Pixsys 2000.35.010 User manual

2000.35.010
Converter / Convertitore
RTD - 4..20mA
User manual - Manuale d’uso
Read carefully the safety guidelines and programming instructions
contained in this manual before using/connecting the device.
Prima di utilizzare il dispositivo, leggere con attenzione
le informazioni di sicurezza e settaggio contenute in questo manuale.
PIXSYS s.r.l.
www.pixsys.net
[email protected] - [email protected]
online assistance: http://forum.pixsys.net
Introduction / Introduzione
Thanks for choosing a Pixsys device.
The Signal converter code 2000.35.010 converts a signal obtained from
temperature sensors PT100, PT1000 or NI100 (with a 2, 3 or 4 wires connection)
into a current signal for 4..20mA loop (2 wires).
Main features are:
• High accuracy;
• 16bit conversion;
• Programmable by RFid (NFC);
• 4K Word non-volatile memory (circular buffer) for data-logging with sampling
time selectable by the user;
• Possibility to rescale the output 4..20mA compared to temperature input
value;
• Field calibration to compensate eventual errors (Gain and Offset);
• Compact dimensions;
• The software RF Programmer (available for download on Pixsys website) and
the RF Programmer allow:
- complete configurability of the device;
- download on PC of logged data;
- visualization/printing of the temperature - time trend
Grazie per aver scelto un prodotto Pixsys.
Lo strumento 2000.35.010 Convertitore RTD 4..20mA converte un segnale
di temperatura acquisito attraverso sonde PT100, PT1000 o Ni100 con
collegamento a 2, 3 o 4 fili in un segnale normalizzato in corrente per loop
4..20 mA (tecnologia 2 fili).
Le caratteristiche dello strumento sono:
• Elevata precisione;
• Conversione della misura a 16 bit;
• Programmabilità via RFid (NFC);
• 4K Word di memoria non volatile (buffer circolare) per data-logging con
tempo di campionamento impostabile dall’utente;
• Possibilità di riscalare l’uscita 4..20mA rispetto all’ingresso in temperatura;
•
Taratura in campo per recuperare eventuali errori delle sonde (Gain e Offset);
• Ridotto ingombro;
• Tramite il software RF Programmer (scaricabile dal sito pixsys.net) e il
programmatore RF Programmer (2000.35.012), è possibile fare:
- configurabilità completa del convertitore;
- download su pc del logging registrato;
- visualizzazione e stampa della curva temperatura - tempo
1 Safety guide lines / Norme di sicurezza
Read carefully the safety guidelines and programming instructions contained in
this manual before using/connecting the device.
Only qualified personnel should be allowed to use the device and/or service it
and in accordance to technical data and environmental conditions listed in this
manual.
Do not dispose electric tools together with household waste material. In
observance European Directive 2002/96/EC on waste electrical and electronic
equipment and its implementation in accordance with national law, electric tools
that have reached the end of their life must be collected separately and returned
to an environmentally compatible recycling facility.
Prima di utilizzare il dispositivo, leggere con attenzione le istruzioni e le
misure di sicurezza contenute in questo manuale.
L’utilizzo/manutenzione è riservato a personale qualificato ed è da intendersi
esclusivamente nel rispetto dei dati tecnici e delle condizioni ambientali
dichiarate.
Non gettare le apparecchiature elettriche tra i rifiuti domestici.
Secondo la Direttiva Europea 2002/96/CE, le apparecchiature elettriche
esauste devono essere raccolte separatamente al fine di essere reimpiegate o
riciclate in modo eco-compatibile.
2 Dimensions and installation / Dimensioni e
installazione
A B
A1 B1
+Vdc
Supply
6...32Vdc
RF
Out
mA
Ø 4 5 m m 23 mm
230 0.10 .176 - Re vB
Software Rev. 1.03
230616
3 Technical Data / Dati tecnici
3.1 General data / Caratteristiche generali
1Operating range
Range funzionamento 6-32 Vdc
2Current output
Uscita in corrente
4..20 mA (2 wires)
4..20 mA (2 fili)
3Output resolution
Risoluzione in uscita 1 μA
4Over-range output
Uscita over-range f.s. + 5°C
5Under-range output
Uscita under-range f.s. - 5°C
6Failure output
Uscita guasto
selectable 21,5mA or 3,8mA
selezionabile tra 21,5mA o 3,8mA
7
Current output protection
Protezione uscita in
corrente
30 mA approx.
30 mA circa
8Rejection
Reiezione 50-60 Hz
9Max transmission error
Max errore di trasmissione
greater between 0,1% f.s. or 0,2°C
maggiore tra 0,1% f.s. o 0,2°C
10 EMI < 0,5%
11 Cable resistance
Resistenza cavi Max 20Ω
12 Temperature coefficient
Coefficiente di temperatura < 100 ppm
13 Sampling time
Tempo di campionamento 300 ms
14 Response time (10..90%)
Tempo di risposta (10..90%) circa 600 ms
15 Sealing
Grado di protezione IP 20
16 Conformity
Normative CE, EN 61000-6-4, EN 61000-6-2
3.2 Thermo-mechanic features / Caratteristiche
termomeccaniche
1Operating temperature
Temp. di funzionamento -40..+85 °C
2Humidity
Umidità
30-90% @ 40°C (non condensing / non
condensante)
3
Storage temperature
Temperatura
magazzinaggio
- 4 0. .+10 5° C
4Connections
Connessioni
Screw pins
Morsetti a vite
5Conductors section
Sezione conduttori 1 mm2
6Wires strip
Spelatura conduttori 8 mm
7Enclosure
Custodia Nylon (PA66)
8Dimensions
Dimensioni 23 mm, Ø 45 mm
4 Input / Ingressi
Pt100
Measuring range: -200..+800°C / Range di misura: -200..+800°C
Resistance range: 18,5...375,7 Ω / Range di resistenza: 18,5...375,7 Ω
Connection: 2, 3, 4 wires / Tecnica di collegamento: 2, 3, 4 fili
Ni100
Measuring range: -50..+170°C / Range di misura: -50..+170°C
Resistance range: 74,3..214,8 Ω / Range di resistenza: 74,3..214,8 Ω
Connection: 2, 3, 4 wires / Tecnica di collegamento: 2, 3, 4 fili
Pt1000
Measuring: -200..+800°C / Range di misura: -200..+800°C
Resistance range: 185,3..3758,3 Ω / Range di resistenza: 185,3..3758,3 Ω
Connection: 2 wires / Tecnica di collegamento: 2 fili
4.1 Connections / Connessioni
Cables colors according to IEC60751 / Colorazioni cavi come da IEC60751
Pt100
Ni100
Pt1000
A B
A1 B1
+Vdc
Supply
6...32Vdc
RF
Out
mA
RTD
2 WIRE
A B
A1 B1
+Vdc
Supply
6...32Vdc
RF
Out
mA
RED
RED
RTD
3 WIRE
A B
A1 B1
+Vdc
Supply
6...32Vdc
RF
Out
mA
WHITE
RTD
4 WIRE
RED
4...20mA
6...32Vdc
4...20mA
6...32Vdc
4...20mA
6...32Vdc
WHITE
WHITE
RED
RED
WHITE
Pt100
Ni100
A B
A1 B1
+Vdc
Supply
6...32Vdc
RF
Out
mA
RTD
2 WIRE
A B
A1 B1
+Vdc
Supply
6...32Vdc
RF
Out
mA
RED
RED
RTD
3 WIRE
A B
A1 B1
+Vdc
Supply
6...32Vdc
RF
Out
mA
WHITE
RTD
4 WIRE
RED
4...20mA
6...32Vdc
4...20mA
6...32Vdc
4...20mA
6...32Vdc
WHITE
WHITE
RED
RED
WHITE
Pt100
Ni100
A B
A1 B1
+Vdc
Supply
6...32Vdc
RF
Out
mA
RTD
2 WIRE
A B
A1 B1
+Vdc
Supply
6...32Vdc
RF
Out
mA
RED
RED
RTD
3 WIRE
A B
A1 B1
+Vdc
Supply
6...32Vdc
RF
Out
mA
WHITE
RTD
4 WIRE
RED
4...20mA
6...32Vdc
4...20mA
6...32Vdc
4...20mA
6...32Vdc
WHITE
WHITE
RED
RED
WHITE
5 Configuration / Configurazione
To configure this signal converter it is necessary to use a RF Programmer
(2000.35.012) and the configuration software RF Programmer, available on
download area www.pixsys.net. After connecting the RF Programmer via USB
and activating the software, it is possible in “EDIT” mode to configure the device
selecting type of sensor, measuring range, output for error signal and sampling
frequency for the registration. The keys “WRITE” and “READ” allow to write and
read data on the devices quickly and easily.
On the lower side of the display a list of all programmed devices is showed; it can
be printed to confirm that the programming has been completed successfully.
La configurazione di questo convertitore di segnale richiede l’utilizzo di
un base programmatore RF Programmer (2000.35.012) e del software di
configurazione RF Programmer scaricabile dall’area download nel sito www.
pixsys.net. Dopo aver connesso tramite porta USB l’RF Programmer e attivato
il software è possibile con la modalità “EDIT” parametrizzare il dispositivo
selezionando il tipo di sensore, range di misura, uscita per segnalazione
errore e la frequenza di campionamento per la registrazione. Con i tasti
“WRITE” e “READ” è possibile scrivere e leggere i vari dispositivi velocemente
e in modo agevole.
Nella parte bassa dello schermo appare la lista riassuntiva dei dispositivi
programmati, che può essere stampata per certificare la buona riuscita delle
operazioni.
6 Data Logger
This signal converter is provided with a datalogging function for the input signal.
Fixing the sampling time (1..3600 seconds) each time the loop 4..20mA powers the
device up, this will store the input value into a non-volatile memory. Through the
RF Programmer it is possible to download/display/print all data.
Questo convertitore di segnale è provvisto di una capacità di storicizzazione
del segnale in ingresso. Fissando il tempo di campionamento (impostabile
tra 1 e 3600 sec.) ogni volta che il loop 4..20mA alimenterà il dipositivo
questo archivia il valore in ingresso su una memoria non volatile. Tramite l’RF
Programmer è possibile scaricare tutti i dati e presentarli a video o stamparli.

Other Pixsys Media Converter manuals

Pixsys CNV510-PBUS-RTU-A User manual

Pixsys

Pixsys CNV510-PBUS-RTU-A User manual

Pixsys 2000.35.015 User manual

Pixsys

Pixsys 2000.35.015 User manual

Pixsys 2000.35.010 User manual

Pixsys

Pixsys 2000.35.010 User manual

Pixsys 2000.35.017 User manual

Pixsys

Pixsys 2000.35.017 User manual

Pixsys ECO-CNV510-PNET-RTU-A User manual

Pixsys

Pixsys ECO-CNV510-PNET-RTU-A User manual

Pixsys CNV510-PNET-RTU-A User manual

Pixsys

Pixsys CNV510-PNET-RTU-A User manual

Popular Media Converter manuals by other brands

Lika LINECOD SMA21 Series manual

Lika

Lika LINECOD SMA21 Series manual

Link SD SDI Open Caption Decoder LEI-589 Specifications

Link

Link SD SDI Open Caption Decoder LEI-589 Specifications

RKC INSTRUMENT COM-JC instruction manual

RKC INSTRUMENT

RKC INSTRUMENT COM-JC instruction manual

MRC 0001911 quick start guide

MRC

MRC 0001911 quick start guide

Lindy 42845 user manual

Lindy

Lindy 42845 user manual

RGBlink FLEXpro 8 quick start

RGBlink

RGBlink FLEXpro 8 quick start

PXM Gate 4 DMX manual

PXM

PXM Gate 4 DMX manual

Lorex ACVRC Series quick start guide

Lorex

Lorex ACVRC Series quick start guide

TR-Electronic 362 Series Assembly instructions

TR-Electronic

TR-Electronic 362 Series Assembly instructions

prophecy gofanco PRO-MSTmDP2DP user guide

prophecy

prophecy gofanco PRO-MSTmDP2DP user guide

Humandata USB-029H2 user manual

Humandata

Humandata USB-029H2 user manual

iNels DAC2-04M instruction manual

iNels

iNels DAC2-04M instruction manual

Clarke PC20 User instructions

Clarke

Clarke PC20 User instructions

GRASS VALLEY Canopus ADVC-HDM1 Additional functions

GRASS VALLEY

GRASS VALLEY Canopus ADVC-HDM1 Additional functions

Alpha Technologies CSM46 Installation & operation manual

Alpha Technologies

Alpha Technologies CSM46 Installation & operation manual

Baumer GXP8W manual

Baumer

Baumer GXP8W manual

Microscan MS-3000 user manual

Microscan

Microscan MS-3000 user manual

Optica 34600 FXBT quick start guide

Optica

Optica 34600 FXBT quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.