© COPYRIGHT 2013 PECO, INC. ALL RIGHTS RESERVED. P/N 70864 3220-2318 REV 00
MENU FEATURE OPTIONS STD. DEFAULT DESCRIPTION / COMMENTS
121 Fan Speeds 1, 2, 3, 4 3 Allows selection of multiple fan speeds.
1 = Single speed Fan (G terminal)
2 = 2-speed Fan (G and A Terminals)
3 = 3-speed Fan (G,A and E Terminals)
4 = 3-speed Staged Fan
130 O/B Reversing
valve
0,1 0 When 0, output is active for cooling. When 1, output is active for heating.
0 = (O) Active with cooling
1 = (B) Active with heating
135 W1 Output
Conguration
0,1 0 Changes operation of W1 for Active to Open (NC Normally Closed) to Active to Close (NO
Normally Open).
0 = NC Operation
1 = NO Operation
150 Backlight 0,1 0 0 = Backlight temporarily on
1 = Backlight always on (low intensity, 24V only)
170 Remote Sensor 0-8 0 Select sensor if used. Contact PECO for information on the T8000 Series Indoor Remote Zone Sensor.
0 = No Remote Sensors
1 = Remote Indoor Sensor Only
2 = Not Used
3 = Not Used
4 = Not Used
5 = Not Used
6 = S3 Input with Aquastat Only
7 = S3 Input with Aquastat and S1 with Remote Indoor Sensor
8 = Not Used
240 Number of Program
Periods
2; 4 events 4 2 = 2 events per day (Selections OCC1 and UnOcc1)
4 = 4 events per day (Selections Occ1-UnOcc1-Occ2- UnOcc2)
250 Clock format 12 or 24 Hours 12 12 = 12-hour clock mode
24 = 24-hour clock mode
260 Temperature Format
(°F or °C)
0,1 1 0 = Celsius
1 = Fahrenheit
265 Single/Dual Setpoint 0,1 1 Determines if single user override setpoint is used, or if user sets heat and cool setpoints independently.
0 = Dual Setpoint (Heat and Cool)
1 = Single Override Setpoint (Single Setpoint with auto changeover algorithm)
290 Range Low 50-90 °F or
10-32°C
50°F (10°C) Choose the lowest selectable temperature setpoint value.
300 Range High 50-90 °F or
10-32°C
90°F (32°C) Choose the highest selectable temperature setpoint value.
310 Setback Low Off; 50-82°F or
11-27°C
55°F (13°C) Temperature setpoint thermostat will Heat to when in Setback mode (Off sets Heating to ~45F Setback).
0 = Off
50-82°F (11-27°C)
320 Setback High Off; 58-90°F or
11-32°C
90°F (32°C) Temperature setpoint thermostat will Cool to when in Setback mode. (Off sets Cooling to ~150F in
Setback).
0 = Off (disabled)
58-90°F (11-32°C)
330 Zone Temp Offset +/-9°F or +/-
4.5°C
0°F (18 °C) Adjusts the sensed Zone Temperature displayed, allowing calibration in the eld.
340 Keypad Lockout 0-3 0 Restricts access to certain features of device; Service Menu still available if keypad lockout is enabled.
0 = No key pad lockout (Default)
1 = Disables Schedule and System keys
2 = Disables Schedule, System, and Fan keys
3 = Disables all keys
341 Enable Pin Access 0,1 0 Applies a 3 digit access code to enter Service Menu 342
0 = Disable
1 = Enable
342 Set PIN 000-999 000 Choose a 3-digit PIN access code.
350 Fan Mode 1-3 3 1 = ON: Fan is always on, regardless of demand
2 = Auto: Fan is only on with heating or cooling demand
3 = ON or Auto: Occupant can choose either selection
360 System Mode 0-3 1 Allows ability to determine which system modes the occupant can select.
0 = OFF, Auto
1 = OFF, Heat, Cool, Auto
2 = OFF, Heat, Cool
3 = Heat, Cool, Auto