P350 Operation Manual
General
Pearpoint has taken care to provide information in this manual to assist in safe installation, operation, maintenance
and disposal of this equipment.
Ariskassessmentshould beperformedpriortocommencingworkasitmayhighlight additionalsafetyissuesspecific
to the application.
Installation
The P350 flexitrax, including its component parts is heavy. If available, use the wheels to assist transport. Observe
heavy-lifting safety practices when lifting any component of this system. Refer to the specifications for a description of the
system’s dimensions and weights.
If mains operated equipment is connected to the system, then the external equipment must be earthed in accordance
with the manufacturer’s instructions.
Failure to complywith this may cause the unit to become live and a LETHAL HAZARD.
Generator / Invertor Selection
Pearpoint strongly recommends the use of generator equipment with Inverter type outputs. This results in
enhanced quality of supply voltage to the P350 system over varying load conditions. To power the P350 system in
isolation (in all configurations) requires an inverter output rated at 1.2kVA, additional electrical loads connected to the
same generator will increase the overall required rating accordingly.
Generator equipment with AVR type outputs may be suitable for use if the minimum requirements of generator
loading for AVR operation are met under all operational circumstances; this is one reason why inverter output
equipment is highly recommended. The minimum load the P350 system provides can be as low as 75VA. AVR
equipment operated below its minimum loading can lead to loss of voltage regulation that could cause damage to the
P350 system. Additional high power loads (such as a water heater or air-conditioner) on an AVR generator can also
lead to voltage fluctuations that could exceed the maximum ratings of the P350 system.
Generator equipment that does not employ voltage regulation techniques outlined above (e.g. condenser or
capacitor output or synchro-converter output) must not be used with the P350 system as damage to the P350 system
from unregulated voltages is likely.
If in doubt regarding generator output selection, voltage stability or installation of the generator into a vehicle, consult
a qualified electrician and/or your generator supplier.
If using a generator, start the generator and let the generator to run for a few seconds before turning the P350
on. Please turn the P350 off before stopping the generator.
If using an invertor to power the system, a good quality full sine-wave model should be selected Quasi-sine wave
investors are not recommended for use with this product.
The flexitrax Power Supply Unit (PSU) is designed to reduce hazards from electric shock provided that proper
operating procedures are followed. The P350 flexitrax system requires connection to a protective earth. It is also
recommended to use a residual current circuit breaker (RCCB) that can protect against electric shock. RCCB devices are
known in some countries as Ground Fault Circuit Interruptors (GFCI). The RCCB needs to be suitable for a load of 13A and
a tripping sensitivity of 30mA or less.