14 VersiStart II 3 ... 15L ..
Fusing according to allocation type „1“
As pre-fuses we recommend to use fuses of the utilization category gG.
The fuse values are to be determied by taking the conductor cross-sectional area of the wiring
into account. Depending on the rated motor current, the maximally occurring starting current
(normally up to the 5-fold rated device current) and the starting frequency, the wiring cross-
sectional area is to be determined. Table 1 shows the values for numerous applications, i.e., with
a 3-fold nominal current as mean starting current and a max. starting time of 10s. In the case of
parameter values exceeding these values, it may be necessary to adapt the fuse value accor-
dingly.
Note: Wiring cross-sectional area according to DIN VDE 0100-430,
DIN EN 57100-430.
Fusing according to allocation type „2“:
The power semiconductors are to be protected by fuses of the utilization class gR (semiconductor
protection fuses, high-speed fuses). However, since these fuses do not ensure line protection, it
is necessary to use additionally line protection fuses (utilization category gL).
To protect the semiconductors it is necessary to select gR-fuses featuring cutoff-I²t-values which
are approx. 10-15% below the I²t-value of the power semiconductor (see technical data). In this
connection, the fuse rating of the selected fuse should not be smaller than the starting current to
be expected.
Note: PETER electronic does not prescribe the use of semiconductor protection fuses.
However, for some UL- or CSA-listed devices there are exceptions which are
indicated in the relevant commissioning instructions.
Note 1 On the basis of the I²t-value of the power semiconductors, the starting time and
possibly the max. starting current, the fuse supplier is able to select a suitable
type. Due to the great variety of producers, sizes and types, PETER electronic
does not recommend any particular fuses.
Note 2 If the value of the fuse or the cutoff-I²t-value is selected too small, it may happen
that the semiconductor fuse reacts during the starting phase or during decele-
ration..
Tabelle 1
Rated device
current (techn. data)
Device type Fuse value
in the case of
allocation type 1
Starting frequencies
Starts / h
6,5A VS II 3 L .. 16A 40
12A VS II 5,5 L .. 20A 20
15A VS II 7,5 L .. 35A 30
25A VS II 11 L .. 50A 20
32A VS II 15 L .. 63A 10