Polon-Alfa Ignis 1000 Installation guide

IGNIS 1000
CONVENTIONAL FIRE DETECTION AND ALARM SYSTEM
IGNIS 1240
FIRE DETECTION AND ALARM
CONTROL PANEL

CPD
EMC
LVD
1438
IGNIS 1240 fire detecti n and alarm c ntr l panel

CONTENTS
1
INTRODUCTION ........................................................................................................................................ 5
1.3.1 Electric shock protection ........................................................................................................................ 5
1.3.2 Installation and equipment safety ......................................................................................................... 5
1.3.3 Repairs and maintenance ...................................................................................................................... 5
1.3.4 Fuse replacement ................................................................................................................................... 6
2
TECHNICAL SPECIFICATIONS ..................................................................................................................... 7
3
GENERAL OPERATION PRINCIPLE ............................................................................................................. 8
4
CONTROL PANEL DESIGN .......................................................................................................................... 9
4.2.1 andling elements and indicators on front panel .................................................................................. 9
4.2.2 andling elements inside the control panel ......................................................................................... 11
5
CONTROL PANEL FUNCTIONALITY .......................................................................................................... 12
5.2.1 Current date and time setting .............................................................................................................. 13
5.2.2 Zone (detection line) testing mode disablement/re-enablement ........................................................ 13
5.2.3 Zone disablement/re-enablement ....................................................................................................... 14
5.2.4 Faults readout ...................................................................................................................................... 14
5.2.5 Disablement/re-enablement of all zones simultaneously .................................................................... 15
5.2.6 Alarm counter readout ........................................................................................................................ 15
5.3.1 Alarming lines (signalling devices) operation option setting ............................................................... 16
5.3.2 General alarm relays actuation delay programming ........................................................................... 17
5.3.3 General alarm signal transmission delay disablement/re-enablement ............................................... 17
5.3.4 Event memory reset ............................................................................................................................. 17
5.3.5 ‘Standard configuration’ loading ......................................................................................................... 18
5.3.6 Alarm variants programming .............................................................................................................. 18
5.3.7 Zone relay programming ..................................................................................................................... 21
5.5.1 Fire alarm signalling ............................................................................................................................ 22
5.5.2 Fire alarm verification by the attending personnel .............................................................................. 22
5.5.3
Automatic alarm signal verification, alarming variants .................................................................. 22

6
POWER SUPPLY ...................................................................................................................................... 26
7
INSTALLATION ........................................................................................................................................ 27
8
COMMISSIONING AND CONFIGURATION ............................................................................................... 27
9
SOFTWARE FOR EVENT MEMORY READOUT .......................................................................................... 29
10
CONTROL PANEL SPECIAL APPLICATIONS ........................................................................................... 31
11
INPUT AND OUTPUT CIRCUIT CONNECTING TERMINALS .................................................................... 31
12
MAINTENANCE ................................................................................................................................... 35
13
PACKING, STORAGE AND TRANSPORTATION ..................................................................................... 36

1 INTRODUCTION
1.1 DOCUMENTATION CONTENTS
1.2 CONTROL PANEL APPLICATION
1.3 SAFETY CONDITIONS
1.3.1 Electric sh ck pr tecti n
1.3.2 Installati n and equipment safety
1.3.3 Repairs and maintenance

1.3.4 Fuse replacement
1.4 DEFINITIONS
Detecti n line -
Fire warning device
Detecti n p int
Detecti n z ne -
M nit ring line -
Alarm line -
Output t m nit ring
Quiescent (supervisi n) m de-
Alarm (fire) m de -
Disablement m de -
Testing m de -
Fault m de -
1.5 DEVICE COMPLETENESS
Item
Descripti n
Quantity

Item
Descripti n
Remarks
2 TECHNICAL SPECIFICATIONS
−
−−
−
−
−−
−
-
-
-
-
-
-

-
-
-
-
-
-
C ntr l panel w rk time
after mains v ltage utage
C ntr l panel batteries
capacity
Maximum current c nsumpti n fr m
external devices p wer supply utput
3 GENERAL OPERATION PRINCIPLE

4 CONTROL PANEL DESIGN
4.1 OVERALL CONTROL PANEL DESCRIPTION
4.2 HANDLING AND SIGNALLING ELEMENTS, ACCESS LEVELS
The 1
st
access level
The 2
nd
access level
The 3
rd
access level
The 4
th
access level
4.2.1 Handling elements and indicat rs n fr nt panel
1…24 ZONE
1…24 ZONE
•

•
•
TRANSMISSION
FIRE
LCD display
POWER SUPPLY
DISABLEMENT
•
•
•
TESTING
FAULT
POWER SUPPLY
•
•
SYSTEM
EXTERNAL DEVICES
SIGNALLING DEVICES
EARTH FAULT
TRANSMISSION; OFF/ON
SIGNALLING DEVICES; OFF/ON
PERSONNEL; OFF/ON
ACKNOWLEDGEMENT
RESET
PERSONNEL ACCESS LEVEL

FUNCTION SW.OVER SELECTION SET
• FUNCTION
• SELECTION -
• SET
4.2.2 Handling elements inside the c ntr l panel
FUNCTION SELECTION SET↑ SET↓
RESET
Jumper N . Jumper p siti n Functi n
÷
WŁ. AKU
ZW1
ZW2

BZ1
BZ3
BZ2
MAINS SWITCH
5 CONTROL PANEL FUNCTIONALITY
5.1 LCD INDICATIONS AT 1
ST
AND 2
ND
ACCESS LEVEL SERVICING
1. Current date and time
2. C ntr l panel alarm m de
3. External signalling devices disablement/re-enablement
4. Alarm signal transmissi n disablement/re-enablement
5. Operati n m de switch ver between ‘pers nnel present’ and ‘pers nnel absent’
02-12-31 23:59
L.1 ALARM ! 0’00
SIGN.DEV. ON SIGN.DEV. OFF
TRANSMISSION ON TRANSMISSION OFF

6. Fire alarm m de reset
7. Access denied
5.2 CONTROL PANEL FUNCTIONS AT 2
ND
ACCESS LEVEL
FUNCTIONSELECTION→,SET↑
•
•
•
•
•
5.2.1 Current date and time setting
5.2.2 Z ne (detecti n line) testing m de disablement/re-enablement
PERSONNEL PRESENT PERSONNEL ABSENT
RESET
ACCESS DENIED
02-12-31 23:59

z ne number 1…16 r 24 0 – testing enabled
1 – testing disabled
TESTING ON z. 01 - 0
5.2.3 Z ne disablement/re-enablement
z ne number 1…16 r 24 0 – z ne enabled
1 – z ne disabled
ZONE ON z. 01 - 0
5.2.4 Faults read ut
FAULT READOUT

5.2.5 Disablement/re-enablement f all z nes simultane usly
X – n changes
1 – z nes enabled
0 – all z nes disabled
ZONES ON OFF - X
N te:
5.2.6 Alarm c unter read ut
0001 z2 07 – 09 - 31

5.3 CONTROL PANEL FUNCTIONS AT 3
RD
ACCESS LEVEL
•
•
•
•
•
•
5.3.1 Alarming lines (signalling devices) perati n pti n setting
0 – sign. dev. perati n acc. t 0 pti n
1 – sign. dev. perati n acc. t 1 pti n
EXT.AL.OPTION - 0
0001 z2 17 : 15 : 48

5.3.2 General alarm relays actuati n delay pr gramming
1’30 – delay time (example)
1’ – minutes (1…9)
30 – sec nds (0…59)
DELAY - 1’ 30
5.3.3 General alarm signal transmissi n delay disablement/re-enablement
z ne number 1…16 r 24 1 – delays enabled
0 – delays disabled
DELAYS ON z. 01 - 1
5.3.4 Event mem ry reset
0 – reset functi n disabled
1 – reset functi n enabled
MEMORY RESET - 0
N te:

5.3.5 ‘Standard c nfigurati n’ l ading
0 – l ading functi n disabled
1 – l ading functi n enabled
STAND. CONF. - 0
N te:
5.3.6 Alarm variants pr gramming
z ne number 1…16 r 24 1 – alarm variant number
(0, 1 r 2)
VARIANT z. 01 - 1
N te:
One-stage alarm
Tw -stage alarm
VARIANT z. 01 - 0
DELAYS ON z. 01 - 0

N te:
One-stage alarm with a preliminary reset
Tw -stage alarm with a preliminary reset
VARIANT z. 01 - 0
DELAY X’ XX’’
DELAYS ON z. 01 - 1
VARIANT z. 01 - 1
DELAYS ON z. 01 - 0
VARIANT z. 01 - 1
DELAY X’ XX’’

N te:
Tw -stage alarm with z ne-time interdependence
N te:
N te:
-
-
-
-
-
-
DELAYS ON z. 01 - 1
VARIANT z. 01 - 2
DELAY X’ XX’’
DELAYS ON z. 01 - 1
This manual suits for next models
1
Table of contents
Other Polon-Alfa Security System manuals
Popular Security System manuals by other brands

Honeywell
Honeywell X-618 installation manual

Teletek electronics
Teletek electronics CA824 installation manual

Bosch
Bosch ISC-FPB1-W60QS Installation and operation guide

Fortinet
Fortinet FortiAnalyzer-800B quick start guide

Lorex
Lorex SG6331 instruction manual

ADT
ADT ADT7AIO Series Installation and setup guide