4-28
VRF SYSTEMS Indoor Unit Specifications
2. Low Silhouette Ducted Type (F2 Type)
2-1. Specifications
Unit specifications (D)
INDOOR MODEL S-106MF2E5A S-140MF2E5A S-160MF2E5A
PANEL MODEL - - -
PERFORMANCE TEST CONDITION ISO15042 / AS / NZS3823 / EN14511 / EN12102
POWER SUPPLY ø, Hz 1ø 50 / 60Hz 1ø 50 / 60Hz 1ø 50 / 60Hz
V 220 230 240 220 230 240 220 230 240
C
O
O
L
I
N
G
CAPACITY
kW 10.6 10.6 10.6 14.0 14.0 14.0 16.0 16.0 16.0
BTU/h 36200 36200 36200 47800 47800 47800 54600 54600 54600
kcal/h(Fri./h) - - - - - - - - -
CURRENT A 1.35 1.30 1.27 1.48 1.44 1.39 1.55 1.50 1.47
INPUT POWER W 195 195 195 215 215 215 225 225 225
ANNUAL CONSUMPTION
W *4 - - - - - - - - -
EER/EER CLASS
(W/W)*5/("A"~"G")
---------
EER BTU/hW - - - - - - - - -
POWER FACTOR % - - - - - - - - -
NOISE INDOOR
(H/M/L)
dB-A 38/34/31 39/35/32 40/36/33
Power Level dB 60/56/53 61/57/54 62/58/55
NOISE OUTDOOR
(H/L)
dB-A - - -
Power Level dB - - -
H
E
A
T
I
N
G
CAPACITY
kW 11.4 11.4 11.4 16.0 16.0 16.0 18.0 18.0 18.00
BTU/h 38900 38900 38900 54600 54600 54600 61400 61400 61400
kcal/h(Fri./h) - - - - - - - - -
CURRENT A 1.37 1.34 1.29 1.46 1.42 1.38 1.55 1.50 1.46
INPUT POWER W 200 200 200 210 210 210 225 225 225
COP/COP CLASS
(W/W)*5/("A"~"G")
---------
COP BTU/hW - - - - - - - - -
POWER FACTOR % - - - - - - - - -
NOISE INDOOR
(H/M/L)
dB-A 38/34/31 39/35/32 40/36/33
Power Level dB 60/56/53 61/57/54 62/58/55
NOISE OUTDOOR
(H/L)
dB-A - - -
Power Level dB - - -
EXTRA LOW TEMP
CAPACITY(kW)/INPUT POWER(W)/COP
---
Cooling
MAX CURRENT(A)/MAX INPUT POWER(W)
1.80 / 265 1.75 / 265 1.70 / 265 1.80 / 265 1.75 / 265 1.70 / 265 1.91 / 285 1.86 / 285 1.81 / 285
Heating
MAX CURRENT(A)/MAX INPUT POWER(W)
1.80 / 265 1.75 / 265 1.70 / 265 1.80 / 265 1.75 / 265 1.70 / 265 1.91 / 285 1.86 / 285 1.81 / 285
STARTING CURRENT(A)/COMP OUTPUT(W) - - - - - - - - -
NETWORK IMPEDANCE (ΩMAX.) *3 - - -
FM OUTPUT (ID/OD) W 235 235 235
MOISTURE REMOVAL VOLUME L/h(Pt/h) 6.4 (13.4) 9.0 (18.9) 10.7 (22.5)
External static pressure
Pa
100 (MIN10 - MAX150) 100 (MIN10 - MAX150) 100 (MIN10 - MAX150)
I/D AIR
FLOW
COOL m3/min (ft3/min) 32/26/21 (1130/918/742) 34/29/23 (1201/1024/812) 36/32/25 (1271/1130/883)
HEAT m3/min (ft3/min) 32/26/21 (1130/918/742) 34/29/23 (1201/1024/812) 36/32/25 (1271/1130/883)
O/D AIR
FLOW
COOL m3/min (ft3/min) - - -
HEAT m3/min (ft3/min) - - -
REFRIGERANT TYPE, AMOUNT g(oz) - - -
P
R
O
D
I
M
HEIGHT : H mm(inch) 290 (11-7/16) 290 (11-7/16) 290 (11-7/16)
WIDTH : W mm(inch) 1400 (55-1/8) 1400 (55-1/8) 1400 (55-1/8)
DEPTH : D mm(inch) 700 (27-9/16) 700 (27-9/16) 700 (27-9/16)
P
A
C
D
I
M
HEIGHT : H mm 355 355 355
WIDTH : W mm 1614 1614 1614
DEPTH : D mm 850 850 850
MASS (NET) kg(lb) 46 (102) 46 (102) 46 (102)
(GROSS) kg(lb) 55 (122) 55 (122) 55 (122)
LAYERS LIMIT (actually) 9 (10) 9 (10) 9 (10)
Operation
Condition
Cool (DBT) - - -
Heat (DBT) - - -
P
I
P
I
N
G
PIPE DIAMETER mm (inch)
(Liquid) ø9.52 (3/8) (Gas) ø15.88 (5/8) (Liquid) ø9.52 (3/8) (Gas) ø15.88 (5/8) (Liquid) ø9.52 (3/8) (Gas) ø15.88 (5/8)
CONNECT METHOD, STD LENGTH m (ft)
fl ared type fl ared type fl ared type
PIPE LENGTH RANGE m (ft)
------
I/D & O/D HEIGHT DIFFERENCE m (ft)
------
ADD GAS AMOUNT
g
/m (oz/ft)
------
PIPE LENGTH FOR ADDITIONAL GAS m (ft)
------
*3:Network Impedance shall be applicable for EUROPE and CHINA models.
*4:The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5:EER and COP classification is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*:In case it is necessary to indicate the air flow volume in (l/s), the value in (m3/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*:
If the EUROVENT Certified models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230V shall be used.
TD831172-00VRFSYSINDOOR.indb28TD831172-00VRFSYSINDOOR.indb28 2014/04/2416:49:162014/04/2416:49:16