Omron H3CR User manual

Chipsmall Limited consists of a professional team with an average of over 10 year of expertise in the distribution
of electronic components. Based in Hongkong, we have already established firm and mutual-benefit business
relationships with customers from,Europe,America and south Asia,supplying obsolete and hard-to-find components
to meet their specific needs.
With the principle of “Quality Parts,Customers Priority,Honest Operation,and Considerate Service”,our business
mainly focus on the distribution of electronic components. Line cards we deal with include
Microchip,ALPS,ROHM,Xilinx,Pulse,ON,Everlight and Freescale. Main products comprise
IC,Modules,Potentiometer,IC Socket,Relay,Connector.Our parts cover such applications as commercial,industrial,
and automotives areas.
We are looking forward to setting up business relationship with you and hope to provide you with the best service
and solution. Let us make a better world for our industry!
Contact us
Tel: +86-755-8981 8866 Fax: +86-755-8427 6832
Email & Skype: [email protected]om Web: www.chipsmall.com
Address: A1208, Overseas Decoration Building, #122 Zhenhua RD., Futian, Shenzhen, China

1
Solid-state Timer
H3CR
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions
or comments. Refer to Warranty and Application Considerations (page 52), and Safety Precautions (page 22, 44, 51).
DIN 48 ✕48-mm Multifunctional Timer Series
• Conforms to EN61812-1 and IEC60664-1 4 kV/2 for Low
Voltage, and EMC Directives.
• Approved by UL and CSA.
• Lloyds/NK approvals.
• Six-language instruction manual provided.
■Broad Line-up of H3CR Series
Note: H3CR-AS, H3CR-A8S: Transistor output models
Contents
Solid-state Timer
H3CR-A .......................................................................................................................................... 2
H3CR-F........................................................................................................................................... 26
H3CR-G .......................................................................................................................................... 34
H3CR-H .......................................................................................................................................... 42
Common to ALL Timers
Operation ........................................................................................................................................ 52
Accessories .................................................................................................................................... 54
Safety Precautions.......................................................................................................................... 58
H3CR
Multifunctional Timer Twin Timer Star-delta Timer Power OFF-delay Timer
H3CR-GH3CR-F
11-pin model
8-pin model
11-pin model
8-pin model
8-pin model
8-pin model
11-pin model
H3CR-A
H3CR-A
H3CR-AS
H3CR-AP
H3CR-A8
H3CR-A8S
H3CR-A8E
8-pin with
instantaneous
contact output
model
H3CR-F
H3CR-FN
H3CR-F8
H3CR-F8N
H3CR-G8L
H3CR-G8EL
H3CR-HRL
H3CR-H8L
H3CR-H8RL
H3CR-H

2
Solid-state Multi-functional Timers
H3CR-A
Multiple Operating Modes and Multiple Time
Ranges. DIN 48 x 48-mm Multifunctional
Timer.
• A wide AC/DC power supply range greatly reduces the number
of timer models kept in stock.
• A wide range of applications with multiple operating modes,
eight modes for 11-pin models and five modes for 8-pin models.
• Ecological design with reduced current consumption.
• Easy sequence checking with instantaneous outputs for a zero
set value.
• Length of 75 mm or less when panel-mounted with a P3G-08
Socket (H3CR-A8E, 100 to 240 VAC, 100 to 125 VDC)
• PNP input models available.
• Standards: UL, CSA, NK, LR, CCC, EN 61812-1, and CE
Marking.
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Model Number Structure
■Model Number Legend
Note: This model number legend includes combinations that are not available. Before ordering, please check the List of Models on page 3 for avail-
ability.
1. Number of Pins
None: 11-pin models
8: 8-pin models
2. Input Type for 11-pin Models
None: No-voltage input (NPN type)
P: Voltage input (PNP type)
3. Output
None: Relay output (DPDT)
S: Transistor output (NPN/PNP universal use)
E: Relay output (SPDT) with instantaneous relay output (SPDT)
4. Suffix
301: Double time scale (range) models (0.1 s to 600 h)
5. Supply Voltage
100-240AC/100-125DC: 100 to 240 VAC/100 to 125 VDC
24-48AC/12-48DC: 24 to 48 VAC/12 to 48 VDC
24-48AC/DC: 24 to 48 VAC/VDC (Only for H3CR-A8E)
H3CR-A@ @ @ - @ @
123 45

H3CR-A
3
Ordering Information
■List of Models
11-pin Models
8-pin Models
Output Supply voltage Input type Time range Operating mode
(See note 2)
Model
(See note 1.)
Contact 100 to 240 VAC (50/60 Hz)/
100 to 125 VDC
No-voltage input 0.05 s to 300 h Eight multi-modes: A, B,
B2, C, D, E, G, J
H3CR-A
24 to 48 VAC (50/60 Hz)/
12 to 48 VDC
100 to 240 VAC (50/60 Hz)/
100 to 125 VDC
Voltage input Eight multi-modes: A, B,
B2, C, D, E, G, J
H3CR-AP
24 to 48 VAC (50/60 Hz)/
12 to 48 VDC
100 to 240 VAC (50/60 Hz)/
100 to 125 VDC
No-voltage input 0.1 s to 600 h H3CR-A-301
24 to 48 VAC (50/60 Hz)/
12 to 48 VDC
Transistor
(Photocoupler)
24 to 48 VAC (50/60 Hz)/
12 to 48 VDC
0.05 s to 300 h H3CR-AS
Output Supply voltage Input type Time range Operating mode
(See note 2)
Model
(See note 1.)
Contact 100 to 240 VAC (50/60 Hz)/
100 to 125 VDC
No-input available 0.05 s to 300 h Five multi-modes: A, B,
B2, E, J
(Power supply start)
H3CR-A8
24 to 48 VAC (50/60 Hz)/
12 to 48 VDC
100 to 240 VAC (50/60 Hz)/
100 to 125 VDC
0.1 s to 600 h H3CR-A8-301
24 to 48 VAC (50/60 Hz)/
12 to 48 VDC
Transistor
(Photocoupler)
24 to 48 VAC (50/60 Hz)/
12 to 48 VDC
0.05 s to 300 h H3CR-A8S
Time-limit contact and
instantaneous contact
100 to 240 VAC (50/60 Hz)/
100 to 125 VDC
H3CR-A8E
24 to 48 VAC/VDC (50/60 Hz)
Supply voltage
Note: 1. Specify both the model number and supply voltage when ordering.
Example: H3CR-A 100-240AC/100-125DC
2. The operating modes are as follows
A: ON-delay D: Signal OFF-delay
B: Flicker OFF start E: Interval
B2: Flicker ON start G: Signal ON/OFF-delay
C: Signal ON/OFF-delay J: One-shot

H3CR-A
4
■Accessories (Order Separately)
Adapter, Protective Cover, Hold down Clip, Setting Ring and Panel Cover
*1
The Y92A-48B Protective Cover and the Y92P-48G
@
Panel Cover can not be used at the same time with the Y92F-73/-74 Flush Mounting Adapter.
*2 The Y92A-48B Protective Cover is made from hard plastic. Remove the Protective Cover to change to set value. The Y92F-73/-74 Flush
Mounting Adapter and the Y92P-48G@Panel Cover cannot be used at the same time with Y92A-48B Protective Cover.
*3 The Y92S-27/-28 Setting Ring cannot be used alone. It must be used together with the Y92P-48G@Panel Cover.
*4
The Y92A-48B Protective Cover and the Y92F-73/-74 Flush Mounting Adapter cannot be used at the same time with the Y92P-48G
@
Panel Cover.
Sockets
Note: 1. The P2CF-@@-E has a finger-protection structure. Round crimp terminals cannot be used. Use forked crimp terminals.
2. The P3GA-11 and P3G-08 Socket can be used together with the Y92A-48G Terminal Cover to implement finger protection.
3. For details, refer to your OMRON website.
Terminal Cover
Note: For details, refer to your OMRON website.
Name/specifications Models
Flush Mounting Adapter Y92F-30
Y92F-73 *1
Y92F-74 *1
Protective Cover Y92A-48B *2
Hold-down Clip (Sold in sets of
two)
For PF085A Socket Y92H-8
For PL08 or PL11 Sockets Y92H-7
Setting Ring A Y92S-27 *3
Setting Ring B and C Y92S-28 *3
Panel Cover Light gray (5Y7/1) Y92P-48GL *4
Black (N1.5) Y92P-48GB *4
Timer Round Sockets
Pin Connection Terminal Models
11-pin Front Connecting DIN track mounting P2CF-11
DIN track mounting
(Finger-safe type)
P2CF-11-E
Back Connecting Screw terminal P3GA-11
Solder terminal PL11
Wrapping terminal PL11-Q
PCB terminal PLE11-0
8-pin Front Connecting DIN track mounting P2CF-08
DIN track mounting
(Finger-safe type)
P2CF-08-E
DIN track mounting PF085A
Back Connecting Screw terminal P3G-08
Solder terminal PL08
Wrapping terminal PL08-Q
PCB terminal PLE08-0
Application Model Remarks
For back connecting socket Y92A-48G For P3G-08 and P3GA-11

H3CR-A
5
Specifications
■General
*The internal circuits are optically isolated from the output. This enables universal application as NPN or PNP transistor.
For details, refer to your OMRON website.
■Time Ranges
Note: When the time setting knob is turned below “0” until the point where the time setting knob stops, the output will operate instantaneously at
all time range settings.
For details, refer to your OMRON website.
Standard (0.05-s to 300-h) Models
Double (0.1-s to 600-h) Models
Item H3CR-A/-AS/-A-301 H3CR-AP H3CR-A8/-A8S/-A8-301 H3CR-A8E
Operating mode A: ON-delay
B: Flicker OFF start
B2: Flicker ON start
C: Signal ON/OFF-delay
D: Signal OFF-delay
E: Interval
G: Signal ON/OFF-delay
J: One-shot
A: ON-delay (power supply start)
B: Flicker OFF start (power supply start)
B2: Flicker ON start (power supply start)
E: Interval (power supply start)
J: One-shot (power supply start)
Pin type 11-pin 8-pin
Input type No-voltage input Voltage input ---
Time-limit output type H3CR-A/-A8/-AP/-A-301/-A8-301: Relay output (DPDT)
H3CR-AS/-A8S: Transistor output (NPN/PNP universal)*
Relay output (SPDT)
Instantaneous output type --- Relay output (SPDT)
Mounting method DIN track mounting, surface mounting, and flush mounting
Approved standards UL508, CSA C22.2 No.14, NK, Lloyds, CCC
Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2.
Output category according to EN60947-5-1 for Timers with Contact Outputs.
Output category according to EN60947-5-2 for Timers with Transistor Outputs.
Time unit s (sec) 10 s (10 sec) min (min) 10 min (10 min) h (hrs) 10 h (10 hrs)
Full scale
setting
1.2 0.05 to 1.2 1.2 to 12 0.12 to 1.2 1.2 to 12 0.12 to 1.2 1.2 to 12
3 0.3 to 3 3 to 30 0.3 to 3 3 to 30 0.3 to 3 3 to 30
12 1.2 to 12 12 to 120 1.2 to 12 12 to 120 1.2 to 12 12 to 120
30 3 to 30 30 to 300 3 to 30 30 to 300 3 to 30 30 to 300
Time unit s (sec) 10 s (10 sec) min (min) 10 min (10 min) h (hrs) 10 h (10 hrs)
Full scale
setting
2.4 0.1 to 2.4 2.4 to 24 0.24 to 2.4 2.4 to 24 0.24 to 2.4 2.4 to 24
6 0.6 to 6 6 to 60 0.6 to 6 6 to 60 0.6 to 6 6 to 60
24 2.4 to 24 24 to 240 2.4 to 24 24 to 240 2.4 to 24 24 to 240
60 6 to 60 60 to 600 6 to 60 60 to 600 6 to 60 60 to 600

H3CR-A
6
■Ratings
Note: 1. DC ripple rate: 20% max. (A single-phase, full-wave-rectification power supply can be used).
2. Do not use an inverter output as the power supply. Refer to your OMRON website for details.
3. Models with 24-to-48-VAC or 12-to-48-VDC power supply have inrush current. Caution is thus required when turning ON and OFF power
to the Timer with a non-contact output from a device such as a sensor. (Models with an inrush current of approximately 50 mA and a 24-
VDC power supply are available (the H3CR-A-302 and H3CR-A8-302).)
For details, consult your OMRON sales representative.
4. The values are for when the terminals 2 and 7 and terminals 10 and 6 are short-circuited, and include the consumption current of the
input circuit.
5. Refer to your OMRON website when using the Timer together with a 2-wire AC proximity sensor.
6. For details, see Input Connections: No-voltage Input Signal Levels on page 11, and Input Connections: Voltage Input Signal Levels on
page 12.
Rated supply voltage (See notes 1, 2, and 5.)
100 to 240 VAC (50/60 Hz)/100 to 125 VDC, 24 to 48 VAC (50/60 Hz)/12 to 48 VDC (24 to 48 VAC/VDC for H3CR-A8E)
(See note 3.)
Operating voltage range 85% to 110% of rated supply voltage (90% to 110% at 12 VDC)
Power reset Minimum power-opening time: 0.1 s
Input (See note 6.) No-voltage Input
ON impedance: 1 kΩmax.
ON residual voltage: 1 V max.
OFF impedance: 100 kΩmin.
Voltage Input
Max. permissible capacitance between inputs lines (terminals 6 and 7): 1,200 pF
Load connectable in parallel with inputs (terminals 6 and 7).
•100 to 240 VAC/100 to 125 VDC
High (logic) level: 85 to 264 VAC/85 to 137.5 VDC
Low (logic) level: 0 to 10 VAC/0 to 10 VDC
•24 to 48 VAC/12 to 48 VDC
High (logic) level: 20.4 to 52.8 VAC/10.8 to 52.8 VDC
Low (logic) level: 0 to 2.4 VAC/0 to 1.2 VDC
Power consumption H3CR-A/-A8
•100 to 240 VAC/100 to 125 VDC
(When at 240 VAC, 60 Hz)
Relay ON: approx. 2.0 VA (1.6 W) Relay OFF: approx. 1.3 VA (1.1 W)
•24 to 48 VAC/12 to 48 VDC
(When at 24 VDC)
Relay ON: approx. 0.8 W Relay OFF: approx. 0.2 W
H3CR-AP (See note 3)
•100 to 240 VAC/100 to 125 VDC
(When at 240 VAC, 60 Hz)
Relay ON: approx. 2.5 VA (2.2 W) (See note 4.) Relay OFF: approx. 1.8 VA (1.7 W) (See note 4.)
•24 to 48 VAC/12 to 48 VDC
(When at 24 VDC)
Relay ON: approx. 0.9 W (See note 4.) Relay OFF: approx. 0.3 W (See note 4.)
H3CR-A8E
•100 to 240 VAC/100 to 125 VDC
(When at 240 VAC, 60 Hz)
Relay ON/OFF: approx. 2 VA (0.9 W)
•24 to 48 VAC/VDC
(When at 24 VDC)
Relay ON/OFF: approx. 0.9 W
H3CR-AS/-A8S
•24 to 48 VAC/12 to 48 VDC
(When at 24 VDC)
Output ON: 0.3 W Output OFF: 0.2 W
Control outputs •Models with Contact Outputs
H3CR-A/-A8/-AP
5A at 250 VAC/30 VDC, 0.15A at 125 VDC, resistive load (cosφ= 1)
Minimum applied load: 10mA at 5 VDC (failure level: P reference value)
Contact materials: Ag-alloy
H3CR-A8E
5A at 250 VAC/30 VDC, 0.15A at 125 VDC, resistive load (cosφ= 1)
Minimum applied load: 10mA at 5 VDC (failure level: P reference value)
Contact materials: AgSnIn
•Transistor output: Open collector(NPN/PNP)
H3CR-AS/-A8S
100 mA max at 30 VDC max., residual voltage: 2 VDC max.

H3CR-A
7
■Characteristics
Note: 1. The value is ±5% FS +100 ms to −0 ms max. when the C, D, or G mode signal of the H3CR-AP is OFF.
2. The influence of voltage of the H3CR-A8E (24 to 48 VAC/12 to 48 VDC) is ±2.0% FS max. with a single-phase power supply with full-
wave rectification.
3. Refer to the Life-test Curve (Reference).
4. Contact output only.
■Life-test Curve (Reference)
Accuracy of operating
time
±0.2% FS max. (±0.2%±10 ms max. in a range of 1.2 s or 3 s)
Setting error ±5% FS ±50 ms (See note 1)
Reset time Min. power-opening time: 0.1 s max.
Min. pulse width: 0.05 s (H3CR-A/-AS)
Reset voltage 10% max. of rated supply voltage
Influence of voltage
(See note 2)
±0.2% FS max. (±0.2%±10 ms max. in a range of 1.2 s or 3 s)
Influence of temperature ±1% FS max. (±1%±10 ms max. in a range of 1.2 s or 3 s)
Insulation resistance 100 MΩmin. (at 500 VDC)
Dielectric strength 2,000 VAC (1,000 VAC for H3CR-A@S), 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-
current-carrying metal parts)
2,000 VAC (1,000 VAC for H3CR-A@S), 50/60 Hz for 1 min (between control output terminals and operating circuit)
2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities)
1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)
2,000 VAC, 50/60 Hz for 1 min (between input and control output terminals and operation circuit) for H3CR-AP
Impulse withstand
voltage
5 kV (between power terminals) for 100 to 240 VAC/100 to 125 VDC, 1 kV for 24 to 48 VAC/12 to 48 VDC
5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 240 VAC/100 to
125 VDC, 1.5 kV for 24 to 48 VAC/12 to 48 VDC and 24 to 48 VAC/VDC
Noise immunity ±1.5 kV (between power terminals) and ±600 V (between no-voltage input terminals), square-wave noise by noise
simulator (pulse width: 100 ns/1 µs, 1-ns rise)
Static immunity Malfunction: 8 kV
Destruction: 15 kV
Vibration resistance Destruction: 10 to 55 Hz with 0.75-mm single amplitude each in 3 directions for 2 hours each
Malfunction: 10 to 55 Hz with 0.5-mm single amplitude each in 3 directions for 10 minutes each
Shock resistance Destruction: 1,000 m/s23 times each in 6 directions
Malfunction: 100 m/s23 times each in 6 directions
Ambient temperature Operating: −10°C to 55°C (with no icing)
Storage: −25°C to 65°C (with no icing)
Ambient humidity Operating: 35% to 85%
Life expectancy
(See note 4)
Mechanical: 20,000,000 operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) (See note 3)
EMC (EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
(EMS) EN61812-1
Immunity ESD: IEC61000-4-2
Immunity RF-interference: IEC61000-4-3
Immunity Burst: IEC61000-4-4
Immunity Surge: IEC61000-4-5
Immunity Conducted Disturbance: IEC61000-4-6
Immunity Voltage Dip/Interruption: IEC61000-4-11
Case color Light gray (Munsell 5Y7/1)
Degree of protection IP40 (panel surface)
Weight Approx. 90 g
10,000
5,000
1,000
500
100
01 23 45
Load current (A)
30 VDC L/R = 7 ms
250 VAC (cosφ= 0.4)
Switching operations (x 103)
250 VAC/30
VDC (cosφ= 1)
Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ= 1) and
a maximum current of 0.1A can be switched at 125V DC and L/R = 7ms.
In both cases, a life of 100,000 operations can be expected.
The minimum applicable load is 10 mA at 5 VDC (failure level: P).

H3CR-A
8
Connections
■Block Diagrams
H3CR-A/-AS/-A-301
AC (DC) input
Output circuit
Reset input, start input, and gate input Input circuit
Power supply
circuit
Oscillation
circuit
Counting
circuit
Zero setting
detection
circuit
Time range/
unit selectors
Operating
mode selector
Indicator
circuit
Power-ON
indicator
Output-ON
indicator
H3CR-AP
AC (DC) input
Output circuit
Start Input circuit
Power supply
circuit
Zero setting
detection
circuit
Oscillation
circuit
Counting
circuit
Time range/
unit selectors
Operating
mode selector
Indicator
circuit
Power-ON
indicator
Output-ON
indicator

H3CR-A
9
■I/O Functions
Note: H3CR-AP incorporates start input only.
Models H3CR-A8/-A8E/-A8S/-A8-301 do not have an input function.
Inputs (for -A/
-AS models)
Start Starts time-measurement.
Reset Interrupts time-measurement and resets time-measurement value. Timing operation is stopped and the
control output turns OFF (it is reset).
Gate The timing operation is interrupted while the gate input is active.
Outputs Control output Outputs are turned ON according to designated output mode when preset value is reached.
H3CR-A8/-A8S/A8-301
AC (DC) input
Output circuit
Power supply
circuit
Zero setting
detection
circuit
Oscillation
circuit
Counting
circuit
Time range/
unit selectors
Operating
mode selector
Indicator
circuit
Power-ON
indicator
Output-ON
indicator
H3CR-A8E
AC (DC) input
Output circuit
Power supply
circuit
Zero setting
detection
circuit
Oscillation
circuit
Counting
circuit
Time range/
unit selectors
Operating
mode selector
Indicator
circuit
Power-ON
indicator
Output-ON
indicator
Instantaneous
output circuit

H3CR-A
10
■Terminal Arrangement
Note: 1. The delayed contact of conventional Timers was indicated as
The contact symbol of the H3CR-A is indicated as because its operating mode is eight multi-modes (five multi-modes for the H3CR-A8).
2. Do not use an empty terminal on the H3CR-AP/-AS/-A8S as a relay terminal or otherwise.
11-pin Models
Note: Terminals 1, 3, 4, and 8 are empty. Terminals 2, 5, 6, 7, and 10
are the same as for the H3CR-A.
Note: 1. Terminal 5 is empty.
2. Separate power supplies can be used for the Timer and in-
puts.
8-pin Models
Note: Terminals 1, 3, 4, and 5 are empty. Terminals 2 and 7 are the
same as for the H3CR-A8.
H3CR-A/-A-301 (Contact Output)
Reset input
Start input
Gate input
Power supply
H3CR-AS (Transistor Output)
Power supply
Reset input
Start input
Gate input
Power supply
Start input
H3CR-AP (Contact Output)
H3CR-A8/-A8-301 (Contact Output)
Power supply
H3CR-A8S (Transistor Output)
Power supply
H3CR-A8E (Contact Output)
Power supply

H3CR-A
11
■Input Connections
H3CR-A/-AS/-A-301
5
6
7
2
+
−
5
6
7
2
+
−
5
6
7
2
The inputs of the H3CR-A/-AS/-A-301 are no-voltage (short-circuit or open) inputs.
No-voltage Input Signal Levels
No-contact Input Contact Input No-contact Input
No-voltage Inputs
Sensor Timer
Gate
Start
Reset
Operates with transistor ON
Timer
Operates with relay ON
Gate
Start
Reset
Input (0 V)
Sensor
Timer
Operates with transistor ON
Gate
Start
Reset
Input (0 V)
(Connection to NPN open
collector output sensor.)
12 to 24 VDC
(sensor power supply)
DC power
supply
Input (0 V)
No-contact
input
1. Short-circuit level
Transistor ON
Residual voltage: 1 V max.
Impedance when ON: 1 kΩmax.
2. Open level
Transistor OFF
Impedance when OFF: 100 kΩmin.
Contact
input
Use contacts which can
adequately switch 0.1 mA at 5 V
(Connection to a voltage
output sensor.)
12 to 24 VDC
(sensor power supply)
DC power
supply

H3CR-A
12
H3CR-AP
6
10
7
6
10
7
22
6
10
7
2
+
−
+
−
The start input of the H3CR-AP is voltage input. (Voltage imposition or open)
Voltage Input Signal Levels
No-contact Input No-contact Input Contact Input
Sensor
Timer
Start
Operates with PNP transistor ON Operates with NPN transistor ON
Timer
Sensor
Timer
Operates with relay ON
Voltage Inputs
Input 0V
Start
Input 0V
Start
Input 0V
AC power supply
DC power supply
(Connection to PNP open
collector output sensor)
12 to 24 VDC
(sensor power supply)
DC power
supply
Power
supply (+)
Power
supply
(−)
(Connection to NPN open
collector output sensor)
12 to 24 VDC
(sensor power supply)
DC power
supply
Power
supply (+)
Power
supply (−)
Note: The input circuit is isolated from the
power supply circuit. Thus, an NPN
transistor can be connected.
Power
supply (+)
Power
supply (−)
Note: Refer to the signal levels in the
following table and be aware of the
minimum applicable load of the relay.
No-contact
input
1. Transistor ON
Residual voltage: 1 V max.
The voltage between terminals 6 and 7 must be 10.8 VDC min.
2. Transistor OFF
Leakage current: 0.01 mA max.
The voltage between terminals 6 and 7 must be 1.2 VDC max.
Contact
input
Use contacts that can adequately switch 0.1 mA at each
operating voltage.
The voltage between terminals 6 and 7 with contacts ON or
OFF must satisfy the specified value.
Contacts ON
100-to-240-VAC and 100-to-125-VDC models: 85 to 264 VAC
or 85 to 137.5 VDC
24-to-48-VAC and 12-to-48-VDC models: 20.4 to 52.8 VAC or
10.8 to 52.8 VDC
Contacts OFF
100-to-240-VAC and 100-to-125-VDC models: 0 to 10 VAC or
0 to 10 VDC
24-to-48-VAC and 12-to-48-VDC models: 0 to 2.4 VAC or 0 to
1.2 VDC
Note: Before making connections, refer to Safety Precautions (H3CR-
@
).

H3CR-A
13
Operation
■Timing Chart (Refer to page 20 for application examples.)
H3CR-A/-AS/-AP*/-A-301
Note: 1. Allow at least 0.1 s for the Timer reset time if the power supply is reset due to an interruption in the power supply.
2. The minimum input pulse width (for start, reset) is 0.05 s.
3. The letter "t" in the timing charts indicates the set time, and "t-a" means that the period is less than the set time. (t - a < 1)
4. H3CR-AP model incorporates start input only. As such, the power supply is reset.
5. Model H3CR-AS only has operation equivalent to time-limit contact: NO.
6. When the setting dial is turned all the way past 0 for instantaneous output, "t" (set time) in the above time chart is 0-sec operation.
7. During timer operation, the flash frequency changes when 90% of the set time has been reached.
Operating
mode
Timing chart
A: ON-delay
B:
Flicker OFF
start
B2:
Flicker ON
start
C:
Signal ON/
OFF-delay
t t
t
Power
Start
Output relay (NC)
Power indicator
Power
Output
Basic operation
Output relay (NO)
(Output indicator)
Start
(See note)
Note: Start input is invalid while the
Timer is in operation.
(See note 4) Reset
(See Note 7)
t t t t
Basic operation
Power
Output
Power
Power indicator
Start
Output relay (NC)
Output relay (NO)
(Output indicator)
Start
(See note)
Note: Start input is invalid while
the Timer is in operation.
(See note 4) Reset
(See Note 7)
ttt t
Basic operation
Power
Output
Power
Start
Power indicator
Output relay (NC)
Output relay (NO)
(Output indicator)
Start
(See note)
Note: Start input is invalid while the
Timer is in operation.
(See note 4) Reset
(See Note 7)
tttt
Basic operation
Power
Output
Power
Start
(See note 4) Reset
Output relay (NC)
Power indicator
Output relay (NO)
(Output indicator)
Start
(See note)
Note: Start input is valid and
retriggerable while the Timer
is in operation.
(See Note 7)

H3CR-A
14
Gate Signal Input (This timing chart indicates the gate input in operating mode A (ON-delay operation).)
Operating
mode
Timing chart
D:
Signal OFF-
delay
E:
Interval
G:
Signal ON/
OFF-delay
J:
One-shot
output
t
Basic operation
Power
Output
Output relay (NC)
Power indicator
Power
Start
Output relay (NO)
(Output indicator)
Start
(See note)
Note: Start input is valid and
retriggerable while the
Timer is in operation.
(See note 5) Reset
(See Note 8)
t
Power
Start
Output relay (NC)
Power indicator
Power
Output
Output relay (NO)
(Output indicator)
Basic operation
Start
(See note)
Note: Start input is valid and
retriggerable while the
Timer is in operation.
(Previous start input
will be cancelled.)
(See note 5) Reset
(See Note 8)
tttt
Basic operation
Power
Output
Power
Start
Output relay (NC)
Power indicator
Output relay (NO)
(Output indicator)
Start
(See note)
Note: Start input is valid and
retriggerable while the Timer
is in operation.
(See note 5) Reset
(See Note 8)
t
Basic operation
Output
Power
Power
Start
(See note 5) Reset
Output relay (NC)
Power indicator
Output relay (NO)
(Output indicator)
1±0.6 s
(Fixed)
1±0.6 s
(Fixed)
Start
(See note) 1±0.6 s
(Fixed)
Note: Start input is valid and
retriggerable while the
Timer is in operation.
(Previous start input will
be cancelled.)
(See Note 8)
t
1
t
2
Power
Start
Gate
Reset
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Output
relay
Note: 1. Allow at least 0.1 s for the Timer reset time if the power
supply is reset due to an interruption in the power supply.
2. The minimum input pulse width (for start, reset) is 0.05 s.
3. The letter "t" in the timing charts indicates the set time, and
"t-a" means that the period is less than the set time.
(t - a < 1)
4.
In J Mode, there will be only one output even if the start input is
longer than the set time.
5. H3CR-AP model incorporates start input only.
As such, the
power supply is reset.
6. Model H3CR-AS only has operation equivalent to time-limit
contact: NO.
7. When the setting dial is turned all the way past 0 for
intantaneous output, "t" (set time) in the above time chart is
0-sec operation.
8. During timer operation, the flash frequency changes when
90% of the set time has been reached.
Note: The set time is the sum of t1 and t2.
Start and reset are also both enabled when the gate signal is ON.

H3CR-A
15
H3CR-A8/-A8S/-A8-301
Note: 1. Allow a timer reset time (Rt) of 0.1 s or longer.
2. The letter "t" in the timing charts indicates the set time, and "t-a" means that the period is less than the set time. (t - a < 1)
3. Model H3CR-A8S only has operation equivalent to time-limit contact: NO.
4. When the setting dial is turned all the way past 0 for intantaneous output, "t" (set time) in the above time chart is 0-sec operation.
5. You can use J Mode to use the power supply as the start input.
6. During timer operation, the flash frequency changes when 90% of the set time has been reached.
Operating
mode
Timing chart
A:
ON-delay
B:
Flicker OFF
start
B2:
Flicker ON
start
v
E:
Interval
J:
One-shot
output
t
Power
Output
Basic operation
Power
Output relay (NC)
Power indicator
Output relay (NO)
(Output indicator)
(See note 6)
Power
Output
tttt
Power
Output relay (NC)
Output relay (NO)
(output indicator)
tttttRtt−at−aBasic operation
Power indicator
(See note 6)
t t t t
Power
Power
Output
Basic operation
Output relay (NC)
Output relay (NO)
(output indicator)
Power indicator
(See note 6)
t
Power
Output
Basic operation
Power
Output relay (NC)
Output relay (NO)
(output indicator)
Power indicator
(See note 6)
t
Power
Power
Output
Basic operation
Output relay (NC)
Output relay (NO)
(output indicator)
1±0.6 s
(Fixed)
1±0.6 s
(Fixed)
1±0.6 s
(Fixed)
Power indicator
(See note 6)

H3CR-A
16
H3CR-A8E
Note: Refer to page 15.
Operating
mode
Timing chart
A:
ON-delay
B:
Flicker OFF
start
B2:
Flicker ON
start
E:
Interval
J:
One-shot
output
t
Power
Power indicator
Power
Output
Basic operation
Output relay (NC)
Output relay (NO)
(output indicator)
Instantaneous
output relay (NC)
Instantaneous
output relay (NO)
(See Note 6)
tttt
tttttRtt−at−a
(See Note 6)
Power indicator
Power
Basic operation
Output relay (NC)
Output relay (NO)
(output indicator)
Instantaneous
output relay (NC)
Instantaneous
output relay (NO)
Power
Output
tttt
Power
Power indicator
Power
Output
Basic operation
Output relay (NC)
Output relay (NO)
(output indicator)
Instantaneous
output relay (NC)
Instantaneous
output relay (NO)
(See Note 6)
t
Power
Output
Basic operation
Power
Power indicator
Output relay (NC)
Output relay (NO)
(output indicator)
Instantaneous
output relay (NC)
Instantaneous
output relay (NO)
(See Note 6)
t
Power
Power indicator
Power
Output
Basic operation
(Fixed) (Fixed)
Output relay (NC)
Output relay (NO)
(output indicator)
Instantaneous
output relay (NC)
Instantaneous
output relay (NO) 1±0.6 s
(Fixed)
(See Note 6)

H3CR-A
17
Nomenclature
Operating mode display window
Scale range display windows
Time unit display window
Power indicator (green) (Flashes when Timer
operates; lit when Timer stops operating)
Output indicator (orange)
(Lit when output)
Time range selector (select one
from 1.2, 3, 12, and 30 at full
scale; with the H3CR-A@-301,
select from 2.4, 6, 24, or 60 at
full scale.)
Time setting
knob (set time)
Time unit selector (select one from
sec, 10s, min, 10m, hrs, and 10h)
Operating mode selector
Select a mode from:
A, B, B2, C, D, E, G, and J (H3CR-A, -AP, and -AS)
A, B, B2, E and J (H3CR-A8, -A8S, and -A8E)
Scale range display windows changes as below by
turning
the Time range selector clockwise.*
* On the H3CR-A@-301 type, the time is twice as long.
0 0.2 0.4 0.6 0.8 1.0 1.2
0 0.5 1 1.5 2 2.5 3
024681012
0 5 10 15 20 25 30

H3CR-A
18
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Note: There are no restrictions to the mounting direction.
*These dimensions vary with the kind of DIN track (reference value).
48
48
66.6
52.3
15
6
44.8 ×44.8
0.7
48
66.6
48
15
652.3
0.7
44.8 ×44.8
11 pins
39 dia.
8 pins
39 dia.
H3CR-A
H3CR-AP
H3CR-AS
H3CR-A-301
H3CR-A8
H3CR-A8S
H3CR-A8E
H3CR-A8-301
50 16.5
50
Dimensions with Set Ring
Y92S-27/-28 (Order Separately)
Panel cover
42 dia.
Time Setting
Ring
100.8* 98.5
2.3*
89.9* 87.6
2.3*
80
15 15 75
81.5 81.5
H3CR-A8@
H3CR-A8-301
H3CR-A8E
H3CR-A8S
Y92F-30
P3GA-11 Y92F-30 P3G-08
H3CR-A
H3CR-A-301
H3CR-AS
H3CR-AP
P2CF-11
P2CF-11-E
P2CF-08
P2CF-08-E
H3CR-A
H3CR-A-301
H3CR-AS
H3CR-AP
+
Adapter
(When
Y92A-48G
mounted)
H3CR-A8@
H3CR-A8-301
H3CR-A8E
H3CR-A8S
+
Adapter
(When
Y92A-48G
mounted)
Dimensions with Front Connecting Socket
P2CF-08-@/P2CF-11-@
Dimensions with Back Connecting Socket
P3G-08/P3GA-11

H3CR-A
19
■Accessories (Order Separately)
Protective Cover
Y92A-48B
To use the Protective Cover with a flush mounting, use the Y92F-30
flush mounting adaptor.
This Protective Cover cannot be used together with the Y92F-73/-74
flush mounting adaptor or the panel cover.
Hold-down Clip
Y92H-8
The Y92H-8 Hold-down Clip is attached to the PF085A socket.
Y92H-7
Y92H-7 Hold-down Clip is attached with screws together with the
PL08 socket or the PL11 socket.
Other manuals for H3CR
3
This manual suits for next models
17
Table of contents
Other Omron Timer manuals

Omron
Omron H3CR -A8 User manual

Omron
Omron H3CR-A8E User manual

Omron
Omron H5CX User manual

Omron
Omron H3FA - User manual

Omron
Omron Ateg H3DT Series User manual

Omron
Omron H3CA-A-101 User manual

Omron
Omron H8CA-S Series User manual

Omron
Omron H7AN User manual

Omron
Omron H2F-D User manual

Omron
Omron H5CN User manual
Popular Timer manuals by other brands

WESTEK
WESTEK TM77DHB Instruction manual & warranty

Toa
Toa TT-104 operating instructions

Ideal Stelrad Group
Ideal Stelrad Group Vogue Combi c26 user guide

Draper
Draper WTM1 Original instructions

Marathon
Marathon TI030018 Series user manual

Intermatic
Intermatic Grasslin Talento Smart B10 mini operating manual