72-PHW-1033 R2.0 023-0388 Wall CO2 Leak Detect Spec&Install.docx RL 2022-02-09 Page 1 of 4
Parker Hannifin Canada
Micro Thermo Technologies TM
12855 rue Brault
Mirabel, QC J7J 0C4 Canada
Office phone 450-668-3033
Technical Data
023-0388 Wall mount CO2 Leak Detector
specification & installation guide
Precision carbon dioxide
control/sensing
FEATURES:
• 2 Available Ranges
• Automatic Calibration Logic Program
• Easy field adjustment
• LCD Display and analog out
• On-board Relay and menu driven set-up
• Solid-state reliability
• Small compact size
• Solid, reliable mounting method
DESCRIPTION:
The CO2 monitor uses a highly accurate and reliable Non-dispersive Infrared (NDIR) sensor with state-of-the-art
digital linearization and temperature compensated circuitry in an attractive, low profile enclosure for room
applications to detect CO2 levels and provides a linear analog signal output of 4-20 mA, 0-5 or 0-10 Vdc signals. An
onboard relay can provide a control signal based on a high limit setting. Parameters are set up via momentary
pushbutton (keypad) and the LCD display which is also used to display current reading.
SPECIFICATIONS:
Gas Type Detected ........................................................................................ Carbon Dioxide (CO2)
Measurement Ranges .................................................................................. 0 –2000, 0 –6000 ppm
Measurement Type ................................................... Dual channel non-dispersive infrared (NDIR)
Sensor Coverage Area ............................................................................... 100 m² (1000 ft²) typical
Sensor Accuracy.............................................................................. ± 30ppm + 3% of reading value
Relay Trip Point (High or Low)............ Programmable 500 –9000 ppm by step of 100 via keypad
Relay Hysteresis .................................................................. Programmable 25-500 ppm via keypad
Contact Ratings ........................... Form A contact (N.O.), 2 Amps @ 140 Vac, 2 Amps @ 30 Vdc
Reading Resolution ......................................................................................................... 1 ppm CO2
Backlight ................................................................................... Auto, Enable or disable via keypad
Power Supply ............................ 24 Vdc ±20% or 24 Vac ±10% (non-isolated half-wave rectified)
Consumption ........................................................ 75 mA @ 24 Vdc max, 150 mA @ 24 Vac max,
Output Signals .......................... 4-20 mA active (sourcing), 0-5 Vdc or 0-10 Vdc (field selectable)
Output Drive Capability ........................................ Current: 550 ohms max Voltage: 10k Ohm min
Output Accuracy ........................ ±0.25% of span (including linearity, hysteresis and repeatability)
Response Time ...................................................................................................... 20 seconds (T63)
Operating Temperature ................................................................................... 0°- 50°C (32°-122°F)
Storage Temperature .............................................................................. -40 to 70°C (-40 to 158°F)
Operating and Storage Humidity ...................................................... 5 to 90 %RH, non-condensing
Sensor Life Expectancy ........................................................... >15 years in normal room condition
Altitude Correction ......................................................... Programmable from 0-2550 m via keypad
Screw Terminal Block ............................................................................................... 14 to 22 AWG
Enclosure Ratings ............................................................................... ABS White, IP30 (NEMA 1)
External Dimensions .................................. 84mm W x 119mm H x 29mm D (3.3” x 4.7” x 1.15”)
Mounting Holes ............................................................................................... Multiple possibilities

72-PHW-1033 R2.0 023-0388 Wall CO2 Leak Detect Spec&Install.docx RL 2022-02-09 Page 2 of 4
Mechanical Information
ORDERING INFO:
Order P/N 023-0388
By fax to 1-844-867-4795
Or email to
MTorder@Parker.com
CO2 Sensors 023-0388 Installation
For leak detection install the CO2 sensor on the rack at 12” (30cm) from floor.
One 24VAC transformer can be used for many CO2 sensors only if the common side is on the same side of the
transformer (Calculate 3VA per CO2 sensor).
The CO2 sensor 023-0388 reading range should be factory set to 0-6000ppm, output set to 4-20mA. When powering
the sensor, the setting must be checked. To check press the Menu button. If these are not the settings make the
changes as follow:
Set Transmitter switch to mA (4-20mA).
Press on MENU repeatedly to choose option, press on UP or DOWN to change value. Value is saved when MENU
is pressed again. CO2 Span = 6000 PPM (Range)
Self-Cal = On
Relay CO2 = High
Relay SP = 4000 PPM (Relay On )
Relay Hy = 200 (Hysteresys to have Relay Off @ 3800 PPM)
Relay Dly = 0min
To exit press MENU until you see current CO2 ppm reading.
Connect the signal on 4-20mA mode with 470-0300 255 ohms resistor at the Sensor Node input to reduce the
reading variation of PPM caused by the wire length.
Option: Use a MT-Display 961-462C to display the PPM remotely. Power it on any 24V transformer (see
installation documentation for Case Display PUID 72-MTA-1003.
Install sign 905-0012 “If the value shown exceeds 5000 ppm DO NO ENTER”above the MT-Display.
Make the connections by following wiring instruction of a manual pull station 961-0001.
Make bindings between nvoUniversalX of the Sensor Node and nviPPM of the MT-Display.
Create model on Alliance see section Adding a CO2 sensor model or PUID 72-MTA-1010.
Set the High limit to 2500ppm and Low limit to 50ppm with a delay of 0 and a low priority.

72-PHW-1033 R2.0 023-0388 Wall CO2 Leak Detect Spec&Install.docx RL 2022-02-09 Page 3 of 4
Addition of CO2 sensor model for MTA V5.X version
Already added in version 7.0 (updated in 8.6)
Create sensor in the menu “Configure-Sensor Model”for the following models
Model on key 341: 023-0388 CO2 6000 ppm (4-20mA)
The range and level of the relay must be changed specifically for the 023-0388 model
Copy “CD2RMC Wall Sensor Transmitter 20mA.bmp”in the “C:\Alliance\Images\SensorModels”
If “CDDn Wall Sensor Transmitter 20mA.bmp”is in the folder \Images\Sensor Models it could be used but is not
exactly the same.
Sensor Node
nvoUniversal
Input U
GND
MT-Display nviPPM
CO26000 ppm
MT-Display
and strobe
installed on
the wall
outside of
the room
sign :
If the value shown
exceeds 5000 ppm
DO NOT ENTER
strobe
Light
Manual pull
station
961-0001
strobe
Light
CO2 sensor on
the rack and the
strobe installed
on the wall inside
of the room
255 ohms
resistor must be
installed at the
sensor node

72-PHW-1033 R2.0 023-0388 Wall CO2 Leak Detect Spec&Install.docx RL 2022-02-09 Page 4 of 4
Addition of CO2 sensor model for MTA V5.X version (suite)
Manufacturer: Micro Thermo
Diagram: CD2RMC Wall Sensor Transmitter 20mA.bmp
Physical type: Gas Concentration
Electrical type: 4-20mA
Choose Absolute
Time Constant: 2s
Max Range: 6000 ppm
Min Range: 0ppm
Max Offset: ±200 ppm
Point 1: 0.02A at 6000 ppm
Point 2: 0.004A at 0ppm
Max send time: 30 s
Min send time: 3s
Send on delta: 40 ppm
Addition of CO2 sensor model for MTA V6.X version
Create sensor in the menu « Configure-Sensor Model » for the following models
Model on key 341 :023-0388 CO2 6000 ppm (4-20mA)
If « CDD4 Wall Sensor Transmitter 20mA.bmp » is in the folder « Images-Sensor Models » it could be used but is not exactly the
same.
Example in MTA V6.0
Configuration of alarm limits
Other Parker Security Sensor manuals
Popular Security Sensor manuals by other brands

Cytron Technologies
Cytron Technologies LSA08 user manual

Ultra-safe
Ultra-safe 96305 User instruction manual

PCB Piezotronics
PCB Piezotronics 138A06 Installation and operating manual

System Sensor
System Sensor SpectrAlert CH24MC Series Installation and maintenance instructions

PEHA
PEHA SENSOLUX 482 FU-BM DE Installation and operating instructions

Pasesa
Pasesa AVE-2000 Pro Instructions for use