POWER Blue. Steady glow indicates power supply is
OK. O󰀨 indicates no power.
IDENTIFY Blue. Blinks when identify is active.
DMX INPUT
A/B
Amber. Steady glow indicates port latched to ac-
tive DMX source. Blinking indicates no incoming
DMX signal. O󰀨 indicates Port is Disabled.
DMX OUTPUT
A/B
Green. Steady glow indicates port is transmit-
ting DMX. Blinking indicates no DMX output. O󰀨
indicates Port is Disabled.
NETWORK
LINK/ACT
Green. Flickering glow means active Ethernet
network link. O󰀨 indicates no network link.
Pathport DIN-Mount DMX/RDM Ethernet Gateway
PWPP DIN P2 Manual
03/08/22
The Pathport® DIN-mount 2-Port Gateway (PWPP DIN P2)
provides the full functionality of other Pathport gateways
in a compact, DIN-rail mountable form factor.
System integrators can now easily put fully customized
universes of DMX where they’re needed.
Ideal for use in NEMA enclosures. Fully compatible with
DIN interfaces (PWINF).
The Pathport PWPP DIN P2 features terminal strips that can
be removed from the card to facilitate easy wiring installation or
replacement. Make the following connections, WITH THE POWER
TURNED OFF.
POWER
The PWPP DIN P2 is designed to run on either Power-over-Ethernet
(PoE), or on an auxiliary power supply providing between 18 and 48
volts DC. The gateway is Class 1 PoE and will draw up to 4 Watts.
If an auxiliary supply is used, observe the correct polarity when
connecting V+ and V-. A second set of terminals are provided so
power may be daisy-chained to other cards. The earth ground
terminal must be connected to the enclosure’s chassis or electrical
ground terminal to improve EMC compliance.
DMX512
DMX connections consist of a shield and data pair. Connect DATA+
and DATA- to D1+ and D1-. Observe the same polarity convention
throughout the system. Connect the cable shield or common to the
SHLD COM terminal.
NETWORK
All network wiring should follow standard Ethernet rules and be
installed by a qualied person. As part of the installation, all wiring
should be certied under the TIA/EIA-568 standard.
OVERVIEW
CONNECTIONS
STATUS INDICATORS
NC
NC
D1+
COM
SHLD
D1-
DMX - A INPUT
DMX PORT A
NC
NC
D1+
COM
SHLD
D1-
V+
V-
GND
EARTH
V-
DMX - A OUTPUT
DMX - B INPUT
DMX - B OUTPUT
AUX POWER IN
18 - 48VDC MAX 4 W
DMX PORT B
V+
POWER NET LINK / ACT
IDENTIFY
DMX512 Inputs/Outputs (2)
LED Indicators
Female RJ45
Ethernet Connector
Power In (If PoE not in use):
18-48VDC, 4W Supply required.
Use PWPWR DIN TERM 100W
48VDC or equal.
Connect Earth ground to to
improve EMC compliance
Fastening mechanism
designed for 35 x 7.5mm
DIN rail
DIN rail release lever
Use large flat-head screwdriver
or similar tool to gently pry
lever away from DIN rail to
release
Pathport DIN-Mount DMX/RDM Ethernet Gateway
PWPP DIN P2 Manual
03/08/22
© 2022 Acuity Brands, Inc. • One Lithonia Way, Conyers GA 30012
Pathway Connectivity | #103 - 1439 17th Ave SE Calgary, AB Canada T2G 1J9
Phone: + 1 866 617 3074 www.pathwayconnect.com
INSTALLATION
• Disconnect all power before proceeding with installation.
• Securely mount DIN rail (if not already installed in an enclosure).
To mount the PWPP DIN P2, hook the upper slots on the back
of the plastic extrusion to the DIN rail and then gently but rmly
press on the bottom front corners of the extrusion to snap the
module onto the rail. DO NOT press directly on the PCB card
itself.
• If the PWPP DIN P2 is using an auxiliary power supply, connect
the power IN terminal block, after checking that polarity is being
observed. The earth ground terminal must be connected to the
enclosure’s chassis or electrical ground terminal to ensure EMC
compliance. Restore power and the card will boot up.
• Attach the network cable to the RJ45 connector. Because good
wiring practice requires building wire to terminate with a female
connector, typically a short (12”/30cm) male-to-male jumper is
used. If PoE is being used, the card will boot up. Both auxiliary
power and PoE may be connected simultaneously without
damaging the PWPP DIN P2.
• The system is now ready for testing.
• To remove the PWPP DIN P2 from the DIN rail, use a athead
screwdriver to gently pry the hooked foot on the end caps of the
device away from the DIN rail. The corner of the device should life
free; repeat at the other side and unhook the device from the rail.
A large number of parameters may be customized for the PWPP
DIN P2, including: port direction, output channel patch, input
universe number, transmit and receive protocols and DMX speed.
Network properties such as IP address and subnet mask are also
customizable by the user.
Detailed gateway configuration and overall network system
management are done using Pathscape software, which is available
for download from www.PathwayConnect.com
Please refer to the Pathscape manual for information on
conguring these additional properties.
PATHSCAPE CONFIGURATION
The PWPP DIN P2 ships as a DMX output gateway with Pathway
ssACN enabled.
The following Ethernet receive protocols are unsecured and are
NOT ENABLED by default: Pathport, Strand Shownet, ETC Net2,
E1.31 streaming ACN and Art-Net.
Before conguring and using the PWPP DIN P2, you must add it
to a Security Domain using Pathscape.
To use the other listed unsecured protocols, you must
use Pathscape and enable the device property ALLOW
UNSECURED RX (see below).
DEFAULT SETTINGS
Due to new cybersecurity laws, all Pathport devices shipped after
January 1, 2020 have security properties enabled. This means
that by default, the device is not set up to receive unsecured
network protocols such as Art-Net, E1.31 sACN, ShowNet, NET2
or Pathport Protocol.
You must add the Pathport to a Security Domain using
Pathscape before conguration and use.
Pathway ssACN (Secure sACN) is enabled by default.
To use the above unsecured protocols, open Pathscape. In
the Pathport base device properties, under the Network DMX
Receive Protocols section, click the Allow Unsecured RX
checkbox.
Once checked, you may select the network protocol(s) to receive.
For further information, please see the following sections in the
Pathscape manual: Security, Pathport Properties > Network
DMX Receive Protocols .
IMPORTANT - UNSCURED NETWORK PROTOCOLS
Pathport DIN-Mount DMX/RDM Ethernet Gateway
PWPP DIN P2 Manual
03/08/22
© 2022 Acuity Brands, Inc. • One Lithonia Way, Conyers GA 30012
Pathway Connectivity | #103 - 1439 17th Ave SE Calgary, AB Canada T2G 1J9
Phone: + 1 866 617 3074 www.pathwayconnect.com
• PoE-powered Class 1 device, 4W max power consumption
• Auxiliary input voltage, 18-48V
• 60V protection on each port
• 10Mb TCP/IP connection
• ANSI E1.11 DMX512-A R2013
• ANSI E1.20 RDM(2010) - Remote Device Management
• ANSI E1.31 sACN - Streaming ACN, Art-Net, Strand ShowNet,
Pathway ssACN
• ANSI E1.33 RDMnet - RDM over IP
• IEEE 802.3af Power-over-Ethernet
• Class 2 Low Voltage
• California Title 1.81.26, Security of Connected Devices
ELECTRICAL INFORMATION
COMPLIANCE
• 4.5”W x 4”H x 1.9”D (113mm x 103mm x 48mm)
• 0.4 lbs (0.18 kg)
• Operating Conditions: 14°F-113°F (-10°C to 45°C); 5-95% relative
humidity, non-condensing
PHYSICAL

Other pathway Gateway manuals

pathway Pathport PWPP WM P2 User manual

pathway

pathway Pathport PWPP WM P2 User manual

pathway Pathport PWPP DIN P1 User manual

pathway

pathway Pathport PWPP DIN P1 User manual

pathway pathport quattro User manual

pathway

pathway pathport quattro User manual

pathway Pathport PWPP HH P1 XLR5F User manual

pathway

pathway Pathport PWPP HH P1 XLR5F User manual

pathway Vignette PWGW Series User manual

pathway

pathway Vignette PWGW Series User manual

Popular Gateway manuals by other brands

HMS Networks Intesis INMBSDAL1280200 Installation sheet

HMS Networks

HMS Networks Intesis INMBSDAL1280200 Installation sheet

ITS Telecom CGW-D Operation manual

ITS Telecom

ITS Telecom CGW-D Operation manual

fluidra iAquaLink iQBridge RS Setup guide

fluidra

fluidra iAquaLink iQBridge RS Setup guide

Dell Edge Gateway 3003 Installation and operation manual

Dell

Dell Edge Gateway 3003 Installation and operation manual

Intel DK100 Series Getting started guide

Intel

Intel DK100 Series Getting started guide

IBM System Storage N7000 Installation and setup instructions

IBM

IBM System Storage N7000 Installation and setup instructions

Digi ConnectPort X2 Getting started guide

Digi

Digi ConnectPort X2 Getting started guide

cypress solutions CTM-ONE Installation

cypress solutions

cypress solutions CTM-ONE Installation

BinTec RS120 Reference manual

BinTec

BinTec RS120 Reference manual

Memotec NetPerformer SDM-9220 Series Hardware installation guide

Memotec

Memotec NetPerformer SDM-9220 Series Hardware installation guide

Acer GOM Series user manual

Acer

Acer GOM Series user manual

Moxa Technologies MGate MB3280 Quick installation guide

Moxa Technologies

Moxa Technologies MGate MB3280 Quick installation guide

Zte ZXHN H268A Maintenance Management Manual

Zte

Zte ZXHN H268A Maintenance Management Manual

HP StorageWorks P4000 Series user guide

HP

HP StorageWorks P4000 Series user guide

PAC 512 quick start guide

PAC

PAC 512 quick start guide

Sinapsi equobox SIN.EQRPT868XT quick start guide

Sinapsi

Sinapsi equobox SIN.EQRPT868XT quick start guide

AsiaRF AP7688-WHM user manual

AsiaRF

AsiaRF AP7688-WHM user manual

CommScope NVG558 user manual

CommScope

CommScope NVG558 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.