Panduit Z11C Series User manual

For Technical Support: http://www.panduit.com/wcs/Satellite?pagename=PG_Wrapper&friendlyurl=/en/support/contact-us
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2014 V00028RH
Page 1 of 8
Z11C-**PreconfiguredNetworkZoneSystem
Preconfigured Network Zone System
Part Number(s): Z11C-**

For Technical Support: http://www.panduit.com/wcs/Satellite?pagename=PG_Wrapper&friendlyurl=/en/support/contact-us
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2014 V00028RH
Page 2 of 8
TABLE OF CONTENTS
Overview of Products
Warnings / Safety Information
Specs/ Tools Needed
Wall Mounting
Reversible Door
Removable Gland Plate
Pre-Configured Layout
Recommended Installation Instructions for:
Power Entry
Uplink Entry
Downlink Entry
Page 3
Page 3
Page 4
Page 5
Page 6
Page 6
Page 7
Page 7
Page 8
Page 8

For Technical Support: http://www.panduit.com/wcs/Satellite?pagename=PG_Wrapper&friendlyurl=/en/support/contact-us
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2014 V00028RH
Z11C-**
Preconfigured Network Zone System Z11C-** configurations include an enclosure and cable
management.
Be sure wall is capable of supporting cabinet and equipment.
DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITIES
The practices contained herein are designed as a guide for use by persons having technical skill at their own discretion and risk. Panduit
does not guarantee any favorable results or assume any liability in connection with these instructions. Local, State, Federal, and Industry
Codes and Regulations, as well as manufacturers requirements, must be consulted before proceeding with any project. Panduit Corp.
makes no representations of nor assumes any responsibility for the accuracy or completeness set forth herein.
Panduit disclaims any liability arising from any information contained herein or for the absence of same.
Page 3 of 8
SAFETY INFORMATION
The information and instructions contained in this document are not intended to be utilized as a substitute for proper training and
experience in the safe installation and operation of product. Prior to installation, it is the Buyer’s responsibility to consult with the
appropriate local Authority Having Jurisdiction (AHJ) for all applicable codes, permits, regulations and standards.
This product, including any equipment that may be installed inside, should only be installed and serviced by a licensed electrical
contractor, or competent technician, that meets the following qualifications;
· Is thoroughly familiar with this product and the instructions for installation and operation
· Is trained (accredited) in industry-accepted safe operating practices and procedures regarding identification and mitigation of
high- and low- voltage hazards and situations.
· Is trained to identify and install appropriately-sized Branch Circuit Disconnect(s) with appropriately-sized Branch-Circuit
Protective Rating and Short-Circuit Current Rating (SCCR), before connecting Panduit product to the branch circuit.
· Is trained and authorized to energize, de-energize, clear and ground power distribution equipment.
Is trained in the care and use of appropriate PPE (personal protective equipment) including, but not limited to; arc-flash protective cloth-
ing, safety glasses, face shield, hard hat, gloves and non-conductive tools (clamp stick, hot stick, etc.).

For Technical Support: http://www.panduit.com/wcs/Satellite?pagename=PG_Wrapper&friendlyurl=/en/support/contact-us
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2014 V00028RH
Tools and supplies needed to complete install of Preconfigured Zone System: (not included)
· Fiber-optic trunk cable: FSPD504 or similar
· LC Fiber-optic connectors: FLCDMCXAQY or similar
· Fiber-optic termination tools: OptiCam termination kit or similar
· Category 6 copper cable for downlinks: PUR6504BU-UY or similar
· Copper cable termination tools: wire cutters, EGJT tool
· Rigid conduit for power and copper downlink cables
· Tools to cut enclosure sidewalls: Greenlee punch or similar
· 5/16” bolts for wall mounting of enclosure
· #6 AWG Infrastructure ground cable: RGEJ660PF or similar
· 3/8" bolts for wall mounting of stainless steel enclosure
· 3/8" socket or box wrench ground bar
Preconfigured Network Zone Z11C-** Specifications
Enclosure Rating UL Type 4/12 and IP66 (IEC 60529), NEMA 4X available
Installation Wall mount with outside-mount flange
Dimensions
Height Width Depth
12”
(305 mm)
14”
(356 mm)
9.7”
(246 mm)
Weight 35 lbs. (15.9 kg)
Page 4 of 8

For Technical Support: http://www.panduit.com/wcs/Satellite?pagename=PG_Wrapper&friendlyurl=/en/support/contact-us
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2014 V00028RH
Wall Mounting
Enclosure may be mounted on any wall utilizing Unistrut or by drilling directly into any concrete wall.
There are two mounting hole locations on the top flange and two locations at the bottom flange.
Step 1:
Drill holes 7.25"-10" apart horizontally and 16" apart vertically.
Step 2:
Mount the enlosure with the locks to the right and secure.
7.25"-10"
16"
Hole Locations for Wall Mounting
Page 5 of 8

For Technical Support: http://www.panduit.com/wcs/Satellite?pagename=PG_Wrapper&friendlyurl=/en/support/contact-us
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2014 V00028RH
Page 6 of 8
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2014
Reversible Door
The enclosure comes with the door opening to the left.
The door may be reversed to open to the right.
Step 1: Remove screws and washers from door hinges.
Step 2: Turn door 180 degrees and mount to opposite side of enclosure using same screws and washers.
**New Hole locations will have to be drilled or punched out.**
Step 1
Detail View-2 Places
Step 2
Detail View-2 Places
Torque 33 in-lbs.
Removable Gland Plate
The Gland Plate, located on the bottom of the enclosure, is removable for machining to accept bulkhead connectors or compression fit-
tings.
To remove gland plate, unfasten the (10) nuts and (10) flat washers attached to the threaded studs of the gland plate and remove plate
from the enclosure.
When reinstalling the gland plate, ensure the nuts are tightened until the gland plate flanges make contact with the enclosure surface.
Gland Plate
Remove nuts and washers

For Technical Support: http://www.panduit.com/wcs/Satellite?pagename=PG_Wrapper&friendlyurl=/en/support/contact-us
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2014 V00028RH
Page 7 of 8
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2014
Recommended Installation Instructions for Bundled Accessories
Preconfigured Network
DIN Rail
DIN rail mounted Mini-Com
adapters (2)
Fiber patch cord
slack spool
Stratix 5700 Industrial
Switch
Cable management L-rings
mounted to the side acces-
sory panel
Power Entry
Run incoming 24 VDC power
through conduit installed on top or
bottom gland plate. Install power
wiring according to the field wiring
diagram. (Conduit or cord grips
provided by customer)
Ground Wire

E-mail:
Fax:
(800) 777-3300
For Instructions in Local Languages
and Technical Support:
http://www.panduit.com/wcs/Satellite?pagename=PG_Wrap-
per&friendlyurl=/en/support/contact-us
Page 5 of 5
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2014 V00028RH
www.panduit.com
Uplink Cabling
Uplink cable entry
Fiber patch cord slack on the
side mounted spool
Downlink Cabling
Downlink cable entry
Slack loop formed around
the L-ring cable managers
Page 8 of 8