PiiGAB M-Bus 900S User manual

www.piigab.com
PiiGAB Processinformation i Göteborg AB • Anders Carlssons gata 7 • S-417 55 Göteborg • Sweden
Tel: +46(0)31 559977 • Fax: +46(0)31 227071 • email: inf[email protected]e
Getting started PiiGAB M-Bus 900S

Getting started PiiGAB 900 Rev 1.01.00
© PiiGAB Processinformation i Göteborg AB Page: 2
Contents
1. DOCUMENT INFORMATION ............................................................................................ 3
1.1 VERSIONS..................................................................................................................... 3
2. REQUIREMENTS............................................................................................................... 3
2.1 OPTIONAL REQUIREMENTS............................................................................................. 3
3. INSTALLATION AND CONNECTIONS ............................................................................ 4
4. MAC-ADDRESS AND SERIAL NUMBER ........................................................................ 5
5. IP-CONFIGURATION ........................................................................................................ 5
5.1 DHCP NETWORK........................................................................................................... 5
5.2 STATIC IP ..................................................................................................................... 5
6. FIND YOUR PIIGAB M-BUS 900S ON YOUR NETWORK .............................................. 8
7. CONFIGURE THE PIIGAB M-BUS 900S.......................................................................... 9
8. PIIGAB M-BUS SETUP WIZARD –M-BUS COMMUNICATION ................................... 10
8.1 COMMUNICATION WITH THE INTERNAL METER................................................................ 11
8.2 COMMUNICATE WITH TEST AND DIAGNOSTIC ADDRESS................................................... 12
8.3 COMMUNICATE WITH THE METER’S ACTUAL PRIMARY ADDRESS ...................................... 13
8.4 IDENTIFY THE METER’S ADDRESSES IN THE PIIGAB M-BUS SETUP WIZARD.................... 14
8.5 PARTS IN THE SECONDARY ADDRESS............................................................................ 14
8.6 SECONDARY ADDRESS –IDENTIFICATION NUMBER AND WILD CARDS............................... 15
8.7 ENTIRE SECONDARY ADDRESS ..................................................................................... 15
8.8 READ M-BUS VOLTAGE AND M-BUS CURRENT............................................................... 16
9. APPENDIX ....................................................................................................................... 17
9.1 CONTACTS.................................................................................................................. 17

Getting started PiiGAB 900 Rev 1.01.00
© PiiGAB Processinformation i Göteborg AB Page: 3
1. Document Information
This document will describe how to configure the PiiGAB M-Bus 900S for M-Bus
communication with one M-Bus meter using static IP or DHCP.
If you see something that is not correct in this document, that misleads you or if you are
missing something please contact us so we can improve this document continuously. See
contact information at the end of the document.
1.1 Versions
Version
Modified by
Details
1.00.00
Stefan Eriksson
Initial version
1.00.01
Stefan Eriksson
Edited distributor contact information
1.01.00
Stefan Eriksson
Updated for PiiGAB M-Bus 900S
2. Requirements
Object
Detail
One PiiGAB M-Bus 900S
For at least 5 M-Bus loads and one client
One M-Bus meter
Supporting EN13757
One power supply
24V AC/DC
A patch cable
PiiGAB M-Bus Setup Wizard
Version 3.1.0 or later
2.1 Optional requirements
Object
Detail
A local area network (LAN)
With DHCP
One network switch

Getting started PiiGAB 900 Rev 1.01.00
© PiiGAB Processinformation i Göteborg AB Page: 4
3. Installation and connections
1. Install the PiiGAB M-Bus Setup Wizard.
2. Connect the PiiGAB M-Bus 900S gateway to your computer with the patch cable.
3. Connect the M-Bus meter to the PiiGAB M-Bus 900S.
4. Connect the PiiGAB M-Bus 900S gateway to a 24V AC or DC power supply.
5. Turn the power supply on.
6. Wait for the PiiGAB M-Bus 900S’s Pwr LED to go steady red.
M-Bus meters
Patch cable
Power supply
24V AC/DC
Network

Getting started PiiGAB 900 Rev 1.01.00
© PiiGAB Processinformation i Göteborg AB Page: 5
4. MAC-address and serial number
On the right gable of the PiiGAB M-Bus 900S you’ll find a label containing the MAC-address
and serial number of your PiiGAB M-Bus 900S. You can use this to identify your PiiGAB M-
Bus 900S with the PiiGAB M-Bus Setup Wizard.
Object
Starts with
MAC-address
E8-99-5A
Serial number
167#####
5. IP-configuration
You can either connect your PiiGAB M-Bus 900S gateway to a static or DHCP network. The
most common IP-configuration of the PiiGAB M-Bus 900S gateway is for static IP-address.
The gateway is by default set to DHCP when delivered.
5.1 DHCP network
If you have a network with DHCP you can connect your PiiGAB M-Bus 900S gateway to it
and the gateway will receive the IP-configuration automatically.
5.2 Static IP
If you don’t have a network with DHCP you must set your PiiGAB M-Bus 900S gateway to a
static IP-address.
Note: If you have an old computer you might need a network switch between your computer
and the PiiGAB M-Bus 900S gateway.
1. Set your computer to a static IP-address. For instance:
IP-address: 192.168.10.1.
Network mask: 255.255.255.0.
Gateway: 192.168.10.254.
2. Start the PiiGAB M-Bus Setup Wizard and go to the main menu.
3. Select Change gateway IP-settings.
4. Press Next to continue.

Getting started PiiGAB 900 Rev 1.01.00
© PiiGAB Processinformation i Göteborg AB Page: 6
5. Select Setup IP using network (UDP broadcast).
6. In the MAC-address field specify the PiiGAB M-Bus 900S gateway’s MAC-address.
7. Press Next to continue.
8. Select Use the following IP-address.
9. Specify the IP-configuration. The PiiGAB M-Bus 900S gateway should match your
computer’s IP-address.
10. Press Next to continue.

Getting started PiiGAB 900 Rev 1.01.00
© PiiGAB Processinformation i Göteborg AB Page: 7
11. Press Apply to set the IP-configuration.
12. Wait for the PiiGAB M-Bus 900S gateway to reboot.
Note: PiiGAB M-Bus Setup Wizard may signal that it failed to set the MAC-address. Please
ignore this warning. The IP-address should be set anyway.
13. Press Back three times to return to the main menu.

Getting started PiiGAB 900 Rev 1.01.00
© PiiGAB Processinformation i Göteborg AB Page: 8
6. Find your PiiGAB M-Bus 900S on your network
You can use the PiiGAB M-Bus Setup Wizard to find your PiiGAB M-Bus 900S on the
network. This will work for both a network with DHCP or static IP-address configuration.
1. Go to the main menu in the PiiGAB M-Bus Setup Wizard.
2. Select Find gateways on your network.
3. Press Next to continue.
4. Your PiiGAB M-Bus 900S gateway should be listed.
5. Find your PiiGAB M-Bus 900S by the MAC-address or serial number.
6. Double click on your PiiGAB M-Bus 900S gateway.
7. Select Yes when you are asked to start the PiiGAB M-Bus 900S’s web interface.
Note: If you have placed your PiiGAB M-Bus 900S gateway on a different sub network you
might not find it in the list of available gateways.

Getting started PiiGAB 900 Rev 1.01.00
© PiiGAB Processinformation i Göteborg AB Page: 9
7. Configure the PiiGAB M-Bus 900S
This section describes how the PiiGAB M-Bus 900S should be configured for M-Bus
communication using 2400 baud, UDP and port 10001 through slave port 1. All configuration
of the PiiGAB M-Bus 900S is done in the gateway’s web interface.
1. Start the PiiGAB M-Bus 900S’s web interface.
2. Specify the PiiGAB M-Bus 900S’s name and password to login.
Default login name and password are: Admin/Admin.
3. Click Configuration in the left panel.
4. Click on Master Port and configure it with these settings.
5. Press Save Settings.
6. Click on Slave port 1 and configure it with these settings.
7. Press Save settings.

Getting started PiiGAB 900 Rev 1.01.00
© PiiGAB Processinformation i Göteborg AB Page: 10
8. PiiGAB M-Bus Setup Wizard – M-Bus
communication
This section will use the PiiGAB M-Bus Setup Wizard to verify if the PiiGAB M-Bus 900S and
an M-Bus meter respond to M-Bus communication.
1. In the main menu select Test, search and configure meters.
2. Press Next to continue.
3. Select Connect using network and configure the connection as shown in the picture
below.
Note: Your PiiGAB M-Bus 900S’s IP-address may not be 192.168.10.123. The PiiGAB M-Bus
Setup Wizard only fills in the IP-address automatically as you selected in Find your PiiGAB M-
Bus 900S on your network.
4. Click Next to continue.

Getting started PiiGAB 900 Rev 1.01.00
© PiiGAB Processinformation i Göteborg AB Page: 11
8.1 Communication with the internal meter
Inside the PiiGAB M-Bus 900S there is an internal M-Bus meter which can be used to read
the PiiGAB M-Bus 900S’s serial number, M-Bus voltage and M-Bus current. This meter is
accessed by primary address 251. By using the internal meter, you can confirm that you have
a working communication with the PiiGAB M-Bus Setup Wizard and your PiiGAB M-Bus
900S.
1. Configure as the picture shown below.
2. Press the Find button to test communication with the internal M-Bus meter.
The internal meter responded and you can see the primary address and secondary
address. The identification number in the secondary address is the PiiGAB M-Bus
900S’s serial number.

Getting started PiiGAB 900 Rev 1.01.00
© PiiGAB Processinformation i Göteborg AB Page: 12
8.2 Communicate with Test and diagnostic address
There is a specific primary address which all M-Bus meters should respond to. This address
is called Test and diagnostic and has the value 254. This address is very useful if only one M-
Bus meter is connected to the M-Bus master and the meter’s actual primary address is
unknown.
1. Configure as the picture shown below.
2. Press the Find button to test communication with the M-Bus meter.
For this example the M-bus meter responded and its primary address is 11.

Getting started PiiGAB 900 Rev 1.01.00
© PiiGAB Processinformation i Göteborg AB Page: 13
8.3 Communicate with the meter’s actual primary address
Always make sure the M-Bus meter responds to the actual primary address.
1. Configure as the picture shown below.
2. Press the Find button to test communication with the M-Bus meter.
As expected the meter responded to primary address 11.

Getting started PiiGAB 900 Rev 1.01.00
© PiiGAB Processinformation i Göteborg AB Page: 14
8.4 Identify the meter’s addresses in the PiiGAB M-Bus Setup
Wizard
The PiiGAB M-Bus Setup Wizard always shows the meter’s actual primary and secondary
addresses. In the previous example the meter’s primary addresses were 11.
Address
Value
Primary
11
Secondary
60820317.25D6.40.07
8.5 Parts in the secondary address
The secondary address is based on four fields. These fields make the meter’s secondary
address entirely unique. These fields are:
Field
Value
Identification number
60820317 (BCD)
Manufacture
25D6 (Hex)
Version
40 (Hex)
Media
07 (Hex)

Getting started PiiGAB 900 Rev 1.01.00
© PiiGAB Processinformation i Göteborg AB Page: 15
8.6 Secondary address –Identification number and wild cards
As the same with primary addresses, make sure the meter responds to the actual secondary
address. For the secondary address there is often just enough to specify the identification
number.
1. Configure as the picture shown below.
2. Press the Find button and test the communication with the meter.
8.7 Entire secondary address
If the meter doesn’t respond to the identification number you can enter the entire secondary
address.
1. Configure as the picture shown below.
2. Press the Find button and test the communication with the meter.

Getting started PiiGAB 900 Rev 1.01.00
© PiiGAB Processinformation i Göteborg AB Page: 16
8.8 Read M-Bus voltage and M-Bus current
With a PiiGAB M-Bus 900S V2.0.0 or later and PiiGAB M-Bus Setup wizard V3.1.0 or later
you can read the PiiGAB M-Bus 900S’s M-Bus voltage and M-Bus current. This is very useful
if you want to make a quick control what’s the status of the PiiGAB M-Bus 900S and the M-
Bus loop.
1. Select Read meter’s telegram and configure as the picture shows.
2. Press the Read button to read the internal M-Bus meter in the PiiGAB M-Bus 900S.
From this response the PiiGAB M-Bus Setup Wizard can read the M-Bus voltage and
M-Bus current from the internal meter’s response.

Getting started PiiGAB 900 Rev 1.01.00
© PiiGAB Processinformation i Göteborg AB Page: 17
9. Appendix
9.1 Contacts
PiiGAB Processinformation
Anders Carlssons gata 7
417 55 Göteborg
Sweden
Phone + 46 31 55 99 77
www.piigab.com
Distributors
Please contact our distributors in respective countries:
Germany
Relay GmbH
Stettiner Str. 38
33106 Paderborn
Germany
Phone +49 5251 17670
www.relay.de
Norway
Autic Systems AS
Stoltenbergs gate 48
3110 Tønsberg
Norway
Phone +47 33 30 09 50
www.autic.no
Czech Republic
Papouch store s.r.o.
Strasnicka 3165/1b
102 00 PRAGUE 10
Czech Republic
Phone +420 267 314 267-8
www.papouch.com
Other manuals for M-Bus 900S
1
Table of contents
Other PiiGAB Gateway manuals