
2
General Information
Attention:
This manual contains important
information for the safe use of this
product. Read this manual completely
before using this product and refer to it
often for continued safe product use. DO
NOT THROW AWAY OR LOSE THIS
MANUAL. Keep it in a safe place so that
you may refer to it often. Reasonable care
and safe methods should be practiced.
Check local codes and requirements
before installation.
Unpacking Pump:
Remove pump from carton. When
unpacking unit, check for concealed
damage. Claims for damage must be
made at the receiving end through the
delivery carrier. Damage cannot be
processed from the factory.
WARNING: Before handling these
pumps and controls, always disconnect
the power first. Do not smoke or use
sparkable electrical devices or flames
in a septic (gaseous) or possible septic
sump.
CALIFORNIA PROPOSITION 65
WARNING:
This product and
related accessories contain chemicals
known to the State of California to
cause cancer, birth defects or other
reproductive harm.
Pumps Not Operating or in Storage:
Pumps with carbon ceramic seals
must have impellers manually rotated
(6 revolutions) after setting non-
operational for 3 months or longer and
prior to electrical start-up.
Pumps with tungsten carbide seals
must have impellers manually rotated
(6 revolutions) after setting non-
operational for 3 weeks or longer and
prior to electrical start-up.
Seal Failure:
An electrode is installed in the seal
chamber so if any water enters the chamber
through the first seal the electrode will be
energized and a signal will be transmitted
to the sensing unit at ground surface
causing a red light to turn on. The electrode
probe is installed in all units, but the
sensing unit is supplied at extra cost and
must be ordered.
In operation the seal failure unit indicates
only that there is some water in the seal
chamber. The pump will continue to
operate but the seal should be checked
immediately after failure is indicated.
The sensing unit is recommended on all
installations as good insurance against
motor failure.
Pump:
The S4MN submersible pump is supplied
for 1 and 3 phase and for 200, 230, 460
or 575 volts. Power cable is supplied
with the green wire for ground. Be sure
green wire is connected to a good ground
such as water pipe or ground stake.
Heat Sensors:
All motors have heat sensor units
embedded in the motor winding to detect
excessive heat. The heat sensors are set to
trip at 120°C on the S4MN. The sensors
automatically reset when motor cools to
safe temperature.
The sensors are connected in series with
the motor starter coil so that the starter is
tripped if heat sensor opens. The motor
starter is equipped with overload heaters
so all normal overloads are protected by
the starter.
IMPORTANT: If Hydromatic®
electrical starting equipment is not
supplied, the heat sensor circuit must
be connected in series with the starter
coil or warranty is void.
Sump Level Control:
Sump level is controlled by Hydromatic
switch controls. The float is held in
position in the sump by a weight attached
to the power cord above the float. The
cord supports the float and is adjusted for
height from the surface.
Duplex systems use three controls:
one set at turn-off, one set at turn-on
for one pump, and one set for turn-on for
two pumps. Pumps alternate operation
on each successive cycle.
Two pumps operate together only if sump
level rises to the third or override control.
The override control also brings on
the second pump in case of failure of
the first pump. Extra floats with
appropriate controls can be supplied for
alarm functions. Triplex systems use four
controls: one set at turn-off, one set at
turn-on for one pump, one set at turn-on
for two pumps, and one set at turn-on
for three pumps. Pumps alternate each
successive cycle.
Three pumps operate together only if
sump level rises to the fourth control
(second override). This control also
brings on the third pump in case of
failure of either or both of the first
two pumps.
Alarm Controls:
The alarm level is usually set above the
override level so the alarm will signal
only if the override level is exceeded.
However, some engineers prefer to have
the alarm level set below the override
level as it is possible for one pump
to fail and the other pump to operate
on the override level with the sump
level never reaching the alarm level.
This is particularly true in cases of low
inflow capacity.
Electrical Control Panel:
It is recommended that the Hydromatic
control panel be used with all pumps as
proper starter heaters and connections for
heat sensor wires are furnished.
Hydromatic electrical equipment is
installed in a weatherproof NEMA 3R
enclosure. The electrical equipment
includes a main circuit breaker for each
pump, a magnetic starter with overload
protection for each pump, an H-O-A
switch and run light for each pump, and
an electric alternator and a transformer
to provide appropriate control for control
circuit and alarms.
Overload Heaters:
Starters with 3 leg overload
protection must be supplied if the
Hydromatic electrical panel is not
used. The heaters must be sized in
accordance with the nameplate amps
on the motor. The amp draw on these
submersible motors is slightly higher
than a corresponding horsepower surface
motor, so heaters must be sized by the
nameplate rating.