Parker Sporlan TCB User manual

Sporlan TCB
Temperature Control Board
December 2010 / BULLETIN 100-50-1

Page 2 / Bulletin 100-50-1
LEGEND
TEST POINTS and PIN JUMPERS
TP1 Test Point 1 positive connection point to millivolt voltmeter to
read set point temperature
TP2 Test Point 2 negative connection point as above
P1 Pin Jumper 1 voltage or current input selector
P2 Pin Jumper 2 TTL logic or 24-120 VAC Pulse Width Modulated
signal input selector
P4 Pin Jumper 4 internal power selector - DO NOT CHANGE
P5 Pin Jumper 5 force valve open switch - valve will open and will
remain open as long as jumper is installed
P6 Pin Jumper 6 force valve closes switch - valve will close and
remain closed while jumper is installed
P7 Pin Jumper 7 temperature sensor enable selector
P8 Pin Jumper 8 “open on rise” logic selector
P9 Pin Jumper 9 “close on rise” logic selector
P10 Pin Jumper 10 SEI .5 to SEI-11 valve selector (1596 step stroke)
P11 Pin Jumper 11 CDS-8 valve selector (3193 step stroke)
P12 Pin Jumper 12 all other valves selector (6386 step stroke)
WIRING CONNECTIONS
PID+ connect positive side of 4-20 ma or 0-10 VDC signal
INPUT connect negative side of 4-20 ma or 0-10 VDC signal
BLACK connect black valve lead
WHITE connect white valve lead
GREEN connect green valve lead
RED connect red valve lead
Square Wave connect TTL logic (5 VDC) step signal
DIRECTION connect TTL logic direction signal. 5 VDC = OPEN, 0 VDC
= CLOSE
24 VAC 2 connections for 24 VAC or 24 VDC @ 40 VA isolated
power input
PUMPDOWN
2 connections for pumpdown contacts. When “shorted”
the valve will close and remain closed. When “open” the
valve will control normally. For alternate operation see 5.
under “Wire the Board” pg 3.
TEMP SENSOR 2 connections for supplied 2 k type B thermistor. Not
polarized.
Blank no connection - for high voltage input isolation.
AC PULSE for one leg of 24-120 VAC, 3-30 second Pulse Width
Modulated signal.
Blank no connection - for high voltage input isolation.
AC PULSE for the other leg of 24-120 VAC, 3-30 second Pulse Width
Modulated signal.
NOTE: Not all inputs or pin jumpers will be used. See Configuration
instructions.
Valves of any capacity except 2500 step
valves such as CDST-4 & CDST-7 (see note
on page 2). Pin jumpers on the face of the
board will permit changes in board control
parameters to suit particular applications.
Figure 1 shows the layout of the board with
connection points labeled.
Figure 1
P6
P5
P1
P2
P12
P11
P10
P9
P8
TP2
Set Point
Potentiometer
TP1
P7
24-120 VAC
PWM Pulse
No Conn.
Temp. Sensor
Pumpdown
24VAC
TTL
Direct.
TTL
Wave
Red
Green
PID+ PID-
Black
White
P4
The Sporlan TCB has been developed to
allow the control of most Sporlan electric
valves with the use of a generic PID or
similar controller, or with the addition of the
Sporlan sensor, to perform as a stand alone
temperature controller. In addition to the 0
to 10 volt DC or 4 to 20 milliamps signal
usual from PID controllers, the TCB can be
configured to modulate a valve in response
to a TTL (5 volt) signal, or a 24-120 volt
AC pulse of three to thirty seconds duration.
The TCB may be ordered less potentiometer
if an external signal (e.g. 4-20ma) is to be
used. See ordering instructions. The board
was designed for easy standoff mounting
in electrical panels supplied by others, and
with screw terminal wiring connections.
The unit is small (3.5” x 4.0”) and eco-
nomical and requires only 24 volts AC or
24 VDC at 40 VA for both board and valve
power. Operating ambient and storage tem-
perature is -10°F to 160°F.
The TCB has been designed to work with
Sporlan SEI/SEH Electric Expansion
Valves, CDS Electric Suction Control
Valves, and SDR Electric Hot Gas Bypass
FOR USE ON REFRIGERATION and/or AIR CONDITIONING SYSTEMS ONLY
Bulletin 100-50-1, December 2010 supersedes Bulletin 100-50-1, January 2006 and all prior publications.

Bulletin 100-50-1 / Page 3
SET POINT POTENTIOMETER
The potentiometer is only used when the
TCB acts as a standalone controller. When
using an external signal source the potenti-
ometer is not required and may be removed.
When used with the optional sensors, tem-
perature range is -40°F to 210°F.
CAUTION: The TCB with potentiometer
cannot be used to directly control an
Electric Expansion Valve (EEV). EEVs
must be controlled by superheat sensing
and the TCB can only supply a single
temperature signal.
PIN JUMPERS
Pin jumpers are used in electronics as
switches for parameters that need not be
changed after initial configuration. Always
remove power from the board before mak-
ing pin jumper changes.
The jumper itself is a small plastic housing
containing metal contacts. These contacts
will fit snugly over two adjoining pins to
create an electrical “closure”. In the tables
and instructions below, the Letters indicate
the pins that are to be connected with the
pin jumpers. Care should be taken to make
sure both pins are covered by the jumper
and the pins themselves are not damaged.
SETUP INSTRUCTIONS
CONFIGURE THE BOARD
1. Choose the valve - See Table 1
2. Choose the signal - See Table 2
3. Set the logic - Refer to instructions
on right
MOUNT THE BOARD
Use the four corner mounting holes with plas-
tic or metal standoffs. Care must be exer-
cised to ensure that mounting screws or
metallic standoffs do not contact any track
or conductor path on the board. Location
chosen should be dry, protected and close to
24 VAC supply and PID controller. If used,
Set Point Potentiometer may be remotely
mounted, e.g. through the control panel.
Refer to “SET POINT POTENTIOMETER”
section for instructions.
WIRE THE BOARD
1. If using an external PID or PLC con-
troller, connect the positive lead to the
first screw terminal on the board and the
negative lead to the second screw terminal.
CAUTION: The PLC or PID controller
must be able to supply 20 milliamps at
12 volts DC into a 600 ohm impedance.
Other signals may not control the TCB
properly. If the internal temperature control
is used, these terminals will not be used.
2. Connect the valve leads to the next four
screw terminals, matching indicated colors.
3. If TTL logic is being used to control
the valve, connect the step signal to the
Square wave terminal and the direction
signal to the DIRECTION terminal. If TTL
logic is not used these terminals will not
be connected. Contact Sporlan for more
information.
4. Connect a 24 VAC, 40 VA transformer
to these terminals. CAUTION: The trans-
former may not be used for any other
device. The isolated secondary of this trans-
former is not polarized and may be con-
nected to either screw terminal.
5. Connect the PUMPDOWN signal, if
used. The board will close the valve
whenever a closure or dry contact across
these terminals is present. When the sig-
nal is removed or “opened” the valve will
resume normal operation. No voltage should
be supplied to these terminals. If pump-
down is not required these terminals may not
be used.
The TCB pumpdown can be configured to
open the valve fully whenever a contact is
made across the “pumpdown” terminals.
To invoke this function, the supplied pin
jumpers on P5 (Open Valve) and P6 (Close
Valve) must be placed across both pins of
each jumper.
6. Connect the temperature sensor to the
two terminals. The leads are not polarized
but the sensor must be Sporlan supplied to
operate properly.
7. Two blank terminals are included for high
voltage isolation. These are the second and
fourth terminals up from the bottom of the
board. No connections are to be made to
these terminals. No screws are present in
the terminals.
8. Two terminals are provided for 24-120
VAC Pulse Width Modulated signal
inputs. The pulse width may be from 3
to 30 seconds in width and no adjustment
to the board is necessary. If the board is
controlled by other means these terminals
will not be used.
SET THE LOGIC
Placing a jumper on either P8 or P9 will set
the logic or direction of “close” in relation
to the temperature sensor, or the externally
generated signal. The “APPLICATION”
section shows the jumper settings for hot
gas bypass valve or evaporator control
valve applications. Selection of “OPEN ON
RISE” or “CLOSE ON RISE” is based on
sensor location, application, and controller
logic. If the valve operates opposite from the
intended manner, move the jumper from P8
to P9 or from P9 to P8. Sporlan will be glad
to provide assistance in this selection.
SET THE BOARD
When used as an interface board, setting
adjustments are made through the controller
used. When used as a standalone control-
ler, setpoint is set with the potentiometer
dial and test points. The dial label will pro-
vide coarse adjustments, a millivolt volt-
meter connected across Test Points 1 and
2 will provide a direct temperature setpoint
readout. For Example:
32 mVdc=32°F Setpoint
Table 1
VALVE STEPS P10 P11 P12
SEI .5 - 11 1596 XXX — —
SEI 50 6386 — — XXX
SEH ALL 6386 — — XXX
CDS-8* 3193 — XXX —
CDS-9, 16 & 17 6386 — — XXX
SDR-3 3193 — XXX —
SDR-4 6386 — — XXX
OTHERS 6386 — — XXX
NOTE: Only one jumper is used.
*CDS-8 is Obsolete
Table 2
INPUT STEPS P1 P2 P7
4-20 ma External L,C — —
0-10 VDC External C,R — —
TTL LOGIC External — L,C —
120 VAC PWM External — C,R —
TEMP
SENSOR External — — Top &
Bottom
NOTE: L = left R = right C = center
When board is viewed as shown in Figure 1.

Page 4 / Bulletin 100-50-1
Parker Hannin Corporation
Sporlan Division
206 Lange Drive • Washington, MO 63090 USA
phone 636 239 1111 • fax 636 239 9130
www.sporlan.com
122010 / Bulletin 100-50-1© 2010 Parker Hannin Corporation
Above are sample applications, many other applications are possible, including heat reclaim, subcooling and desuperheating. Please contact
SPORLAN DIVISION - PARKER HANNIFIN, Attn: Product Manager - Electronic Products for suggestions or questions.
TCB Controlling an Electric Evaporator Control Valve
TCB Controlling an Electric Hot Gas Bypass Valve
ORDERING INFORMATION
Evaporator
Air Sensor p/n 952669 or
Surface Sensor p/n 952662
TEV
TCB
24 Volts
CDS-8*, 9, 16 & 17
Evaporator
SDR 3 & 4
TEV
24 Volts
TCB
211/16”
31/2”
31/2”
4”
1” max.
3/16” min.
VALVE JUMPERS INSTALLED
CDS-8*
P8 - OPEN ON RISE
P11 - CDS-8
P7 - TEMP ENABLE
CDS-9, 16 & 17
P8 - OPEN ON RISE
P12 - ALL OTHERS
P7 - TEMP ENABLE
VALVE JUMPERS INSTALLED
SDR-3 & SDR-3X
P9 - CLOSE ON RISE
P11 - CDS-8
P7 - TEMP ENABLE
SDR-4
P9 - CLOSE ON RISE
P12 - ALL ON OTHERS
P7 - TEMP ENABLE
Table 3
ITEM DESCRIPTION ITEM #
TCB with Potentiometer 952664
TCB Less Potentiometer 952660
Air Sensor (-40°F to 210°F) 952669
Surface Sensor with Mounting Clip (-40°F to 210°F) 952662
SMA-12 Battery Powered Valve Actuator and Diagnostic Tool 953276
High Amp TCB to control 2 valves 952792
High Amp TCB with Potentiometer 952793
TCB quick response (EEV interface)* 952714
TCB for 24 VDC input, use standard 952687
-obsolete
*When used to control an Electric Expansion Valve (EEV), the external
controller must sense and control superheat. Failure to do so may lead to
floodback and system damage. Contact Sporlan with questions.
*CDS-8 is Obsolete
APPLICATIONS
Failure or improper selection or improper use of the products described herein or related items can cause death, personal injury and property damages.
This document and other information from Parker-Hannin Corporation, its subsidiaries and authorized distributors provide product or system options for further investigation by users having
technical expertise.
The user, through its own analysis and testing, is solely responsible for making the nal selection of the system and components and assuring that all performance, endurance, maintenance,
safety and warning requirements of the application are met. The user must analyze all aspects of the application, follow applicable industry standards, and follow the information concerning
the product in the current product catalog and in any other materials provided from Parker or its subsidiaries or authorized distributors.
To the extent that Parker or its subsidiaries or authorized distributors provide component or system options based upon data or specications provided by the user, the user is responsible for
determining that such data and specications are suitable and sufcient for all applications and reasonably foreseeable uses of the components or systems.
WARNING – USER RESPONSIBILITY
Table of contents
Other Parker Temperature Controllers manuals