level.
e) Low Product:Percentage of volume that will trigger a low-level alarm (minimum of 1
percent; cannot be set to zero).
f) Delivery Needed:Percentage of volume that will trigger a delivery needed alarm (0
disabled).
g) High Water:The water level that will trigger a high-water alarm.
h) Sudden Loss:Rate of increase/decrease needed during a VLD test to trigger a sudden
loss alarm.
i) Probe Temp High: Temperature needed to activate probe high temp alarm.
j) Probe Temp Low: Temperature needed to activate probe low temp alarm.
Enter corresponding values on each box then press the “NEXT PAGE” icon to continue
programming the strapping chart for the same tank.
Figure 7.1

OMNTEC Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DOC00007 rev1.1.docx 13 of 37 Rev Date: 12-14-2021
Programming Manual
OEL8000III Series
8. Tank Table (Strapping)
Tank Chart Points: Used to
create the chart for each
tank. (See Figure 8.1)
a) Tank Number: Selects a tank for setup.
b) Chart Increment: Used to calculate how many chart points are used for the chart.
Divide the tank diameter by the chart increment to get the number of chart points.
Enter the correct volume for each level given in the tank chart. It is recommended to
input at least 20 chart increment points for accuracy, based on that specific tank’s
manufacturer’s tank chart. Linear tanks can use 2 increment points.
Press the “NEXT PAGE” icon to continue programming parameters for the same tank.
Figure 8.1

OMNTEC Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DOC00007 rev1.1.docx 14 of 37 Rev Date: 12-14-2021
Programming Manual
OEL8000III Series
9. Tank Drop and Other
Setup-Tank Parameters: Information
needed to provide more accurate
inventory and delivery data.(See
Figure 9.1)
a) Tank Number:Selects a tank for setup.
b) Drop Threshold:The volume amount needed to initiate a delivery in progress.
c) Drop Dwell Time:Time delayed after a drop is completed before generating the drop
report.
d) Product Code:User number that identifies the product.
e) Temperature Thermistors Offset: Used to offset temperatures for gauging probe.
(See Figure 9.2)
f) Zero Product Null: Resets the product null to factory default of 1.
g) Zero Water Null: Resets the water null to factory default of 1.57.
h) Increment Factor: Requires password. Used to change probe sensitivity, only change
with OMNTEC permission.
Figure 9.1
Figure 9.2

OMNTEC Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DOC00007 rev1.1.docx 15 of 37 Rev Date: 12-14-2021
Programming Manual
OEL8000III Series
i) Tank Tilt: Number obtained by the tank tilt formula to further calibrate probe levels.
P= The center of fill riser opening to the center of probe riser opening.
M= The distance of the center of probe riser opening to the center of the tank.
D= The difference in gross liquid level between fill opening and riser opening (fill – probe).
Note: Not required if MTG probe is located in the center of the tank or if the tank is level. (See Figure 9.2)
Figure 9.3

OMNTEC Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DOC00007 rev1.1.docx 16 of 37 Rev Date: 12-14-2021
Programming Manual
OEL8000III Series
10.Tank Colors & Orientation
Setup Tank View: Used to
control display settings for
each tank. (See Figure 10.1)
a) Select Product Color: Choose a color to distinguish the contents of each tank.
b) Select Tank Profile: Choose your tank orientation profile (Horizontal or Vertical), or
Oil Water Separator.
IMPORTANT: The PROTEUS® is now programmable for oil/water separator (OWS)
applications. When choosing Oil Water Separator, the tank alarm points will change
to HIGH-HIGH OIL, HIGH OIL, HIGH LIQUID, LOW LIQUID, and LOW WATER alarms. If
you have a PROTEUS® OWS system, please refer to our PROTEUS® Oil/Water
Separator Programming & Installation supplement for additional programming and
installation details (document DI00014 DI00015 DI00018 DI00020 DI00026‐7).
Figure 10.1

OMNTEC Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DOC00007 rev1.1.docx 17 of 37 Rev Date: 12-14-2021
Programming Manual
OEL8000III Series
11. Copy Tank Parameters
“Copy Tank”: Used to copy
the full set of tank
parameters from one tank to
another tank. You must still
however program unique
parameters for each tank
such as product type and
probe wire speed (See Figure
11.1).
Figure 11.1

OMNTEC Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DOC00007 rev1.1.docx 18 of 37 Rev Date: 12-14-2021
Programming Manual
OEL8000III Series
12.BX-Sensor Control
Sensor Control:This page is used to
add or delete sensors. When replacing
a sensor, it is recommended to delete
the old sensor first so when you add
the new sensor it will take the sensor
assignment place of the old sensor.
This will be helpful to keep relay events
from being reprogrammed. (See Figure
12.1)
Adding a Sensor:
1. Turn off the unit and connect the new sensor.
2. Turn on the unit.
3. Go into SENSOR CONTROL in the SETUP MENU and select the FIND SENSORS button (See
Figure 12.2) for the system to install the new sensor. It may be necessary to repeat this
step for systems with multiple sensors. When the system confirms the new sensor, exit
SETUP and allow the system to reboot and save new changes. NOTE: as of Version 9,
the system will not auto-find newly installed sensors upon boot-up.
4. Go into BX-SENSOR PARAMETERS in the SETUP MENU to set the sensor’s labels.
Deleting a Sensor:
1. Turn off the unit and disconnect the sensor.
2. Turn on the unit and go to SETUP.
3. Go into SENSOR CONTROL and choose which sensor to delete.
4. Exit SETUP; system will reboot and save new changes.
Figure 12.1
Figure 12.2

OMNTEC Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DOC00007 rev1.1.docx 19 of 37 Rev Date: 12-14-2021
Programming Manual
OEL8000III Series
13.BX-Sensor Parameters
Sensor Parameters:Parameters used
to define the sensor type, location, and
labeling. (See Figure 13.1)
a) Sensor Number: Sensor number assigned by system, selects a sensor for setup.
b) Sensor Type: Sensor Type assigned by system based upon serial number.
c) Location: User selectable to describe where the sensor is located.
d) Location #: If more than one sensor is present in the same location and tank # then
you may have a location number to differentiate between both sensors.
e) Enable/Disable: Shows if the selected sensor is enabled or disabled.
f) Serial Number: Serial number that is programmed on each sensor.
g) Tank #: The tank number assigned to this sensor for labeling purposes.
h) Print Status on Shift Report: Enables/Disables sensor status for shift report.
Sensor Parameters: BX-TC-1
temperature sensor, designed to
monitor temperatures ranging from
-58°F to 302°F (-50°C to 150°C) with an
accuracy of ±2°F. (See Figure 13.2)
a) Temp – High: Temperature above this value will create a High Temperature alarm.
b) Temp – Low: Temperature below this value will create a Low Temperature alarm.
c) Temp – Offset: Temperature offset if needed.
Note: Temp High, Low, and Offset are for BX‐TC‐1 only.
Figure 13.1
Figure 13.2

OMNTEC Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DOC00007 rev1.1.docx 20 of 37 Rev Date: 12-14-2021
Programming Manual
OEL8000III Series
14.Comm Ports
Comm Port Settings: Used to program
settings for on-board RS-232 or RS-485
port. (See Figure 14.1)
a) Comm Port: Selects between RS-232 and RS-485 port settings (RS-485 for PROTEUS K
& X only). Click on the arrow down icon (˅) to toggle between RS-232 and RS-485.
b) Baud Rate: Selections available are 1200, 2400, 4800, 9600, 19200, 38400, or 57600
baud.
c) Data Bits: Selections available are 8 or 7.
d) Parity: Selections available are none, odd, and even.
e) Stop Bits: Selections available 1 or 2.
f) Comm Type:
•For RS-232 Comm Type there is REMOTE (OMNTEC PC, Mini-Me, or industry
standard protocol) and MODBUS.
•For RS-485 Comm Type (click on the COMM PORT arrow down ˅), there is
REMOTE, MODBUS, RD-625, or RD7CTS (Mini-Me).
g) Remote Security Code: Enabled/Disabled for Ethernet ports to allow data protection.
Must enter security code before industry standard command but after “control a”
(example â000000i20100). **Not currently used via RS-232.**
h) Setup Modbus:Navigates to Modbus Settings Page as shown in the next section.
i) Save:Must be pressed for any changes to take effect.
Figure 14.1