
4
is dc-coupled to ground; therefore the output of the
preamplifier must be either ac-coupled or have
approximately zero dc voltage under no-signal
conditions.
The 460 incorporates Pole-zero cancellation in
order to enhance theoverload characteristics of the
amplifier. This technique requires matching the
network to the preamplifier decay time constant in
order to achieve perfect compensation. The
network is variable and factory adjusted to 50 µs to
approximatelymatchallORTECFETpreamplifiers.
If other preamplifiers or more careful matching is
desired, the adjustment is accessible from the front
panel. Adjustment is easily accomplished by using
a monoenergetic source and observing the
amplifier baseline with an oscilloscope after each
pulseunderoverloadconditions.Adjustmentshould
be made so that the pulse returns to the baseline in
a minimum of time with no undershoot.
Preamplifier power of +24 V, +12 V, -24 V and -12
V is available on the preamplifier power connector.
When using the 460 with a remotely located
preamplifier (i.e., preamplifier-to-amplifier
connection through 25 ft or more of coaxial cable),
care must be taken to ensure that the characteristic
impedance of the transmission line from the
preamplifier output to the 460 input is matched.
Since the input impedance of the 460 is 1000
S
,
sending end termination will normally be preferred;
i.e., the transmission line should be series-
terminated at the output of the preamplifier. All
ORTEC preamplifiers contain series terminations
that are either 93
S
or variable; coaxial cable type
RG-62/U or RG-71/U is recommended.
3.3. CONNECTION OF TEST PULSE
GENERATOR
Connection to the 460 Through a Preamplifier
The satisfactory connection of a test pulse
generator such as the ORTEC 419 or equivalent
depends primarily on two considerations: the
preamplifier must be properly connected to the 460
as discussed in Section 3.2, and the proper input
signal simulation must be applied to the
preamplifier. To ensure proper input signal
simulation, refer to the instruction manual for the
particular preamplifier being used.
Direct Connection to the 460 Since the input of
the 460 has 1000
S
input impedance, the test pulse
generator will normallyhavetobeterminated at the
amplifier input with an additional shunt resistor. If
the test pulse generator hasadcoffset greater than
1 V, a large series isolating capacitor is also
required since the input of the 460 is dc-coupled.
ORTEC Test Pulse Generators are designed for
direct connection. When any of these units are
used, they should be terminated with a 100
S
terminator at the amplifier input or be used with at
least one of the output attenuators set at In. (The
small error due to the finite input impedance of the
amplifier can normally be neglected.)
Special Considerations for Pole-Zero
Cancellation The pole-zero-cancellation network
in the 460 is factory-adjusted for a 50-
:
s decay
time to match ORTEC FET preamplifiers. When
a tail pulser is connected directly to the amplifier
input, the PZ Adj should be adjusted if overload
tests are to be made (other tests are not affected).
See Section 6.2 for the details.
If a preamplifier is used and a tail pulser is
connected to the preamplifier test pulse input,
similar precautions arenecessary. In thiscase the
effect of the pulser decay must be removed, i.e., a
step input should be simulated. Details for this
modification are also given in Section 6.2.
3.4. CONNECTION TO POWER
Turn off the Bin Power Supply when inserting or
removing modules. The ORTEC NIM modules are
designed so that it is not possible to overload the
Bin Power Supply with a full complement of
modulesintheBin. Since,however, thismaynotbe
true when the Bin contains modules other than
those of ORTEC design, check the Power Supply
after inserting the modules. The4001/4002 has test
points on the Power Supply control panel for
monitoring the dc voltages.
3.5. SHAPING CONSIDERATIONS
The rise time of the output pulses from the 460 will
be a function of the rise time furnished from the
preamplifier and of the setting of the front panel
Integ switch. When the switch is set at 0.04
:
s, the
rise time for a step input from the preamplifier will
be less than 100 nsec. The 0.1- and 0.25-
:
s switch
settings will provide proportionately longer rise
times. Check the input specifications for the
instrument into which the 460 output pulses will be