manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Potter
  6. •
  7. Control Unit
  8. •
  9. Potter PAD100-SM User manual

Potter PAD100-SM User manual

Installation Manual: PAD100-SM Speaker Module
NOTICE TO THE INSTALLER
This manual provides an overview and the installation instructions for the PAD100-SM module. This module is only compatible with
addressable re systems that utilize the PAD Addressable Protocol.
All terminals are power limited and should be wired in accordance with the requirements of NFPA 70 (NEC) and NFPA 72 (National
Fire Alarm Code). Failure to follow the wiring diagrams in the following pages will cause the system to not operate as intended. For
further information, refer to the control panel installation instructions.
The module shall only be installed with listed control panels. Refer to the control panel installation manual for proper system
operation.
1. Description
The PAD100-SM uses one (1) SLC loop address. The module mounts on either an UL Listed 2-1/2" deep 2-gang box or 1-1/2"
deep 4" square box. The module is capable of switching one of the two audio input channels to its audio output channel.
The PAD100-SM includes one red LED to indicate the module's status. In normal condition, the LED ashes when the device is
being polled by the control panel. If the LED blink has been disabled via the programming software, in a normal condition the LED
of the device will be off.
2. Setting the Address
All PAD protocol detectors and modules require an address prior to connection to the panel's SLC loop. Each PAD device's
address (i.e., detector and/or module) is set by changing the dip switches located on the device. PAD device addresses are
comprised of a seven (7) position dip switch used to program each device with an address ranging from 1–127. For example, if
the address number assigned is "8", the rst input will be identied as "8.1", and the second input channel will be "8.2."
Figure 1. PAD Device Dip Switch Addresses Table (Addresses 1–127)
Note: Each "gray" box indicates that the dip switch is "On," and each "white" box indicates "Off."
The examples shown below illustrate a PAD device's dip switch settings: the 1st example shows a device not addressed where all
dip switch settings are in the default "Off" position, the 2nd illustrates an addressed PAD device via the dip switch settings.
Figure 2. Examples of PAD Device Showing Default Dip Switch Setting (Unaddressed) & Addressed PAD Device
Off
On
1 2 4 16
8 32 64 All dip switches are
shown in the "Off"
position. Off
On
1 2 4 16
832 64 Example shows this PAD device's
address = 42. Dip switches #2, 8 &
32 are in the "On" position.
Document 5406316-A 02/16
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: (800) 325-3936 • www.pottersignal.com
PAGE 1 OF 3
1 2 4 8 16 32 64 1 2 4 8 16 32 64 1 2 4 8 16 32 64 1 2 4 8 16 32 64 1 2 4 8 16 32 64
1 27 53 78 103
2 28 54 79 104
3 29 55 80 105
4 30 56 81 106
5 31 57 82 107
6 32 58 83 108
7 33 59 84 109
8 34 60 85 110
9 35 61 86 111
10 36 62 87 112
11 37 63 88 113
12 38 64 89 114
13 39 65 90 115
14 40 66 91 116
15 41 67 92 117
16 42 68 93 118
17 43 69 94 119
18 44 70 95 120
19 45 71 96 121
20 46 72 97 122
21 47 73 98 123
22 48 74 99 124
23 49 75 100 125
24 50 76 101 126
25 51 77 102 127
26 52 1 2 4 8 16 32 64 1 2 4 8 16 32 64 1 2 4 8 16 32 64
1 2 4 8 16 32 64 1 2 4 8 16 32 64
firealarmresources.com
INSTALLATION MANUAL: PAD100-SM SPEAKER MODULE
Document 5406316-A 02/16
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: (800) 325-3936 • www.pottersignal.com
PAGE 2 OF 3
Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to the SLC or device.
• Power to the SLC is removed.
• Field wiring on module is correctly installed.
• Field wiring has no open or short circuits.
3. Technical Specications
Operating Voltage 24.0V
Max SLC Standby Current 240 μ A
Max SLC Alarm Current 240 μ A
Output Channel Ratings 2A @ 30VDC, 0.5A @ 25VAC, 60 Watts
Input Channel Ratings 25 VRMS, 70.7 VRMS, 30 VDC, 120 VAC
EOL Resistor 5.1K Ω
Operating Temperature Range 32 to 120 F (0 to 49 C)
Operating Humidity Range 0 to 93% (non-condensing)
Max no. of Module Per Loop 127 units
Dimensions 4.17" L x 4.17" W x 1.14" D
Mounting Options UL Listed 2-1/2" deep 2-gang box or
1-1/2" deep 4" square box
Shipping Weight 0.6 lbs
4. Wiring Diagrams
The wiring diagram shown below illustrates how to wire a PAD100-SM module. Additionally, an installation diagram shows how to
install the module using a compatible electrical box.
Figure 3. Example of Installing a PAD100-SM Using a Compatible Electrical Box
Figure 4. Example of Wiring a PAD100-SM as Class B Output Channel
FROM FACP OR
PREVIOUS MODULE
TO NEXT MODULE
FROM AMPLIFIER 1
FROM AMPLIFIER 2
END-OF-LINE RESISTOR
5.1K OHM
Part #3005013
12W
PAD100-SM Class B Wiring
SP SP
SP
firealarmresources.com
INSTALLATION MANUAL: PAD100-SM SPEAKER MODULE
Document 5406316-A 02/16
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: (800) 325-3936 • www.pottersignal.com
PAGE 3 OF 3
Figure 5. Example of Wiring a PAD100-SM as Class A Output Channel
Notes:
• SLC wiring style supports the Class A, Class B and Class X.
• Output channel wiring supports Class A or Class B wiring styles.
• SLC loop wiring (SLC+, SLC-) are power limited.
• Wiring for terminals SLC+, SLC- are supervised.
• All wiring is between #12 (max.) and #22 (min.).
• Wire Preparation – Strip all wires 1/4 inch from their edges as shown here:
– Stripping too much insulation may cause a ground fault.
– Stripping too little may cause a poor connection and subsequently an open circuit.
These instructions do not purport to cover all the details or variations in the equipment described, nor provide for
every possible contingency to be met in connection with installation, operation and maintenance.
Specications subject to change without prior notication.
For Technical Assistance contact Potter Electric Signal Company at 866-956-1211.
Actual performance is based on proper application of the product by a qualied professional.
Should further information be desired or should particular problems arise, which are not covered sufciently for
the purchaser's purpose, the matter should be referred to a distributor in your region.
1/4 inch
It is possible that the internal relay in the PAD100-SM may be shipped in the non-normal / activated state. To ensure
that the internal relay is set to the normal state, connect the module to the SLC loop and reset the control panel
before terminating the wiring to the module's output.
FROM FACP OR
PREVIOUS MODULE
TO NEXT MODULE
FROM AMPLIFIER 1
FROM AMPLIFIER 2 NOTE: END-OF-LINE RESISTOR NOT REQUIRED
PAD100-SM Class A Wiring
SP SP
SP
firealarmresources.com

Other Potter Control Unit manuals

Potter Nohmi MOM-4 User manual

Potter

Potter Nohmi MOM-4 User manual

Potter PAD100-IM User manual

Potter

Potter PAD100-IM User manual

Potter PAD100-ZM User manual

Potter

Potter PAD100-ZM User manual

Potter PAD100-SIM User manual

Potter

Potter PAD100-SIM User manual

Potter PAD100-LEDK User manual

Potter

Potter PAD100-LEDK User manual

Potter PAD100-LED User manual

Potter

Potter PAD100-LED User manual

Popular Control Unit manuals by other brands

IBC control VariMax50M manual

IBC control

IBC control VariMax50M manual

evaton technologies Link user manual

evaton technologies

evaton technologies Link user manual

ICP DAS USA M-7028 quick start guide

ICP DAS USA

ICP DAS USA M-7028 quick start guide

Carrera Digital 124 Wireless+ Assembly and operating instructions

Carrera

Carrera Digital 124 Wireless+ Assembly and operating instructions

Victaulic I-769N Installation, Maintenance, and Testing Manual

Victaulic

Victaulic I-769N Installation, Maintenance, and Testing Manual

Eaton Vickers DG3V-8 Series Overhaul manual

Eaton

Eaton Vickers DG3V-8 Series Overhaul manual

elsner elektronik KNX A3-B2 Installation and adjustment

elsner elektronik

elsner elektronik KNX A3-B2 Installation and adjustment

Azbil VDC user manual

Azbil

Azbil VDC user manual

Texas Instruments DAC7731 user guide

Texas Instruments

Texas Instruments DAC7731 user guide

GEA Aseptomag AMV operating instructions

GEA

GEA Aseptomag AMV operating instructions

SMAR FY302 Operation, maintenance & instruction manual

SMAR

SMAR FY302 Operation, maintenance & instruction manual

CEBEK CD-34 quick start guide

CEBEK

CEBEK CD-34 quick start guide

NSK Ultimate XL-F Operation manual

NSK

NSK Ultimate XL-F Operation manual

Siemens SINAMICS G120 List manual

Siemens

Siemens SINAMICS G120 List manual

Quectel NB-IoT Module Series user guide

Quectel

Quectel NB-IoT Module Series user guide

Eaton DXC-EXT-LOCSIM Instruction leaflet

Eaton

Eaton DXC-EXT-LOCSIM Instruction leaflet

Siemens 3AK operating instructions

Siemens

Siemens 3AK operating instructions

RadiSys EPC-26A/27 manual

RadiSys

RadiSys EPC-26A/27 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.