Omron H3RN User manual

Solid-state timer H3RN B-97
Timers
Solid-state timer
H3RN
Ultra-slim Timer for G2R Relay Socket
• Pin configuration compatible with G2R Relay and mounts to the
P2R/P2RF Socket.
• Standard multiple time ranges and multiple operating modes.
• Conforms to EN61812-1 and IEC60664-1 4 kV/2 for Low Volt-
age, and EMC Directives.
Model Number Structure
■Model Number Legend
1. Output
1: SPDT
2: DPST-NO
2. Time Range
None: Short-time range (0.1 s to 10 min)
1: Long-time range (0.1 min to 10 hrs)
Ordering Information
■List of Models
■Accessories (Order Separately)
Connecting Socket
H3RN-@@
1 2
Supply voltage Time-limit contact Short-time range model
(0.1 s to 10 min) Long-time range model
(0.1 min to 10 h)
24 VAC;
12, 24 VDC
SPDT H3RN-1 H3RN-11
DPST-NO H3RN-2 H3RN-21
Note: Specify both the model number and supply voltage when ordering.
Example: H3RN-1 24 VAC
Supply voltage
Timer Track mounting/Front connecting socket Back connecting socket
H3RN-1/-11 P2RF-05-E P2R-057P
H3RN-2/-21 P2RF-08-E P2R-087P

B-98 Solid-state timer H3RN
Specifications
■Ratings
Note: When using the H3RN in any place where the ambient temperature is more than 50°C, supply 90% to 110% of the rated voltages (12 VDC:
95% to 110% of the rated voltage).
■Characteristics
Item H3RN-1/H3RN-2 H3RN-11/H3RN-21
Time ranges 0.1 s to 10 min (1 s, 10 s, 1 min, or 10 min max.
selectable)
0.1 min to 10 h (1 min, 10 min, 1 h, or 10 hrs max.
selectable)
Rated supply voltage 24 VAC (50/60 Hz); 12, 24 VDC
Pin type Plug-in
Operating mode ON-delay, interval, flicker OFF-start, or flicker-ON start selectable by DIP switch
Operating voltage range 85% to 110% of rated supply voltage (12 VDC: 90% to 110% of rated supply voltage)
(see note)
Reset voltage 10% max. of rated supply voltage
Power consumption 24 VAC: Relay ON: approx. 0.8 VA (0.6 W) at 24 VAC, 60 Hz
Relay OFF: approx. 0.6 VA (0.4 W) at 24 VAC, 60 Hz
12 VDC: Relay ON: approx. 0.5 W at 12 VDC
Relay OFF: approx. 0.2 W at 12 VDC
24 VDC: Relay ON: approx. 0.6 W at 24 VDC
Relay OFF: approx. 0.3 W at 24 VDC
Control outputs 3 A at 250 VAC, resistive load (cosφ= 1) (G6B-2@14P-FD-US used)
The minimum applicable load is 10 mA at 5 VDC (P reference value).
Item H3RN-1/H3RN-2 H3RN-11/H3RN-21
Accuracy of operating time ±1% FS max. (1 s range: ±1%±10 ms max.)
Setting error ±15%±50 ms FS max.
Reset time Min. power-opening time:12, 24 VDC: 0.1 s max. (including halfway reset)
24 VAC: 0.5 s max. (including halfway reset)
Influence of voltage ±2% FS max.
Influence of temperature ±2% FS max.
Insulation resistance 100 MΩmin. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between operating circuit and control output, or contacts of different
poles)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Vibration resistance Destruction: 10 to 55 Hz, 0.75-mm single amplitude for 1 h each in 3 directions
Malfunction: 10 to 55 Hz, 0.5-mm single amplitude for 10 min each in 3 directions
Shock resistance Destruction: 300 m/s2
Malfunction: 100 m/s2
Ambient temperature Operating: −10°C to 55°C (with no icing)
Storage: −25°C to 65°C (with no icing)
Ambient humidity Operating: 35% to 85%
Life expectancy Mechanical: 10,000,000 operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (3 A at 250 VAC, resistive load at 1,800 operations/h)
Impulse withstand voltage Between power terminals: 1 kV
Noise immunity ±1.5 kV, square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise)
Static immunity Destruction: 8 kV
Malfunction: 4 kV
Degree of protection IP40 (Terminal screw sections are excluded.)
Weight Approx. 18 g

Solid-state timer H3RN B-99
Timers
Connections
■Connection
Pulse Operation
A pulse output for a certain period can be obtained with a random external input signal.
Use the H3RN in interval mode as shown in the following timing charts.
!Caution
Be careful when connecting wires.
EMC (EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
(EMS) EN61812-1
Immunity ESD: EN61000-4-2: 6 kV contact discharge (level 3)
8 kV air discharge (level 3)
Immunity RF-interference from AM Radio Waves: IEC61000-4-3:10 V/m (80 MHz to 1 GHz) (level 3)
Immunity Burst: EN61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Immunity Surge: IEC51000-4-5: 1 kV line to line (level 3)
2 kV line to ground (level 3)
Approved standards UL508, CSA C22.2 No. 14
Conforms to EN61812-1, IEC60664-1 4 kV/2.
Output category according to IEC60947-5-1.
Item H3RN-1/H3RN-2 H3RN-11/H3RN-21
OUT PW
Bottom View
H3RN-1/H3RN-11 H3RN-2/H3RN-21
DIN Indication DIN Indication
OUT PW
Bottom View
Timer
circuit Timer
circuit
H3RN-2/H3RN-21
External input
Power (3-8)
External short circuit (1-4)
External input (1-3)
Timer
circuit
50 ms
min.
Time limit contact
NO (6-5)
Run/Power indicator (PW)
Output indicator (OUT)
Note: t: Set time
Rt: Reset time
Mode Terminals
Pulse operation Power supply between 3 and 8
Short-circuit between 4 and 1
Input signal between 3 and 1
Operating mode; interval and all other
modes Power supply between 1 and 8

B-100 Solid-state timer H3RN
Operation
■Timing Chart
Note: t: Set time
Rt: Reset time
Operating mode Timing chart
H3RN-1/H3RN-11 H3RN-2/H3RN-21
ON-delay
Power
Output
Power (1-5)
Time limit contact
NC (4-2)
Time limit contact
NO (4-3)
Run/Power
indicator (PW)
Output indicator
(OUT)
Power (1-8)
Time limit contact
NO (4-3, 5-6)
Run/Power
indicator (PW)
Output indicator
(OUT)
Interval
Power
Output
Power (1-5)
Time limit contact
NC (4-2)
Time limit contact
NO (4-3)
Run/Power
indicator (PW)
Output indicator
(OUT)
Power (1-8)
Time limit contact
NO (4-3, 5-6)
Run/Power
indicator (PW)
Output indicator
(OUT)
Flicker OFF-start
Power
Output
Power (1-5)
Time limit contact
NC (4-2)
Time limit contact
NO (4-3)
Run/Power
indicator (PW)
Output indicator
(OUT)
Power (1-8)
Time limit contact
NO (4-3, 5-6)
Run/Power
indicator (PW)
Output indicator
(OUT)
Flicker ON-start
Power
Output
Power (1-5)
Time limit contact
NC (4-2)
Time limit contact
NO (4-3)
Run/Power
indicator (PW)
Output indicator
(OUT)
Power (1-8)
Time limit contact
NO (4-3, 5-6)
Run/Power
indicator (PW)
Output indicator
(OUT)

Solid-state timer H3RN B-101
Timers
■DIP Switch Settings
The 1-s range and ON-delay mode for H3RN-1/-2, 1-min range and ON-delay mode for H3RN-11/-21 are factory-set before shipping.
Time Ranges
Note: The left two DIP switch pins are used to select the time ranges.
Operating Modes
Note: The right two DIP switch pins are used to select the operating modes.
Nomenclature
Model Time range Time setting
range Setting Factory-set
H3RN-1,
H3RN-2
1 s 0.1 to 1 s Yes
10 s 1 to 10 s No
1 min 0.1 to 1 min No
10 min 1 to 10 min No
H3RN-11,
H3RN-21
1 min 0.1 to 1 min Yes
10 min 1 to 10 min No
1 h 0.1 to 1 h No
10 h 1 to 10 h No
Operating mode Setting Factory-set
ON-delay Yes
Interval No
Flicker OFF-start No
Flicker ON-start No
Run/Power Indicator (Green)
(Lit: Power ON)
Output Indicator (Orange)
(Lit: Output ON)
Main Dial
Set the desired time according to time
range selectable by DIP switch.

B-102 Solid-state timer H3RN
Dimensions
Note: All units are in millimeters unless otherwise indicated.
■Timers
H3RN-1/H3RN-11 Front Mounting
H3RN-2/H3RN-21 Front Mounting
Mounting Height
P2RF-@-E P2R-@7P
H3RN Series H3RN Series
Use the P2RF-@-E or P2R-@7P to mount the H3RN. When ordering any one of these sockets,
replace "@" with "05" for SPDT or "08" for DPST-NO.
The P2RF-@cannot be used because the hook is a different shape.
P2RF-@-E
Socket
79.5 (see note 1)
(83.5) (see note 2)
80.9 (see note 1)
(84.9) (see note 2)
P2R-@7P
Socket
Note: 1. The value shown indicates the dimension for the
P2RF-05-E with the PFP-@N Mounting Rail.
The value is 71.5 mm when using the PFP-N@2.
2. The value shown in parentheses indicates the di-
mension for the P2RF-08-E with the PFP-@N
Mounting Rail.
The value is 75.5 mm when using the PFP-N@2.

Solid-state timer H3RN B-103
Timers
Precautions
■Correct Use
When using the H3RN in any place where the ambient temperature
is more than 50°C, supply 90% to 110% of the rated voltages (at
12 VDC: 95% to 110%).
Do not leave the H3RN in time-up condition for a long period of time
(for example, more than one month in any place where the ambient
temperature is high), otherwise the internal parts may become dam-
aged. Therefore, the use of the H3RN with a relay as shown in the
following circuit diagram is recommended.
The H3RN must be disconnected from the socket when setting the
DIP switch, otherwise the user may touch a terminal imposed with a
high voltage and get an electric shock.
Do not connect the H3RN as shown in the following circuit diagram
on the right hand side, otherwise the H3RN’s internal contacts differ-
ent from each other in polarity may become short-circuited.
Use the following safety circuit when building a self-holding circuit
with the H3RN and an auxiliary relay, such as a G2R Relay, in combi-
nation.
In the case of the above circuit, the H3RN will be in pulse operation.
Therefore, if the circuit shown on page 99 is used, no auxiliary relay
will be required.
Do not use the SPDT contact in a circuit which may cause short-cir-
cuiting at three points (otherwise, short-circuiting of the power supply
may occur) because the SPDT contact of H3RN-1/-11 is composed
of an SPST-NC contact.
Do not set to the minimum setting in the flicker modes, otherwise the
contact may be damaged.
Do not use the H3RN in places where there is excessive dust, corro-
sive gas, or direct sunlight.
Make sure that there is a space of 3 mm or more between any H3RN
Models next to each other. (When using the P2RF-@-E Socket, a
space of 3 mm or more will be secured.) If a space of 3 mm or more
is not secured, the ambient temperature must be less than 50°C.
The internal parts may become damaged if a supply voltage other
than the rated ones is imposed on the H3RN.
■Precautions for EN61812-1
Conformance
The H3RN as a built-in timer conforms to EN61812-1 provided that
the following conditions are satisfied.
Handling
Do not touch the DIP switch while power is supplied to the H3RN.
Before dismounting the H3RN from the socket, make sure that no
voltage is imposed on any terminal of the H3RN.
Wiring
Basic insulation is ensured between the H3RN’s operating circuit and
control output.
Basic insulation: Overvoltage category III,
pollution degree 2
(with a clearance of 3.0 mm and a creepage
distance of 3.0 mm at 240 VAC)
The clearance from the edge of the P2R-087P Socket to internal,
current-carrying metal parts is 1.3 mm. Position the H3RN to provide
the necessary clearance for the voltage used.
When using the P2RF-@-E or P2R-057P Socket, basic insulation is
ensured in the mounted condition for a voltage of 250 VAC max.
X1T X2
X2/b T/a X1/a X1/a
X:Auxiliary relay such as G2R Relay
Correct Incorrect
G2R Relay
3
4
2
15
Short-circuit current
Power supply
for load

B-104 Solid-state timer H3RN
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. L090-E1-02
Other manuals for H3RN
1
This manual suits for next models
4
Table of contents
Other Omron Timer manuals

Omron
Omron H5AN Series User manual

Omron
Omron H5F - User manual

Omron
Omron H3CR-AS User manual

Omron
Omron H3JA User manual

Omron
Omron Ateg H3DT Series User manual

Omron
Omron H5CR series User manual

Omron
Omron H5CC-AWSD User manual

Omron
Omron H3CR User manual

Omron
Omron H8GN - V1.02 User manual

Omron
Omron H3CR-A8 User manual