Peter electronic VersiStart i II Training manual

Commissioning Instructions
VersiStart i II
Quality is our Drive.
Qualität ist unser Antrieb.
Peter Electronic GmbH & Co. KG Bruckäcker 9 D-92348 Berg www.peter-electronic.com
Phone: +49(0)9189/4147-0 Fax: +49(0)9189/4147-47 07/2018
Contents
1. Caution Statements .............................................................................................................................2
1.1 Avertissements à l'attention des clients canadiens.................................................................................2
2. Declaration of conformity....................................................................................................................3
3. Mechanical Installation........................................................................................................................4
3.1 Dimensions and Weights........................................................................................................................4
3.2 Physical Installation................................................................................................................................4
4. Electrical Installation...........................................................................................................................5
4.1 Power Terminations................................................................................................................................5
4.2 Control Voltages.....................................................................................................................................5
4.3 Control Circuits.......................................................................................................................................6
4.4 Outputs...................................................................................................................................................7
4.5 Electrical Schematics .............................................................................................................................7
5. Adjustments .........................................................................................................................................8
6. Troubleshooting.................................................................................................................................10
6.1 LEDs.....................................................................................................................................................10
6.2 Trip Codes............................................................................................................................................10
6.3 Protections............................................................................................................................................10
6.4 Reset....................................................................................................................................................11
7. Accessories........................................................................................................................................12
7.1 Finger Guard Kit...................................................................................................................................12
7.2 Remote Operator..................................................................................................................................12
7.3 Communication Modules......................................................................................................................12
7.4 PC Software.........................................................................................................................................12
8. Specifications.....................................................................................................................................13
8.1 General Technical Data........................................................................................................................13
8.2 Model Code..........................................................................................................................................15
8.3 Current Ratings....................................................................................................................................15
8.4 Semiconductor Fuses...........................................................................................................................16
8.5 Disposal Instructions ............................................................................................................................16

2 VersiStart i II
1. Caution Statements
Caution Statements cannot cover every potential cause of equipment damage but can highlight common
causes of damage. It is the installer's responsibility to read and understand all instructions in this manual prior
to installing, operating or maintaining the equipment, to follow good electrical practice including applying
appropriate personal protective equipment and to seek advice before operating this equipment in a manner
other than as described in this manual.
•Isolate the VersiStart i II completely from the power supply before attempting any work on the
VersiStart i II or motor.
•Cables to the control inputs must be segregated from mains voltage and motor cabling.
•Some electronic contactor coils are not suitable for direct switching with PCB mount relays. Consult
the contactor manufacturer/supplier to confirm suitability.
•Do not apply incorrect voltages to the control input terminals.
•Power factor correction capacitors must be connected to the supply side of the soft starter. Connecting
static power factor correction to the output side will damage the soft starter.
The examples and diagrams in this manual are included solely for illustrative purposes. The information
contained in this manual is subject to change at any time and without prior notice. In no event will responsibility
or liability be accepted for direct, indirect or consequential damages resulting from the use or application of this
equipment.
WARNING - ELECTRICAL SHOCK HAZARD
The VersiStart i II contains dangerous voltages when connected to mains voltage. Only a qualified
electrician should carry out the electrical installation. Improper installation of the motor or the
VersiStart i II may cause equipment failure, serious injury or death. Follow this manual and local
electrical safety codes.
GROUNDING AND BRANCH CIRCUIT PROTECTION
It is the responsibility of the user or person installing the VersiStart i II to provide proper grounding and
branch circuit protection according to local electrical safety codes.
SHORT CIRCUIT
The VersiStart i II is not short circuit proof. After severe overload or short circuit, the operation of the
VersiStart i II should be fully tested by an authorised service agent.
1.1 Avertissements à l'attention des clients canadiens
AVERTISSEMENT
L'icône AVERTISSEMENT ci-contre signale les informations concernant des risques pouvant
entraîner des blessures graves, voire mortelles. Pour votre sécurité, veuillez consulter les
avertissements sur cette page ou demander une copie du présent manuel en français auprès de votre
distributeur local.
AVERTISSEMENT
Isoler complètement le VersiStart i II de l'alimentation secteur avant de tenter toute intervention sur le
VersiStart i II ou sur le moteur. Les bornes de commande peuvent être au potentiel de la tension de
phase.
AVERTISSEMENT - DANGER D'ÉLECTROCUTION
Le VersiStart i II contient des tensions dangereuses lorsqu'il est raccordé à l'alimentation secteur.
Seul un électricien compétent peut effectuer l'installation électrique. Une mauvaise installation du
moteur ou du VersiStart i II peut déclencher une panne d'équipement, provoquer de graves blessures
ou même la mort. Suivre les instructions de ce manuel et des codes locaux concernant la sécurité
électrique.
AVERTISSEMENT
Toujours appliquer la tension de commande avant (ou en même temps que) la tension secteur.

VersiStart i II 3
2. Declaration of conformity
In industrial linguistic usage the drive controllers of the type series VersiStart i II are called "devices", however,
in the sense of the "law on the safety of equipment", the "EMC-law" or the "EC-machinery directive" they are not
devices or machines ready for use or connection but they are components. It is only possible to define their final
function, when these components are integrated into the design and construction of the user.
To be able to use the devices to their intended purpose, it requires power supply networks according to
DIN EN 50160 (IEC 60038).
The user takes the responsibility that the user's design and construction comply with the applicable legal
provisions.
The commissioning is strictly forbidden as long as the conformity of the final system with the guidelines
2006/42/EC (Machinery directive) and 2014/35/EU (Low voltage directive) is not proved.
The devices of the VersiStart i II series are electrical equipment that is used in industrial electrical power
installations. They are designed for application in machines, in order to reduce the starting torque and starting
current peaks as well as the tripping torque of drives with three-phase induction motors. With due regard to the
installation guidelines they meet the following requirements:
Emitted interference: Continuous duty EN 61000-6-3:2005
Acceleration, decel. EN 60947-4-2
Immunity to interference: EN 61000-6-2:2005
VersiStart i II has been designed to meet the standards specified in EN 60947-4-2: Low voltage switchgear –
Part 4-2 Contactors and motor-starters – AC Semiconductor motor controllers and starters, for low voltage
safety, operation and EMC.
This product has been designed as Class A equipment. Use of this product in domestic environments may
cause radio interference, in which case the user may be required to employ additional mitigation methods.
Dr. Thomas Stiller
Managing director

4 VersiStart i II
3. Mechanical Installation
3.1 Dimensions and Weights
08240.E
B
D
C
AE
H H
G
F
Width
mm (inch)
Height
mm (inch)
Depth
mm
(inch)
mm
(inch)
mm
(inch)
mm
(inch)
Weight
kg
(lb)
Model
A
B
C
D
E
F
G
H
VS i II 018
VS i II 034
VS i II 042
98
82
201
188
165
55
90.5
23
2.2
VS i II 048
(3.85)
(3.22)
(7.91)
(7.40)
(6.49)
(2.16)
(3.6)
(0.9)
(4.85)
VS i II 060
VS i II 075
VS i II 085
145
124
215
196
193
-
110.5
37
4.0
VS i II 100
(5.70)
(4.88)
(8.46)
(7.71)
(7.59)
(4.4)
(1.5)
(8.81)
VS i II 140
VS i II 170
200
160
240
216
214
-
114.5
51
6.5
VS i II 200
(7.87)
(6.30)
(9.44)
(8.50)
(8.43)
(4.5)
(2.0)
(14.33)
3.2 Physical Installation
12
3
4
08241.D
VS i II 018 ~ VS i II 100: Allow 100 mm (3.9 inch) between soft starters.
VS i II 140 ~ VS i II 200: Allow 200 mm (7.9 inch) between soft starters.
VS i II 018 ~ VS i II 100: Allow 50 mm (2.0 inch) between the soft starter and solid surfaces.
VS i II 140 ~ VS i II 200: Allow 200 mm (7.9 inch) between the soft starter and solid surfaces.
Soft starters may be mounted side by side with no clearance (that is, if mounted without
communications modules).
The soft starter may be mounted on its side. Derate the soft starter's rated current by 15%.

VersiStart i II 5
4. Electrical Installation
4.1 Power Terminations
L1/1, L2/3, L3/5, T1/2, T2/4, T3/6
mm2(AWG)
A1, A2, A3, 01, 02,
B4, B5, 13, 14, 23, 24
mm
2
(AWG)
018 - 060
075 - 100
140 - 200
018 - 200
10427.A
10 - 35
(8 - 2)
1
0428.A
14 mm
(0.55
inch)
25 - 50
(4 - 1/10)
10428.A
14 mm
(0.55
inch)
n/a
26
(1.02)
11
(0.43)
Ø 8.5
(0.33)
10429.A
mm (inch)
0.14 - 1.5
(26 - 16)
10428.A
6 mm
(0.24
inch)
Torx (T20)
3 Nm
2.2 ft-lb
Torx (T20)
4 Nm
2.9 ft-lb
n/a
n/a
7 mm
3 Nm
2.2 ft-lb
7 mm
4 Nm
2.9 ft-lb
n/a
3.5 mm
0.5 Nm max
4.4 in-lb max
4.2 Control Voltages
VersiStart i II soft starters can be supplied in either of two control voltage configurations:
VS i II xxx xxx C1 .... 110-240 VAC (+ 10% / - 15%) or 380-440 VAC (+ 10% / - 15%)
VS i II xxx xxx C2 .... 24 VAC/VDC (± 20%)
WARNING
Always apply control voltage before (or with) mains voltage.
CAUTION
With 24 VAC/VDC use contacts rated for low voltage and low current (gold flash or similar).

6 VersiStart i II
4.3 Control Circuits
WARNING
Isolate the VersiStart i II completely from the power supply before attempting any work on the
VersiStart i II or motor. Control terminals may be at phase voltage potential.
CAUTION
For VS i II xxxxxxC2 (24 VAC/VDC control voltage) units you can connect an external 24 VDC supply
into the control input terminals 01, 02.
Two-wire control
Three-wire control
110-240 VAC
&
24 VAC/VDC
A3
A1 (+)
A2 (-)
01
02
A3
A1
A2
01
02
1
1
03241.D
A3
A1 (+)
A2 (-)
01
02
A3
A1
A2
01
02
2
3
2
3
03242.E
380-440 VAC
Start/stop. To reset a trip, open then close 02.
Start.
Stop. To reset a trip, open then close 02.
4.3.1 Motor Thermistor
Motor thermistors can be connected directly to the VersiStart i II terminals B4, B5. If motor thermistors are not
used, there must be a link between B4, B5 (the VersiStart i II is supplied with a link fitted).
B4
B5
B4
B5
B4
B5
03247.A
OK OK

VersiStart i II 7
4.4 Outputs
4.4.1 Main Contactor Output
The Main Contactor output (terminals 13, 14) closes as soon as the soft starter receives a start command and
remains closed while the soft starter is controlling the motor (until the motor starts a coast to stop, or until the
end of a soft stop). The Main Contactor output will also open if the soft starter trips.
The Main Contactor output can be used to directly control a main contactor coil.
4.4.2 Programmable Output
The programmable output relay (terminals 23, 24) can be used to signal either trip or run status. This relay is
normally open.
Trip:
The relay closes when the VersiStart i II trips. The relay can be used to operate the shunt-trip mechanism of
an upstream circuit breaker (in order to isolate the motor branch circuit), or to signal the trip to an automation
system or externally. The relay will open when the trip is reset.
Run:
The relay operates when the soft start is complete, the bypass relays are closed and full voltage is being
applied to the motor. The relay can be used to operate a contactor for power factor correction capacitors, or to
signal soft starter run status to an automation system.
4.5 Electrical Schematics
Soft starter installed with a system protection
circuit breaker complete with a shunt trip device
Soft starter installed with a system protection circuit breaker
and main contactor
6/T3
4/T2
2/T1
5/L3
3/L2
1/L1
13
14
M
23
24
K1
6/T3
4/T2
2/T1
5/L3
3/L2
1/L1
13
14
M
K1
K1
23
24
M
Motor (three phase)
K1
Main contactor
13, 14
Main contactor output
23, 24
Programmable output (set to Trip)

8 VersiStart i II
5. Adjustments
08242.B
1
2
3
78
6
5
4
Current Ramp
Current Limit
Motor Trip Class
Motor FLC
Soft Stop Time
Excess Start Time
Auxiliary Relay Function
Phase Sequence Protection
Current Ramp
08244.A
Select the initial start current (A) and ramp time (B).
Current ramp starting extends the time soft starter
takes to reach the current limit and is suitable for
generator set supplies, loads requiring an extended
start time or applications with extreme load
variation between starts.
The ramp time does not control the time the motor
will take to reach full speed.
Current
Time
Current Limit
08245. A
Select the current limit (C).
The current limit is the maximum level of current
the soft starter will deliver to the motor during the
soft start.
Current
Time
Motor Trip Class
08246.A
Select the trip class for motor overload protection.
The trip class reflects the maximum time (in
seconds) that the motor can run at locked rotor
current. The Motor Trip Class setting assumes a
locked rotor current of 600%.
Setting the motor trip class to "Off" disables motor
overload protection.
Motor FLC
08247.A
Configure the soft starter to match the motor's full
load current (FLC).
Configure according to the motor's nameplate
current. Divide the motor's FLC by the soft starter's
maximum current rating (on the soft starter's
nameplate label).
08239.A
INPUTRATING: 200-440VAC, 50/60Hz,3PH
OUTPUTFLC: xxAAC53b4-6:354,30 kW@400V
AUXILIARYCONTACTS: 5A@250VAC/360VA,5A @30VDCResistive
WITHSTANDCURRENT: 5000ARMS,600VACmax.
POWERCONTACTS: #10-#2AWG,6 -35mm2(3-5Nm,2.2-3.7lb-ft)
AUXILIARYCONTACTS: 20-16AWG,0.75 - 1.5 mm2(0.5 Nm, 4.5 lb-in)
Motor FLC
Soft starter FLC

VersiStart i II 9
Soft Stop Time
08248.A
Select the soft stop ramp time (D).
Soft stop extends the time soft starter takes to
reduce voltage to zero.
The ramp time does not control the time the motor
will take to stop completely.
Voltage
Time
Excess Start Time
08249.A
Configure the soft starter's excess start time
protection.
Select a time slightly longer than the motor requires
for a normal healthy start. The soft starter will trip if
the start does not complete within the selected time
(E).
Current
Time
Auxiliary Relay Function
08250. A
Select the function of the soft starter's
programmable output (terminals 23, 24).
When set to "Run", the relay will operate when the
soft start is complete. When set to "Trip", the relay
will operate when the soft starter trips.
Time
Phase Sequence Protection
08251. A
Configure the soft starter's phase sequence
protection.
Select the allowable phase sequences. A setting
of "Fwd" allows forward sequence (positive
rotation) only and a setting of "Any" defeats the
protection.
NOTE
Auxiliary relay function and phase sequence are configured using a shared switch. Set the auxiliary
relay function as required, then set phase sequence protection.

10 VersiStart i II
6. Troubleshooting
6.1 LEDs
14243.A
Ready
Run
Ready
Run
Reset
350 %
90%
80 %70%
60%
400 %300 %
50% 100%
16s
8s 12s
10s
No
S of t Sto p
450%250%
6s
4s
2s
14s
20s
16
8 12
10
OF F
6
4
2
14
20
16
8 12
10
OFF T RI P RUN
FWD FW D
AN Y A N Y
6
4
2
5s
2s 1 5s
5s
OF F
15s
5s
2s
2s
15s
4
2
14
20
LED Status
Ready
Run
Off
No control power
Motor not running
On
Ready
Motor running at full speed
Flash
Starter tripped
Motor starting or stopping
6.2 Trip Codes
The Ready LED will flash a different number of times to indicate the cause of the trip.
Ready LED
Description
x 1
Power Circuit: Check mains supply (L1, L2, L3), motor circuit (T1, T2, T3), soft starter SCRs and
bypass relays.
x 2
Excess Start Time: Check load, increase Current Limit or adjust Excess Start Time setting.
x 3
Motor Overload: Allow motor to cool, reset soft starter and restart.
The soft starter cannot be reset until the motor has cooled.
x 4
Motor Thermistor: Check motor ventilation and thermistor connection B4, B5. Allow motor to
cool.
x 5
Current imbalance: Check for mains supply or line current imbalance (L1, L2, L3).
x 6
Supply Frequency: Check mains voltage is available and supply frequency is in range.
x 7
Phase sequence: Check for correct phase sequence.
x 8
Network Communication Failure (between module and network): Check network connections,
settings and configuration.
x 9
Starter Communication Failure (between starter and module): Remove and refit accessory
module.
x 10
Bypass Overload: Starter rating may be too low for the application.
6.3 Protections
The VersiStart i II includes the following types of protection for the motor and starter:
6.3.1 Excess Start Time Protection
The VersiStart i II will trip on excess start time if the motor does not successfully start within the time selected in
the Excess Start Time setting. This may indicate that the load has stalled.
If the soft starter frequently trips on excess start time:
•check that the Current Limit setting is high enough for the application
•check that the Excess Start Time setting is long enough for the application
•check that the load has not stalled or increased since the soft starter was installed

VersiStart i II 11
6.3.2 Motor Overload Protection
The VersiStart i II will trip on motor overload if it calculates that the motor has been running above its operating
range for longer than the time selected in the Motor Trip Class setting. Motor Trip Class should be set to
match the motor's locked rotor time. If this information is not available from the motor datasheet, use the
default setting (Motor Trip Class = 10). Using a higher setting can damage the motor.
NOTE
Motor overload protection does not protect the soft starter, and does not protect the motor from short
circuit.
6.3.3 Current Imbalance Protection
The VersiStart i II will trip on current imbalance if the highest and lowest currents on the three phases vary by
an average of 30% for more than 3 seconds. Current imbalance protection is not adjustable, and is only active
when the average motor current is 50% or more of the programmed motor FLC.
If the soft starter frequently trips on current imbalance:
•check that there is no imbalance on the mains voltage (on the input side of the soft starter)
•insulation test the motor
•move all input cables over one position (move L1 cable to L2, move L2 cable to L3, move L3 cable to
L1) to rule out a cabling fault
6.3.4 Supply Frequency Protection
The soft starter will trip on supply frequency if the frequency rises above 72 Hz or falls below 40 Hz for more
than five seconds while the soft starter is running. These trip points are not adjustable.
In pre-start, starting and stopping modes the high and low frequency limits both apply with no time delay.
A supply frequency trip will also occur if:
•all three input phases are lost while the soft starter is running
•all three input phases fall below 120 VAC at start or while the soft starter is running
•the line contactor opens while running
6.3.5 Bypass Overload Protection
Bypass overload protection protects the soft starter from severe operating overloads while running. The
protection is not adjustable and has two components:
•The soft starter will trip if it detects overcurrent at 600%of the programmed motor full load current.
•The soft starter models the temperature of the internal bypass relays and will trip if the temperature
exceeds the safe operating level.
If the trip occurs frequently, this indicates that the soft starter has not been selected correctly for the application.
6.4 Reset
Trips can be cleared by pressing the Reset button on the soft starter, sending a Reset command from the serial
communications network, or by switching the control inputs.
To clear a trip via the control inputs, the soft starter requires a closed to open transition on the stop input (02).
•In three-wire control, use the external stop button to momentarily open the stop input (open A1-02).
•In two-wire control, if the soft starter tripped with a start signal present, remove the start signal (open
A1 to 01, 02).
•In two wire control, if the VersiStart i II tripped with no start signal present (eg VersiStart i II motor
thermistor trip), apply then remove the start signal (close then reopen A1 to 01, 02).
The Reset button is located on the front of the unit, above the adjustment switches.
The soft starter will trip again immediately if the cause of the trip still exists.

12 VersiStart i II
7. Accessories
7.1 Finger Guard Kit
Finger guards may be specified for personnel safety. Finger guards fit over the soft starter terminals to prevent
accidental contact with live terminals. Finger guards provide IP20 protection when used with cable of
diameter 22 mm or greater.
7.2 Remote Operator
The Remote Operator can control and monitor the soft starter's performance. Functionality includes:
•Operational control (Start, Stop, Reset, Quick Stop)
•Starter status monitoring (Ready, Starting, Running, Stopping, Tripped)
•Performance monitoring (motor current, motor temperature)
•Trip code display
•4-20 mA analog output (Motor Current)
7.3 Communication Modules
VersiStart i II soft starters support network communication via easy-to-install communications modules. Each
soft starter can support one communications module at a time.
Available protocols:
Ethernet (Profinet, Modbus TCP, Ethernet/IP), Profibus, DeviceNet, Modbus RTU, and USB.
NOTE
Ethernet communication modules are not suitable for use with VersiStart i II starters using 380/440
VAC control voltage.
7.4 PC Software
WinMaster can be used with Peter Electronic soft starters to provide the following functionality for networks of
up to 99 soft starters:
•Operational control (Start, Stop, Reset, Quick Stop)
•Starter status monitoring (Ready, Starting, Running, Stopping, Tripped)
•Performance monitoring (motor current, motor temperature)
To use WinMaster with the VersiStart i II, the soft starter must be fitted with a USB Module, Modbus Module or
a Remote Operator.

VersiStart i II 13
8. Specifications
8.1 General Technical Data
Mains Supply
Mains voltage (L1, L2, L3)
440 ........................................................................................... 3 x 200 VAC ~ 440 VAC (+ 10% / - 15%)
575 ........................................................................................... 3 x 200 VAC ~ 575 VAC (+ 10% / - 15%)
Mains frequency (at start) ......................................................................................................... 45 Hz to 66 Hz
Rated insulation voltage ...................................................................................................................... 600 VAC
Form designation............................................................................Bypassed semiconductor motor starter form 1
Control Voltage (A1, A2, A3)
VS i II xxx xxx C1 ............................................................................................... 110-240 VAC (+ 10% / - 15%)
..................................................................................................................or 380-440 VAC (+ 10% / - 15%)
VS i II xxx xxx C2 ........................................................................................................... 24 VAC/VDC (± 20%)
Current consumption (during run) ...................................................................................................... < 100 mA
Current consumption (inrush)
VS i II xxx xxx C1 ..............................................................................................................................10 A
VS i II xxx xxx C2 .............................................................................................................................. 2 A
Inputs
Start (terminal 01) ...................................................................................................................... Normally open
...................................................................................... 150 kΩ@ 300 VAC and 5.6 kΩ@ 24 VAC/VDC
Stop (terminal 02) .................................................................................................................... Normally closed
...................................................................................... 150 kΩ@ 300 VAC and 5.6 kΩ@ 24 VAC/VDC
Outputs
Main contactor relay (terminals 13, 14) ....................................................................................... Normally open
......................................................................................................... 6 A, 30 VDC / 6 A, 250 VAC resistive
Programmable relay (terminals 23, 24) ........................................................................................ Normally open
......................................................................................................... 6 A, 30 VDC / 6 A, 250 VAC resistive
Environmental
Degree of Protection VS i II 018 to VS i II 100 ........................................................................................... IP20
Degree of Protection VS i II 140 to VS i II 200 ........................................................................................... IP00
Operating temperature ......................................................................................................... - 10 °C to + 60 °C
Storage temperature ....................................................... -25 °C to + 60 °C (to +70 °C for less than 24 hours)
Humidity .............................................................................................................. 5% to 95% Relative Humidity
Pollution degree ................................................................................................................... Pollution Degree 3
Vibration ............................................................................................................. IEC 60068 Test Fc Sinusoidal
..................................................................................................... 4 Hz to 13.2 Hz: ± 1 mm displacement
........................................................................................................................ 13.2 Hz to 200 Hz: ± 0.7 g
EMC Emission
Equipment class (EMC) ........................................................................................................................ Class B
Conducted radio frequency emission .................................................... 0.15 MHz to 0.5 MHz: < 56-46 dB (µV)
.............................................................................................................. 0.5 MHz to 5 MHz: < 46 dB (µV)
............................................................................................................... 5 MHz to 30 MHz: < 50 dB (µV)
Radiated radio frequency emission .......................................................... 30 MHz to 230 MHz: < 30 dB (µV/m)
................................................................................................... 230 MHz to 1000 MHz: < 37 dB (µV/m)

14 VersiStart i II
EMC Immunity
Electrostatic discharge ................................................................... 4 kV contact discharge, 8 kV air discharge
Radio frequency electromagnetic field .................................................... 0.15 MHz to 1000 MHz: 140 dB (µV)
Rated impulse withstand voltage (Fast transients 5/50 ns) .......................... 2 kV line to earth, 1 kV line to line
Voltage dip and short time interruption ........................................................... 100 ms (at 40% nominal voltage)
Harmonics and distortion .................................................................... IEC61000-2-4 (Class 3), EN/IEC61800-3
Short Circuit
Rated short-circuit current VS i II 018 to VS i II 048 .................................................................................. 5 kA 1
Rated short-circuit current VS i II 060 to VS i II 200 ................................................................................ 10 kA 1
1These short circuit ratings are with fuses used as given in the table under Semiconductor Fuses on page 16.
Heat Dissipation
During Start ............................................................................................................................. 3 watts / ampere
During Run ................................................................................................................................ 10 watts typical
Standards Approvals
CE ............................................................................................................................................. EN 60947-4-2
Lloyds ........................................................................................................................................ IEC 60947-4-2
UL / C-UL ................................................................................................................................................. UL 508
Operational Life
VS i II 018~100 ............................................................................................................... 1,000,000 operations
VS i II 140~200 .................................................................................................................... 30,000 operations

VersiStart i II 15
8.2 Model Code
VS i II
Control voltage
C1 = 110-240 VAC & 380-440 VAC
C2 = 24 VAC/VDC
Current rating
Mains voltage
440 = 200 ~ 440 VAC
575 = 200 ~ 575 VAC
8.3 Current Ratings
AC53b 4-6:354
< 1000 metres
AC53b 4-20:340
< 1000 metres
40 °C
50 °C
40 °C
50 °C
VS i II 018
18 A
17 A
17 A
15 A
VS i II 034
34 A
32 A
30 A
28 A
VS i II 042
42 A
40 A
36 A
33 A
VS i II 048
48 A
44 A
40 A
36 A
VS i II 060
60 A
55 A
49 A
45 A
AC53b 4-6:594
< 1000 metres
AC53b 4-20 580
< 1000 metres
40 °C
50 °C
40 °C
50 °C
VS i II 075
75 A
68 A
65 A
59 A
VS i II 085
85 A
78 A
73 A
67 A
VS i II 100
100 A
100 A
96 A
87 A
VS i II 140
140 A
133 A
120 A
110 A
VS i II 170
170 A
157 A
142 A
130 A
VS i II 200
200 A
186 A
165 A
152 A

16 VersiStart i II
8.4 Semiconductor Fuses
Semiconductor fuses can be used with VersiStart i II soft starters to reduce the potential for damage to SCRs
from transient overload currents and for Type 2 coordination. VersiStart i II soft starters have been tested to
achieve Type 2 coordination with semiconductor fuses. Suitable Bussmann and Ferraz/Mersen semiconductor
fuses are detailed below.
Model SCR I2t (A2s)
Ferraz/Mersen Fuse
European/IEC Style
(North American Style)
Bussmann Fuse
Square Body (170M) Bussmann Fuse
British Style (BS88)
VS i II 018 1150
6.6URD30xxxA0063
(A070URD30xxx0063)
170M-1314 63 FE
VS i II 034 8000
6.6URD30xxxA0125
(A070URD30xxx0125)
170M-1317 160 FEE
VS i II 042 10500
6.6URD30xxxA0160
(A070URD30xxx0160)
170M-1318 160 FEE
VS i II 048 15000
6.6URD30xxxA0160
(A070URD30xxx0160)
170M-1318 180 FM
VS i II 060 18000
6.6URD30xxxA0160
(A070URD30xxx0160)
170M-1319 180 FM
VS i II 075 51200
6.6URD30xxxA0250
(A070URD30xxx0250)
170M-1321 250 FM
VS i II 085 80000
6.6URD30xxxA0315
(A070URD30xxx0315)
170M-1321 250 FM
VS i II 100 97000
6.6URD30xxxA0315
(A070URD30xxx0315)
170M-1321 250 FM
VS i II 140 168000
6.6URD31xxxA0450
(A070URD31xxx0450)
170M-1322 500 FMM
VS i II 170 245000
6.6URD31xxxA0450
(A070URD31xxx0450)
170M-3022 500 FMM
VS i II 200 320000
6.6URD31xxxA0450
(A070URD31xxx0450)
170M-3022 500 FMM
xxx = Blade Type. Contact Ferraz/Mersen for options.
8.5 Disposal Instructions
Equipment containing electrical components may not be disposed of together with
domestic waste.
It must be collected separately as electrical and electronic waste according to local
and currently valid legislation.
This manual suits for next models
11
Table of contents
Other Peter electronic Controllers manuals

Peter electronic
Peter electronic VersiStart p III Series Training manual

Peter electronic
Peter electronic VersiStart II 3L Series Training manual

Peter electronic
Peter electronic SGP 160-2,5 Training manual

Peter electronic
Peter electronic VB 230-6 L Training manual

Peter electronic
Peter electronic VS p III Series Training manual

Peter electronic
Peter electronic VersiStart i III Training manual