Omron POWLI BU50XS User manual

•This manual gives you important information to use the BU50XS/BU70XS/BU100XS safely
and therefore be sure to read it before installation and use.
•Keep this manual handy at the place where you install the BU50XS/BU70XS/BU100XS so that
you can read it whenever necessary.
No part or while of this manual may be reproduced without permission.
BU50XS / BU70XS / BU100XS
Uninterruptible Power Supply (UPS)
Instruction Manual

Introduction
Notes on the use of the Backup Power Supply
●This product is designed and manufactured for use for OA equipment such as personal com-
puters.
Do not use it when very high reliability and safety are required as listed below.
•Medical equipment that may cause death directly
•Applications that may cause injury (applications that directly affect the operation and con-
trol of planes, ships, railroads, elevators, and so on)
• Applications that are always subjected to vibration such as cars and ships
•Applications in which a failure of this product may cause significant damage or effect to the
society and public (important computer systems, main communication equipment, public
transportation systems, and so on)
• Equipment with the same level of importance
●For equipment that greatly affects the safety of people and maintaining public functions, spe-
cial considerations related to operation, maintenance, and management must be taken such
as duplicating the system and emergency power generation facilities.
●Observe the contents of this manual such as the use conditions and environments.
●When you want to use this product for an important system that requires very high reliability,
contact us; ___________________________
●Do not modify/alter this product.
©OMRON Corporation. 2004 All Rights Reserved.
Features of this product
Thank you for purchasing Omron's Uninterruptible Power Supply (UPS).
●The UPS protects computers and other devices from power failures, voltage variations, in-
stantaneous voltage drops/power failures, and surge voltage caused by thunders and so on
(a phenomenon in which extraordinary high voltage occurs instantaneously).
●Under normal conditions, it converts the commercial power to a direct current once, recon-
verts it to a stable 100-VAC sine wave, and outputs it.
When detecting a failure of the commercial power, it switches to battery-supplying to provide
the continuous output of a sine wave. This is called On-line Power Method.
It is suitable especially for use where power supply conditions are bad (for example, voltage
variations are large).
●The output capacity is 500VA/350W for BU50XS, 700VA/490W for BU70XS and 1KVA/700W
for BU100XS.
●It provides Network line surge protection function to protect communication devices such as
modems from surge voltage that comes through the line (a phenomenon in which extraordi-
nary high voltage occurs instantaneously).

1
IMPORTANT SAFETY INSTRUCTION
1. SAVE THESE INSTRUCTIONS.
This manual contains important instruction for Model BU50XS/BU70XS/
BU100XS.
That should be followed during instruction of the UPS and batteries.
2. SYMBOL
This symbol indicates earth ground.
This symbol indicates turining on UPS.
This symbol indicates turining off UPS.
3. INTERNAL BATTERY.
Internal battery voltage is 24Vdc for BU50XS/BU70XS, 36Vdc for BU100XS.
4. TEMPERATURE RATING.
Maximun ambit temperature of UPS 40°C.
5. ENVIRONMENT
The unit is intended for installation in a temperature controlled, indoor area
free of conductive contaminants.

Table of Contents
2
Introduction
IMPORTANT SAFETY INSTRUCTION .............................................................................................................. 1
Safety precautions ............................................................................................................................................. 3
1. Preparation ................................................................................................................................................... 9
1-1 Unpacking the product ........................................................................................................................ 9
1-2 Checking the accessories ................................................................................................................... 9
1-3 Name of each part ............................................................................................................................. 10
1-4 Explanation of symbol used on unit................................................................................................... 11
2. Installation and connection ......................................................................................................................... 12
2-1 Precautions and notes on installation and connection ...................................................................... 12
2-2 Installation ......................................................................................................................................... 14
2-3 Connecting the equipment ................................................................................................................ 15
2-4 Checking the operation ..................................................................................................................... 17
2-5 Charging the battery .......................................................................................................................... 19
2-6 Measuring the backup time ............................................................................................................... 19
3. Operating the UPS ..................................................................................................................................... 20
3-1 Precautions and notes on operation.................................................................................................. 20
3-2 Start and stop procedures ................................................................................................................. 21
3-3 Interpreting a beep and display ......................................................................................................... 22
4. Functions of the UPS ................................................................................................................................. 25
4-1 Suspending a beep ........................................................................................................................... 25
4-2 Testing the UPS (executing the self-diagnostic test) .........................................................................26
4-3 Description of the auto battery test.................................................................................................... 27
5. Measuring the backup time ........................................................................................................................ 28
5-1 Measuring method of the backup time .............................................................................................. 28
5-2 Estimated backup time ...................................................................................................................... 28
6. Maintenance and inspection ....................................................................................................................... 29
6-1 Checking the battery ......................................................................................................................... 29
6-2 Replacing the battery ........................................................................................................................ 29
6-3 Replacing the fan .............................................................................................................................. 34
6-4 Cleaning ............................................................................................................................................ 34
7. Using the Network Line Surge Protection Function .................................................................................... 35
7-1 When connecting to the telephone line ............................................................................................. 35
7-2 When connecting to the ISDN line .................................................................................................... 35
7-3 When connecting to LAN 10Base-T/100 Base-Tx ............................................................................. 35
7-4 Example of connection ...................................................................................................................... 35
8. Using the UPS monitoring software and Contact Signal ............................................................................ 36
8-1 When performing the auto shutdown processing by the UPS monitoring software .......................... 36
8-2 Details on Contact Signal .................................................................................................................. 37
8-3 Expanding the signal card ................................................................................................................. 39
8-4 Precautions and notes on the use of the Contact Signal .................................................................. 39
9. Extending the backup time ......................................................................................................................... 40
9-1 Expanding the battery unit (BU100XS only) ...................................................................................... 40
10. Changing the setting of the functions ......................................................................................................... 41
10-1 Function that can be set/change from the UPS................................................................................. 41
10-2 Functions that can be set/change from the UPS monitoring software .............................................. 42
11.Troubleshooting .......................................................................................................................................... 43
References ....................................................................................................................................................... 44
A. Specifications ......................................................................................................................................... 44
B. Dimensional outline drawing .................................................................................................................. 45
C. Circuit block diagram ............................................................................................................................. 45
D. Related products .................................................................................................................................... 46

3
Safety precautions
:Indicates prohibition (things that you must not do). For example, indicates that disassembly is
prohibited.
:Indicates compulsory (things that you must do). For example, indicates that grounding is
necessary.
Misuse may cause death or serious injury.
Warning
Caution
Safety precautions
●The safety symbols and their meaning used in this manual are as follows.
* Property damage means damage to houses/household effects, livestock, and pets.
Notice that information provided as a caution may cause more significant results under certain conditions.
The information described here is very important and must be observed strictly.
The weight of the product is 13kg (BU50XS/BU70XS)/15.5kg (BU100XS).
Unpack/transport this product considering this weight.
●Dropping may cause injury.
Keep packing materials including plastic bags and films out of the reach
of children.
●They may put their head into it or put it into their mouth, hindering their breathing.
Do not disassemble, repair, or modify the product.
●Doing so may cause an electric shock or a fire.
If liquid leaks from the product, do not touch it.
●Doing so may cause blindness or burns.
●If it touches your eyes or skin, wash it out with lots of clean water and consult your doctor.
Do not use it when very high reliability and safety are required as listed
below. (This product is designed and manufactured for use for OA equip-
ment such as personal computers.)
●Medical equipment or system that may cause death directly
●Applications that directly affect the safety of people (For example, the operation and control
of cars and elevators)
●Applications in which a failure of this product may cause significant damage or effect to the
society and public (For example, important computer systems and main communication equip-
ment.)
●Applications with the same level of importance
Warning
Warning (use of the product)
Caution (installation)
Important information for safety use is described.
Be sure to read it before installation and start of use.
Misuse may cause injury or property damage.

4
Safety precautions
Provide secure grounding.
●Connect the ground terminals of the UPS and the devices to be connected to the ground.
(Refer to "2. Installation and connection" on page 12.)
If a failure or leak occurs, it may cause an electric shock. Touching the UPS and other devices
without grounding at the same time may cause an electric shock.
●When you use the 3P-2P conversion Plug for the AC Input Plug, be sure to perform grounding
before connecting the AC Input Plug into a wall outlet (commercial power). On the other hand,
be sure to disconnect the AC Input Plug from a wall outlet (commercial power) before discon-
necting the grounding wire.
●Without grounding, the Power line surge protection and the Network line surge protection do
not work.
The installation orientation is designated. Do not install the product in
other orientations.
●Refer to "2-2 Installing the product" on page 14.
●Falling may cause injury.
Do not use the product where the maximum temperature exceeds 40°C.
●The battery becomes week rapidly, which may cause a fire.
●Doing so may cause a failure or malfunction of the UPS.
Concerning installation and storage of the products, follow the instructions
listed below.
●Do not install the product in a place where humidity is lower than 20% or higher than 90%.
●Do not use the product in a place where humidity is lower than 25% or higher than 85%.
●Do not install the products at a closed place such as in a cabinet without clearance, at a place
with flammable gas or corrosive gas exist and in the open air.
●Doing so may cause a fire.
Do not obstruct the air inlet and outlet in the side and rear of the product.
●Inside temperature increases, which may cause a failure of the UPS and the deterioration of
the battery.
●Install the product at least 5 cm from the walls.
Do not install the product on an unstable base.
●Dropping or falling may cause injury.
Caution (installation)
Connect the UPS to a wall outlet (commercial power) with a current capacity
larger than the maximum input current of the UPS.
●Otherwise, the power cord may be heated.
●When the equipment of the maximum capacity is connected, the maximum current that flows
is 8A for the BU50XS, 10A for the BU70XS and 14A for the BU100XS.
Be sure to connect the input plug of the UPS to a wall outlet (commercial
power) of 100 VAC (50/60Hz).
●Connecting it to a wall outlet (commercial power) of a different voltage may cause a fire.
●The UPS may fail.
Caution (connection)

5
Safety precautions
Do not connect equipment that exceeds the output capacity of the UPS.
You can use a plug strip and so on to connect extra equipment, but, in this
case, do not connect equipment that exceeds the current capacity of the
plug strip.
●The UPS may detect overload and stop the output.
●The wiring of the plug strip heats up, which may cause a fire.
Caution (connection)
If the input plug is disconnected while the product is operating, never
touch its metal part.
●Doing so may cause an electric shock.
●The leak current of this product itself is less than the value of the safety standard (leak current:
1 mA). However, leak current increases due to connected equipment. Therefore, never touch
the metal part of the input plug.
●When the product is operating, voltage is generated at the metal part of the input plug via
capacitors in the internal circuit regardless of elapsed time.
If the Battery Replacement Lamp goes on or the backup time becomes
shorter than the required time, immediately replace the battery pack or
stop using the UPS and discard the battery pack.
●Continuing the use of it may cause a fire.
●For information on how to inspect the battery, refer to "6. Maintenance and inspection" on
page 29.
If you notice abnormal sound or smell, smoke, or liquid from the inside,
immediately press the Stop Switch of the UPS and disconnect the AC
Input Plug from a wall outlet (commercial power).
●Using the product under these conditions may cause a leak or fire.
●If you notice such a condition, never use the product and contact the shop from which you
purchased this product or our company for inspection and repair.
●Use the product under the conditions in which you can immediately disconnect the AC Input
Plug from a wall outlet (commercial power) in the event of the occurrence of an abnormal
condition.
When maintaining connected equipment, stop the UPS and disconnect
the AC Input Plug from a wall outlet (commercial power).
●Even if you disconnect the AC Input Plug while the UPS is operating, supplying power is
continued from the Power Supply Output Receptacles by the backup function.
●If the scheduled operation is enabled, supplying power is started when the operation start
time is reached with the AC Input Plug connected to a wall outlet (commercial power).
Caution (use)
*The values in the left table are the expected life under
standard use conditions and are not guaranteed values.
Ambient temperature
20°C
30°C
Expected life
4 to 5 years
2 to 2.5 years

6
Safety precautions
Do not short the battery with metal objects.
●Doing so may cause burns or a fire.
●Some electrical energy remains inside the battery even if it is exhausted.
Do not put the battery into fire or do not break it.
●The battery may explode or dilute sulfuric acid may leak.
Do not use a replacement battery other than specified.
●Doing so may cause a fire.
●Product model: For BU50XS, BU70XS: BP70XS
For BU100XS: BP100XS
Do not use a new battery and an old battery at the same time.
●Dilute sulfuric acid may leak.
Do not drop the battery or do not give strong impact on it.
●Dilute sulfuric acid may leak.
Do not replace the battery in a place where there is flammable gas.
●Sparking may occur when connecting the battery, which may cause a fire.
Caution (battery replacement)
Do not put something on the product or do not drop metal objects onto
the product.
●Doing so may cause distortion/damage to the case or a failure of the internal circuit, which
may cause a fire.
Do not use the product in a closed place or do not cover the product.
●Doing so may cause abnormal heating or a fire.
Do not wet or pour water on the product.
●Doing so may cause an electric shock or a fire.
Do not insert metal objects into the Power Supply Output Receptacles of
the UPS.
●Doing so may cause an electric shock.
Do not insert metal objects into the Battery Connection Connector or the
Expansion Connector.
●Doing so may cause an electric shock.
Caution (use)

7
Safety precautions
Notes
Charge the battery (for at least 8 hours) immediately after purchasing the product.
●If you do not use the product for a long time after purchase, the characteristics of the battery may deteriorate
and become unavailable.
●When you connect the AC Input Plug of the UPS to a wall outlet (commercial power), the battery is automati-
cally charged.
If you store the UPS, charge the battery for at least 8 hours before storage.
●Even if you do not use the battery, it discharges spontaneously and goes into over discharge status if it is left
for a log time. The backup time may become shorter or the battery may become unavailable.
●The storable period of the built-in battery of the UPS is 6 months after charging it for at least 8 hours.
●If you want to store the battery longer than 6 months, connect the AC Input Plug of the UPS to a wall outlet for
at least 8 hours before the limit is exceeded.
●Press the Stop Switch of the UPS to stop it during storage.
Do not reverse the connection of Line/Hub Side and Modem/TA/PC Side of the Network
Line Surge Protection.
●If a failure of the protection circuit occurs, the line side (telephone/ISDN line) may be damaged.
Do not short the output lines of the UPS each other and the output lines to the ground.
●The UPS may fail.
Do not connect the AC Input Plug of the UPS to its Power Supply Output Receptacle.
●The UPS may fail.
Before cutting out commercial power by turning off the breaker or disconnecting the
AC Input Plug, stop the UPS.
If you cannot stop the UPS, it is recommended to automatically stop it in the minimum
backup time using the UPS monitoring software.
●When you stop commercial power, the battery mode starts. If you repeat charging and discharging in a way
in which you stop commercial power and discharge the battery completely, the life of the battery decreases
extremely.
The less the amount of charging and discharging is, the less the effect on the lift becomes.
Do not connect a page printer to the UPS.
●The connection capacity may be exceeded repeatedly during operation using commercial power, which
may cause the status in which the input voltage is outputted directly (bypass mode).
●The peak current of the page printer is large and it may be detected that the connection capacity is ex-
ceeded.
Do not perform a withstand voltage test.
●The input circuit of UPS has a built-in surge absorption device. A withstand voltage test may break it.
●When performing an insulation resistance test, use the 250 VDC range.

8
Safety precautions
Explanation
Usual operation
●You may continue the operation of the UPS or stop it each time shutting down the connected
system.
You can choose either of the operation methods for your convenience.
●Connecting the UPS to a wall outlet (commercial power) charges the battery.
End of Battery mode
●If the time of a power failure is long, the voltage supply from the UPS stops. Shut down you computer using
a proper procedure (for example, saving data) while the UPS supplies the voltage.
Reboot
●If the battery discharges completely during a power failure, the UPS stops. After the recovery from a failure
of the power supply (for example, power failure), the UPS automatically restarts and supplies the voltage. If
you do not want to start the connected equipment, turn off its power switch.
●The UPS monitoring software allows you to disable automatic restart.
Scheduled operation using the UPS monitoring software
●When performing scheduled operation in which the UPS is stopped and the commercial power is stopped
using a breaker and so on at the same time, specify a period within 3 months for the start of the next
operation. If you specify a period longer than 3 months, the internal timer is reset and the scheduled opera-
tion does not start.
Notice that this period reduces to approximately half when the battery is dead.
If 3 months are exceeded, you start operation by supplying commercial power and press the Start Switch.
However, if the battery is dead, you may not be able to start operation. In this case, replace the battery
according to "6-2 Replacing the battery" on page 29.
Notes
Recycling and Discarding the Battery
●The UPS uses a lead acid battery. It is recyclable, precious resources. Please recycle it when
you replace it or discard the produce you do not use any more.
Installation and storage places
●Do not install or store the UPS in a place exposed to direct sunlight.
The rise of temperature may cause the battery to deteriorate and become unavailable.
Pb

9
1. Preparation
BU50XS/BU70XS/BU100XS
1. Instruction Manual (Japanese) ...................... 1
(English) .......................... 1
2. Telephone cable (modular cable) ................. 1
3. Warranty card ................................................ 1
4. User registration card .................................... 1
5. 3P-2P conversion plug .................................. 1
6. Guidance label for operation status .............. 1
7. Automatic shut down software set ................. 1
(including CD-ROM and RS232C Cable)
Open the package box and take out the UPS and accessories.
The weight of the product is 13kg (BU50XS, BU70XS) / 15.5kg (BU100XS).
Unpack/transport this product considering this weight.
●Dropping may cause injury.
Do not install the product on an unstable base.
●Dropping or falling may cause injury.
1-2 Checking the accessories
Check whether all the accessories are included and there is no damage to their outside.
If you should notice defects or something wrong, please contact us;
Caution
1. Preparation
1-1 Unpacking the product
Warranty card
Telephone cable
(modular cable)
Instruction Manual
User registration card Guidance label for
operation status

10
1. Preparation
1-3 Name of each part
This section describes the name of each part of the UPS.
For information on the function of each part, refer to "2. Installation and connection" on page 12 and "3. Oper-
ating the UPS" on page 20 that provides the details.
Front view
[ Enlarged view of the operation part ]
Side view
Air inlet
Rear sideFront side
< Operation part >
100%
75%
運転
テスト/
ブザー停止
容量表示
接続容量
オーバー
バッテリ
交換
異常
バイパス運転
電源出力
AC入力
バックアップ
運転
バッテリ
増設
INPUT OUTPUT
停止
50%
25%
!
A. Start Switch
B. Stop Switch
C. AC Input Lamp
D. Bypass mode Lamp
(The input voltage is
outputted directly.)
E. Power Supply Output
Lamp
F. Battery Expansion Lamp
(BU100XS only)
G. Battery mode Lamp
H. Battery Replacement Lamp
I. Connection Capacity
Exceeded Lamp
J. Error Lamp
K. Connection Capacity/
Battery Remain Level
Meter
100%
75%
運転
テスト/
ブザー停止
容量表示
接続容量
オーバー
バッテリ
交換
異常
バイパス運転
電源出力
AC入力
バックアップ
運転
バッテリ
増設
INPUT OUTPUT
停止
50%
25%
!
A
B
C
D
E
F
G
KJIH

11
1. Preparation
Rear view
A. RS232C Contact signal Connector
B. Signal Card Expansion Slot
C. Battery Expansion Connector (BU100XS only)
D. Power Supply Output Receptacle
(Backed up at a power failure)
E. Grounding Terminal
F. Network Surge Protection
G. AC Input Overcurernt Protection
H. AC Input Cable
I. Cooling Fan (air outlet)
1-4 Explanation of symbol used on unit
Symbol Description
Start the UPS.
Stop the UPS.
Suspend a beep.
AC input power supplied to the UPS.
UPS output power enable, supplied by operating on line mode, battery mode or bypass mode.
UPS operating on battery mode.
UPS operating on bypass mode.
Expanding battery unit connecting to the UPS. (For BU100XS only.)
UPS has Error.
Connected Overload. Excess output capacity by connected devices.
Batteries in end of useful life, necessary to replace the batteries.
C
D
RS232C
信号入出力コネクタ
信号カード
増設
冷却ファン
OUTPUT電源出力AC100V50/60Hz
最大10A/700W
接地
回線サージ保護
回線
ハブ側
モデム・TA
パソコン側
バッテリ
増設コネクタ
DC36V/20A
INPUT
AC100V入力
50/60Hz
15A
LINE/HUB MODEM・TA
NetworkCard
AC入力
過電流保護
15A
AB
I
H
G
FE

12
2. Installation and connection
Caution
2. Installation and connection
2-1
Precautions and notes on installation and connection
Precautions and notes on installation and connection are given below. Be sure to read them for correct use.
The weight of the product is 13kg (BU50XS, BU70XS) / 15.5kg (BU100XS).
Unpack/transport this product considering this weight.
●Dropping may cause injury.
Keep packing materials including plastic bags and films out of the reach
of children.
●They may put their head into it or put it into their mouth, hindering their breathing.
Provide secure grounding.
●Connect the ground terminals of the UPS and the devices to be connected to the ground.
(Refer to "2. Installation and connection" on page 12.)
If a failure or leak occurs, it may cause an electric shock.
Touching the UPS and other devices without grounding at the same time may cause an elec-
tric shock.
●When you use the 3P-2P conversion Plug for the AC Input Plug, be sure to perform grounding
before connecting the AC Input Plug into a wall outlet (commercial power). On the other hand,
be sure to disconnect the AC Input Plug from a wall outlet (commercial power) before discon-
necting the grounding wire.
●Without grounding, the Power Line Surge Protection and the Network Line Surge Protection
do not work.
Connect the UPS to a wall outlet (commercial power) with a current capacity
larger than the maximum input current of the UPS.
●Otherwise, the power cord may be heated.
●When the equipment of the maximum capacity is connected, the current that flows is 8A for
the BU50XS, 10A for the BU70XS and 14A for the BU100XS.
Be sure to connect the AC Input Plug of the UPS to a wall outlet (commercial
power) of 100 VAC (50/60Hz).
●Connecting it to a wall outlet (commercial power) of a different voltage may cause a fire.
●The UPS may fail.

13
2. Installation and connection
Notes
Do not short the output lines of the UPS each other and the output lines to the ground.
●The UPS may fail.
Do not connect the AC Input Plug of the UPS to its Power Supply Output Receptacle.
●The UPS may fail.
Do not connect a page printer to the UPS.
●The connection capacity may be exceeded repeatedly during operation using commercial power, which
may cause bypass mode.
●It may be detected that the connection capacity is exceeded.
Caution
Prohibition (things that you must not do)
Do not use the product in a closed place or do not cover the product.
●Doing so may cause abnormal heating or a fire.
Concerning installation and storage of the products, follow the instructions
listed below.
●Do not install the product in a place where humidity is lower than 20% or higher than 90%.
●Do not use the product in a place where humidity is lower than 25% or higher than 85%.
●Do not install the products at a closed place such as in a cabinet without clearance, at a place
with flammable gas or corrosive gas exist and in the open air.
●Doing so may cause a fire.
Do not connect equipment that exceeds the output capacity of the UPS.
You can use a plug strip and so on to connect extra equipment, but, in
this case, do not connect equipment that exceeds the current capacity of
the plug strip.
●The UPS may detect overload and stop the output.
●The wiring of the plug strip heats up, which may cause a fire.
Do not insert metal objects into the Power Supply Output Receptacle of
the UPS.
●Doing so may cause an electric shock.
Do not install the product in other orientations.
●Dropping or falling may cause injury.
Do not obstruct the air inlet and outlet in the side and rear of the product.
●Inside temperature increases, which may cause a failure of the UPS and the deterioration of
the battery.
●Install the product at least 5 cm from the walls.

14
2. Installation and connection
2-2 Installation
Install the UPS.
Do not use the product in an orientation other than the correct one shown in the figure below.
100%
75%
運転
テスト/
ブザー停止
容量表示
接続容量
オーバー
バッテリ
交換
異常
バイパス運転
電源出力
AC入力
バックアップ
運転
バッテリ
増設
INPUT OUTPUT
停止
50%
25%
!
100%
75%
運転
テスト/
ブザー停止
容量表示
接続容量
オーバー
バッテリ
交換
異常
バイパス運転
電源出力
AC入力
バックアップ
運転
バッテリ
増設
INPUTOUTPUT
停止
50%
25%
!
100%
75%
運転
テスト/
ブザー停止
容量表示
接続容量
オーバー
バッテリ
交換
異常
バイパス運転
電源出力
AC入力
バックアップ
運転
バッテリ
増設
INPUT OUTPUT
停止
50%
25%
!
100%
75%
運転
テスト/
ブザー停止
容量表示
接続容量
オーバー
バッテリ
交換
異常
バイパス運転
電源出力
AC入力
バックアップ
運転
バッテリ
増設
INPUTOUTPUT
停止
50%
25%
!
Correct installation orientation
Wrong installation orientation

15
2. Installation and connection
2-3 Connecting the equipment
(1) Disconnect the AC Input Plugs of all devices you want to back
up such as your PC and modems from a wall outlet (commer-
cial power).
(2) Connect devices you want to back up to the Power Supply
Output Receptacles of the UPS.
•If you need more output receptacles than those of the UPS,
purchase a plug strip and so on separately and use it as
extra output receptacles.
•Even if the input plug of a device you want to connect is 2-pin type, you can connect it directly to the
Power Supply Output Receptacle of the UPS. Notice that the input plug is 2-pin type with the grounding
wire, connect the grounding wire to the Grounding Terminal of the UPS.
•When you want to use an AC adaptor, connect it to a Power Supply Output Receptacle of the UPS with
space enough for the connection.
PC
Modem or other
peripheral
Wall outlet
(commercial power)
Plug of connected
device Plug of connected
device
Plug of connected
device
Connect it directly. Connect it directly. Connect the plug directly.
Connect the grounding
wire to the Grounding
Te r minal of the UPS.
Connect the Grounding Terminal
of the connected device to the
Grounding Terminal of the UPS.
< Example of
connection 1 >
< Example of
connection 2 >
PC
PC
Modem or other peripheral
External HDD

16
2. Installation and connection
●The UPS has been charged prior to shipment. However, the backup time becomes shorter when
using it for the first time due to spontaneous discharge.
We recommend charging the UPS before using it.
When you connect the AC Input Plug of the UPS to a wall outlet (commercial power), charging the
battery is automatically started and it is fully charged for 8 hours or less.
●You can perform "2-4 Checking the operation" on page 17 also before charging the battery.
(3) Connect between the UPS and the surge protection circuit.
See also "7. Using the Network Line Surge Protection Function" on page 35
* If you do not use the Network Line Surge Protection Function, this step is not required.
(4) If you use the attached UPS monitoring software or the standard UPS service of Windows NT or Windows
XP/2000 or if you use Contact Signal, connect the connecting cable between the UPS and your PC.
See also "8. Using the UPS monitoring software and Contact Signal" on page 36
* If you do not use the UPS monitoring software and Contact Signal, this step is not required.
(5) When the installation and connection is complete, connect the AC Input Plug of the UPS to a wall outlet
(commercial power).
RS232C
信号入出力コネクタ
信号カード
増設
冷却ファン
OUTPUT電源出力AC100V50/60Hz
最大10A/700W
接地
回線サージ保護
回線
ハブ側
モデム・TA
パソコン側
バッテリ
増設コネクタ
DC36V/20A
INPUT
AC100V入力
50/60Hz
15A
LINE/HUB MODEM・TA
NetworkCard
AC入力
過電流保護
15A
Use the Grounding Terminal
for grounding connection as
necessary (for example,
when the AC plug does not
provide any grounding
means).
Wall outlet for 3 pins
Wall outlet for 2 pins
Connect it to the Grounding
Te r minal of the wall outlet.
Grounding Terminal
PC

17
2. Installation and connection
2-4 Checking the operation
Before use, check that the Battery mode is performed normally according to the following procedure.
This operation check simulates an occurrence of a power failure by disconnecting the AC Input Plug from a
wall outlet.)
Caution
If the input plug is disconnected while the product is operating, never touch its
metal part.
●Doing so may cause an electric shock.
●The leak current of this product itself is less than the value of the safety standard (leak
current: 1 mA). However, leak current increases due to connected equipment. Therefore,
never touch the metal part of the input plug.
●When the product is operating, voltage is generated at the metal part of the input plug via
capacitors in the internal circuit regardless of elapsed time.
(1) Connect your PC and other devices to the UPS and then connect the AC Input Plug of the UPS to a wall
outlet (commercial power).
(2) Press the Start Switch to start the operation of the UPS.
Bring all connected devices into operation at the start of the operation.
(Including devices connected to the AC outlet of your PC.)
Operate them in a way in which it is allowable that power supply to the connected devices stops.
(3) Under this condition, check the display lamps of the UPS.
Are they the same status in the right figure?
Yes
The operation is normal.
Proceed to (4).
No
The operation is abnormal.
The display is one of them described in "C. Failure
(display and beep when a failure occurs in equipment)"
on page 23. Take necessary measures according to
the remedy and then proceed to (4).
Goes
on
Goes
out
Goes on, blinks,
or goes out
depending
on the status.
100%
75%
運転
テスト/
ブザー停止
容量表示
接続容量
オーバー
バッテリ
交換
異常
バイパス運転
電源出力
AC入力
バックアップ
運転
バッテリ
増設
INPUT OUTPUT
停止
50%
25%
!

18
2. Installation and connection
Yes
The operation is normal.
Proceed to (5).
No
The operation is abnormal.
●If the display is one of them described in "C. Failure (display and beep when a failure occurs in equipment)"
on page 23, take necessary measures according to the remedy and then go back to (4).
●If no Battery mode is performed and the UPS and the connected devices stop, insufficient charging of the
battery is suspected.
Connect the AC Input Plug of the UPS to a wall outlet (commercial power), charge the battery for at least 8
hours, and then go back to (4).
If the problem persists after checking the 2 points above, contact us please;
< When the battery is sufficient > < When the battery is low >
(4) Disconnect the AC Input Plug of the UPS from a wall outlet (commercial power) to bring it into backup
status.
Under this condition, check the display lamps and a beep of the UPS.
Are they the same status in the below figure?
Beep One beep at intervals of 4 second Beep One beep at intervals of 1 second
100%
75%
運転
テスト/
ブザー停止
容量表示
接続容量
オーバー
バッテリ
交換
異常
バイパス運転
電源出力
AC入力
バックアップ
運転
バッテリ
増設
INPUT OUTPUT
停止
50%
25%
!
100%
75%
運転
テスト/
ブザー停止
容量表示
接続容量
オーバー
バッテリ
交換
異常
バイパス運転
電源出力
AC入力
バックアップ
運転
バッテリ
増設
INPUT OUTPUT
停止
50%
25%
!
This manual suits for next models
2
Table of contents
Other Omron UPS manuals

Omron
Omron BL50T User manual

Omron
Omron BN75R User manual

Omron
Omron Powli BU1002SW User manual

Omron
Omron BW40T User manual

Omron
Omron POWLI BY50FW User manual

Omron
Omron BU5002RWLG User manual

Omron
Omron Powli BU3002SW User manual

Omron
Omron S8BA-24D24D480SBF User manual

Omron
Omron BN50T User manual

Omron
Omron BU150R User manual

Omron
Omron BU1002RW User manual

Omron
Omron POWLI BX75XS2 User manual

Omron
Omron S8BA-24D24D Series SBF User manual

Omron
Omron Powli BU50SW User manual

Omron
Omron POWLI BU60RE User manual

Omron
Omron POWLI BX35F User manual

Omron
Omron S8BA-24D24D960SBF User manual

Omron
Omron BU2002RWL User manual

Omron
Omron Powli BY35S User manual

Omron
Omron POWLI User manual