manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. OutBack Power
  6. •
  7. Inverter
  8. •
  9. OutBack Power GSLC175-AC-230 User manual

OutBack Power GSLC175-AC-230 User manual

Components
900-0156-01-00 Rev B.vsd\Page-1\2013-06-14
©2013 OutBack Power Technologies. All Rights Reserved.
Contact Technical Support:
Telephone: +1.360.618.4363
Email: Support@outbackpower.com
Website: www.outbackpower.com
Radian System Products
Major Components
GS7048E Inverter/Charger
GSLC175-AC-230
GS Load Center GSLC175-AC-230
Inverter/Charger GS7048E
IMPORTANT:
Not intended for use with
life support equipment.
PV and Grid-Tied
Inverter
Battery Bank
Vented Battery Enclosure
MATE3
System
Display and
Controller
GS Load Center
(GSLC)
System Display MATE3
MATE3 uses FW-MB3 mounting bracket
MATE3 requires revision 002.015.xxx or higher
Includes Remote Temperature Sensor (RTS)
Optional OutBack Components
FLEXnet DC Monitor (FN-DC)
Communications
Manager HUB10.3
HUB10
HUB4
AC Sources Utility Grid (required)
AC Generator (optional)
Main Electrical Panel
Electrical Distribution Subpanel
(Protected Load Panel)
Battery Bank
Photovoltaic (PV) Array
Customer-Supplied Components
Grid-Tied Inverter, 230 Vac
De-energize/Shutdown Procedures
2a
2b
1
2
1
1b
1c 1d
3a
To de-energize or shut down the AC-coupled system:
1. Turn off (open) the AC circuit breakers.
2. Turn off (open) the DC circuit breakers for the battery.
Wait 5 minutes for the inverter to internally discharge itself.
3. Verify 0 Vdc on the first DC bus of the inverter by placing the voltmeter leads
on and .
4. Verify 0 Vdc on the second DC bus by placing the voltmeter leads on
and .
5. Verify 0 Vac on the AC output circuit breakers by placing the voltmeter leads
on and .
6. Verify 0 Vac on the grid-tied inverter terminals and .
1
2
Functional Test Points
Battery Voltage Test Points
AC OUT Voltage Test Points
(Terminal bus bar = TBB)
1a 1b 1c 1d
3a 2b
2a 2b
Grid-Tie Inverter Test Points
WARNING: Lethal Voltage
Review the system configuration to identify all possible
sources of energy. Ensure ALL sources of power are
disconnected before performing any installation or
maintenance on this equipment. Confirm that the
terminals are de-energized using a validated voltmeter
(rated for a minimum 1000 Vac and 1000 Vdc) to verify
the de-energized condition.
WARNING: Lethal Voltage
The numbered steps will remove power from the
inverters. However, sources of energy may still be
present inside the GSLC and other locations. To
ensure absolute safety, disconnect ALL power
connections at the source.
WARNING: Burn Hazard
Internal parts can become hot during
operation. Do not remove the cover
during operation or touch any internal
parts. Be sure to allow them
sufficient time to cool down before
attempting to perform any product
maintenance.
2a 2b
3a 2b
1b 1c
1b 1d
2a 2b
3a 2b
AC-Coupled Application
Radian Dimensions (includes MATE3):
85 cm (29.1") tall X 60.6 cm (23.9") wide
5. Secure the inverter to the surface using a minimum
of 1 wall screw (or other appropriate hardware).
6. Follow the instructions for installing the GS Load Center.
7. Follow the instructions for installing the bracket for the MATE3.
8. Follow appropriate instructions for installing the PV array and grid-tied
inverter (if not already present).
Wire Sizes & TorqueMounting
WARNING: Fire/Explosion Hazard
Do not place combustible or flammable materials within 3.7 m (12 feet) of the equipment. This unit employs mechanical
relays and is not ignition-protected. Fumes or spills from flammable materials could be ignited by sparks.
WARNING: Personal Injury
Use safe lifting techniques and standard safety equipment when working with this equipment.
IMPORTANT:
Clearance and access requirements may vary by location. Maintaining a 91.4 cm (36") clear space in front of the system for
access is recommended. Consult local electric code to confirm clearance and access requirements for the specific location.
900-0156-01-00 Rev B.vsd\Page-2\2013-06-14
©2013 OutBack Power Technologies. All Rights Reserved.
Torque Requirements
Circuit Breaker Stud Torque
M8
¼ - 20
5/16 - 18
3/8 - 16
AC Wire Sizes and Torque Values
It is recommended that conductors be 16 mm2
THHN copper, or larger, rated to 75°C
(minimum) unless local code requires otherwise.
AWG In-lb
#14 - 10
#8
#6 - 4
#3
#2
#1
1/0
Wire Size Torque
Radian Mounting:
1. Ensure the mounting surface is strong enough to handle 3 times the total weight of
all the components. Add a piece of plywood if necessary to strengthen the surface.
2. Attach the wall bracket to the surface centering the mounting holes on the sides
with the wall studs. Use all 6 mounting screws to secure the bracket.
3. Lift the inverter so that the inverter bracket is above the wall bracket.
4. Lower the inverter into place so that the inverter bracket slips into the wall bracket.
1
3
4
6
GSLC175-AC-230
N
E
U
L1 L2
GRID
L1 L2
GEN
N
E
U
N
E
U
L1 L2
OUT
RELAY
AUX
+ -
12V
AUX
Switch
INV
Remote Battery
Temp
Minimum DC Cable based on the
DC Circuit Breaker Amperage
Torque
DC
Circuit
Breaker Cable Size
125 70 mm2(1/0)
175 70 mm2(2/0)
250 120 mm2(4/0)
80 25 mm2 (#4 AWG)
60 16 mm2 (#6 AWG)
MATE3
GS8048
GSLC
1
2 2
3
4
5
7
8
8
9
ON/OFF
INV
9
Plywood
(Optional)
Wall Board
Wall
Bracket
Wall Stud
Side View
Inverter
Bracket
40.6 cm (16")
Plywood (Optional)
Wall Board
Wall Stud
Wall Bracket
Wall Stud
1
22
3
4
5
56
7
8
8
10 11 12
13
14
15
16
17
Radian Series
Inverter/Charger
MATE3
Mounting
Bracket
MATE3
GS Load Center
7
Shunt
Bolt 3/8"
Lock Washer
Flat Washer
Battery
Negative (–)
Lug
Negative Battery Cable
Connections
DC Plates
3/8 - 16Upper holes (+)
3/8 - 16Lower holes (+)
3/8 - 16Shunt Bolts (–)
Lower holes (+)
CAUTION: Equipment Damage
When connecting cables from the inverter to the battery
terminals, ensure the proper polarity is observed.
Connecting the cables incorrectly can damage or
destroy the equipment and void the product warranty.
!
PV and Grid-Tied
Inverter
mm2
2.5 – 6
10
16 – 25
35
35
50
70
Nm 20
25
35
35
40
50
50
2.3
2.8
4.0
4.0
4.5
5.6
5.6
Nm
5.6
25.4
25.4
4.0
4.0
In-lb
50
225
225
35
35
In-lb
20
35
50
225
22560
225225
22560
50
Nm
2.3
4.0
5.6
25.4
25.46.8
25.425.4
25.46.8
5.6
Battery
Negative (–)
Lug
Control Wiring Terminal Block:
The 12V AUX and RELAY AUX terminals are used to
control the devices which disconnect the grid-tied
inverter (the ROCB and the relays). These devices can
also automatically start a generator if one is present.
AC Circuit Breakers
1
2
3
4
DC Terminals - Inverter
AC Terminals - Inverter
5
DC Circuit Breakers
6
7
8
Mechanical Interlock
(Bypass)
9
10
Communication Ports
Auxiliary Terminals
11
12
13
14
15
AC OUT Bus Bar L1
16
17
GRID IN Bus Bar L1
GEN IN Bus Bar L1
AC Neutral
Ground
DC Positive (+) Plate
DC Negative (–) Bus Bar
Remote Operated
Circuit Breaker (ROCB)
Relays
Grid-Tied Inverter
Bus Bar
Bolt 3/8"
DC Positive (+)
Plate
Battery
Positive (+)
Lug
Flat Washer
Positive Battery Cable
Connections
Nut
Lock Washer
Flat Washer
15
6
NOTE: See the MATE3 manual for advanced generator start and other setup features
Acceptable modes for Gen input: Gen, Support
(based on application)
Acceptable modes for Grid input: Grid Tied,
Backup, UPS, Mini Grid (based on application)
Grid Tied or Backup required;
Off Grid mode not supported
for this application
IMPORTANT:
Steps through required for proper operation.
Programming should be done by a qualified installer who is trained on programming inverter power systems.
Failure to program accurate parameters for the system could potentially cause equipment damage.
Damage caused by inaccurate programming is not covered by the limited warranty for the system.
3 4
52
Front Relay
Rear Relay
Energize/Startup Procedures
Pre-startup Procedures:
1. Double-check all wiring connections.
2. Inspect the enclosure to ensure no tools or debris has been left inside.
3. Disconnect all AC loads at the backup (or critical) load panel.
4. Disconnect the AC input feed to the GSLC at the source.
900-0156-01-00 Rev B.vsd\Page-3\2013-06-14
©2013 OutBack Power Technologies. All Rights Reserved.
GSLC175-AC-230
CAUTION: Equipment Damage
Incorrect polarity will damage the equipment.
!
22 NC 12
Functional
Test Points
Battery Voltage Test Points
GRID IN Voltage Test Points
(Terminal bus bar = TBB)
Grid-Tie Inverter Test Points
AC OUT Voltage Test Points
(Terminal bus bar = TBB)
4a 2b
GEN IN Voltage Test Points
(Terminal bus bar = TBB)
2b
3a 2b
5a 2b
MATE3 Programming
Relays
(Top View)
1b
1a
1
2
3
4
6
2a 4a 5a 3a
5
6
2b
To energize the AC-coupled system:
1. Using a digital voltmeter (DVM), verify 48 Vdc
on the DC input terminals by placing the DVM leads
on and .
Confirm that the battery voltage is correct for the
inverter model.
Confirm the polarity.
2. Turn on (close) the DC circuit breakers from the
battery bank to the inverter.
3. Perform all programming (see the next section).
4. If the inverter is in the off state, turn it on.
5. Verify 230 Vac on the AC Output TBB by placing
the DVM leads on and .
6. Turn on (close) the AC output circuit breakers.
7. No voltage should be present on the grid-tied inverter
terminals and . Verify the condition of these terminals
using the DVM.
8. Start the generator (if present). Verify 230 Vac at the location of the AC sources.
9. Turn on the AC input feed to the GSLC at the source.
10. Verify 230 Vac on the GRID IN TBB by placing the DVM leads on and .
11. Verify 230 Vac on the GEN IN TBB by placing the DVM leads on and .
12. Turn on the AC disconnects at the backup (or critical) load panel and test the loads.
13. Turn on (close) the grid AC input circuit breaker.
14. When the rear relay energizes, its LED indicator will illuminate and AC should be present
on the grid-tied inverter terminals and . Verify 230 Vac on these terminals using
the DVM.
15. Check the grid-tied inverter for proper functionality.
Optional steps to test generator and ROCB function:
16. Turn on either the 12V AUX or the RELAY AUX menu item, or the generator circuit breaker
(if present). Turning on any of these three items will energize the front relay .
The LED indicator on the front relay will illuminate. At the same time the ROCB will
automatically turn off (open). No AC should be present on the grid-tied inverter terminals
and . Verify the condition of these terminals with the DVM.
17. Turn off the generator or AUX. The front relay will de-energize. The LED indicator will turn off.
The ROCB will automatically turn on (close). AC should be present on the grid-tied terminals.
Repeat these steps for the other two items from Step 16 if testing is necessary.
1a 1b
1
2
3
2a 2b
3a 2b
4
5
4a 2b
5a 2b
6
3a 2b
3a
2b
7
76
1a 1b
Rear Relay
ROCB
6 7
7
LED Indicator 7
1
15
2a
Insert wire
Insert narrow screwdriver
Press straight down to unlock
wire release mechanism
22 12
21 11
24 14
A2 A1
22 12
21 11
24 14
A2 A1
Front Relay
Rear Relay
Relays
(Top View)
RELAY
AUX
+ -
12V
AUX
Switch
INV Remote Battery
Temp
Neutral
Ground
AC IN
HOT NEUTRAL
GROUND
AC Subpanel
Loads
(230 Vac)
General Wiring for AC-Coupled Applications
900-0156-01-00 Rev B.vsd\Page-4\2013-06-14
©2013 OutBack Power Technologies. All Rights Reserved.
IMPORTANT: Example only. Actual wiring
may vary depending on local electric codes.
Factory wiring and inverter AC wiring are not shown.
GSLC175-AC-230
AC Generator
L1
Negative
Positive
Ground
BATTERY
LEGEND
Neutral
HOT L1
Ground
AC LEGEND AC
Distribution Panel
Battery Bank
Vented Battery Enclosure
Ground
Electrode
Conductor
(Ground Rod)
RTS
Radian Inverter/Charger
N
E
U
L1 L2
GRID
L1 L2
GEN
N
E
U
N
E
U
L1 L2
OUT
RELAY
AUX
+ -
12V
AUX
Switch
INV Remote Batte ry
Temp
REMOTEO PERATED DEVICE
SEVERESHOCKHAZARD
W W
A A
R R
N N
I I
N N
G G
DISCONNECT POWERTO
THISDEVIC EBEFORE
SERVICING
Generator Start
Relay AUX
RELAY
LEGEND
12V AUX
+
–
Accessory
Terminals PV and
Grid Tie Inverter
MATE3
System Display
L1
L1
GEN
N
N
N
L1
L1
L1
L1
N
N
N
GEN
L1 L1 L1
L1

Other OutBack Power Inverter manuals

OutBack Power FXR International Series User manual

OutBack Power

OutBack Power FXR International Series User manual

OutBack Power EnerSys RADIAN Series User manual

OutBack Power

OutBack Power EnerSys RADIAN Series User manual

OutBack Power SKYBOX User manual

OutBack Power

OutBack Power SKYBOX User manual

OutBack Power FLEXpower ONE VFX3524 User manual

OutBack Power

OutBack Power FLEXpower ONE VFX3524 User manual

OutBack Power Radian GS8048A User manual

OutBack Power

OutBack Power Radian GS8048A User manual

OutBack Power GS7048E User manual

OutBack Power

OutBack Power GS7048E User manual

OutBack Power GTFX Series Owner's manual

OutBack Power

OutBack Power GTFX Series Owner's manual

OutBack Power ProHarvest PRO208-5k75 User guide

OutBack Power

OutBack Power ProHarvest PRO208-5k75 User guide

OutBack Power RADIAN Series User manual

OutBack Power

OutBack Power RADIAN Series User manual

OutBack Power Radian GS8048A User manual

OutBack Power

OutBack Power Radian GS8048A User manual

OutBack Power FLEXWare FLEXmax 100 User manual

OutBack Power

OutBack Power FLEXWare FLEXmax 100 User manual

OutBack Power FXR2012A User manual

OutBack Power

OutBack Power FXR2012A User manual

OutBack Power Radian GS8048A User manual

OutBack Power

OutBack Power Radian GS8048A User manual

OutBack Power Radian International Series User manual

OutBack Power

OutBack Power Radian International Series User manual

OutBack Power GSLC175-AC-120 User manual

OutBack Power

OutBack Power GSLC175-AC-120 User manual

OutBack Power FXR2012E User manual

OutBack Power

OutBack Power FXR2012E User manual

OutBack Power FXR2012A User manual

OutBack Power

OutBack Power FXR2012A User manual

OutBack Power GS Load Center Series User manual

OutBack Power

OutBack Power GS Load Center Series User manual

OutBack Power FX Mobile Series User manual

OutBack Power

OutBack Power FX Mobile Series User manual

OutBack Power RADIAN Series User manual

OutBack Power

OutBack Power RADIAN Series User manual

OutBack Power FLEXware SKYBOX RSD-1 User manual

OutBack Power

OutBack Power FLEXware SKYBOX RSD-1 User manual

Popular Inverter manuals by other brands

Lenze 8400 BaseLine C Reference manual

Lenze

Lenze 8400 BaseLine C Reference manual

Tsun TSOL-ESK350-E Quick installation guide

Tsun

Tsun TSOL-ESK350-E Quick installation guide

Yamaha NPS 4500 owner's guide

Yamaha

Yamaha NPS 4500 owner's guide

Kemot PROsolar-500 owner's manual

Kemot

Kemot PROsolar-500 owner's manual

Fuji Electric FRENIC-Multi instruction manual

Fuji Electric

Fuji Electric FRENIC-Multi instruction manual

SunSynk SUN-25K-SG01HP3-EU-BM2 Installer manual

SunSynk

SunSynk SUN-25K-SG01HP3-EU-BM2 Installer manual

Black & Decker PI200AB instruction manual

Black & Decker

Black & Decker PI200AB instruction manual

Hameg HM 8131-2 manual

Hameg

Hameg HM 8131-2 manual

Veikong VFD500 Series user manual

Veikong

Veikong VFD500 Series user manual

Agilent Technologies 33250A user guide

Agilent Technologies

Agilent Technologies 33250A user guide

GoWISE PS1007 user manual

GoWISE

GoWISE PS1007 user manual

Mitsubishi Electric FR-A7AZ instruction manual

Mitsubishi Electric

Mitsubishi Electric FR-A7AZ instruction manual

Beghelli Nova UAC instructions

Beghelli

Beghelli Nova UAC instructions

RedEarth BlackMax installation manual

RedEarth

RedEarth BlackMax installation manual

Work Men WMG2300 owner's manual

Work Men

Work Men WMG2300 owner's manual

Sungrow SG60KU-M user manual

Sungrow

Sungrow SG60KU-M user manual

SolaX Power X1-ESS G4 user manual

SolaX Power

SolaX Power X1-ESS G4 user manual

Cooks Hydro Bottle H2 quick start guide

Cooks

Cooks Hydro Bottle H2 quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.