Powerdist DECS125-15 Operating and safety instructions

POWERDIST AUST PTY LTD 1/14
DONE BY: CDP / JHI REV 1 DATE: 01/05/12
P
OWERDIST
AUST PTY LTD
PO Box 197
Kotara NSW 2289
Unit 3, 44 Park Ave
Adamstown NSW 2289
Tel: (+61) 02 4965 5771
Fax: (+61) 02 4965 5772
INSTRUCTIONS TO REPLACE A
DECS125-15 BY A DECS-200

POWERDIST AUST PTY LTD 2/14
DONE BY: CDP / JHI REV 1 DATE: 01/05/12
T A B L E O F C O N T E N T S
1
MECHANICAL LAYOUT.......................................................................................................................... 3
1.1
DECS125-15, DECS63-15, DECS32-15...............................................................................................................3
1.2
DECS200..............................................................................................................................................................4
- PROJECTION MOUNTING:....................................................................................................................................4
- FRONT DOOR MOUNTING (BRACKET):...............................................................................................................5
2
TERMINAL BLOCK CROSS REFERENCES.......................................................................................... 6
3
ELECTRICAL DRAWINGS ...................................................................................................................... 7
3.1
SAME FEATURES: DECS125-15 / DECS200.....................................................................................................7
- FIELD OUTPUT.......................................................................................................................................................7
- VOLTAGE SENSING ..............................................................................................................................................7
- CURRENT SENSING..............................................................................................................................................7
- BUS SENSING........................................................................................................................................................7
- SETPOINT ADJUSTMENT .....................................................................................................................................8
- REGULATION MODE SELECTION........................................................................................................................8
3.2
DIFFERENCES: DECS-125-15 / DECS-200........................................................................................................9
- POWER INPUT.......................................................................................................................................................9
- CROSS CURRENT COMPENSATION (CCC)........................................................................................................9
- ACCESSORY INPUT............................................................................................................................................10
- ALARM CONTACT OUTPUT................................................................................................................................10
3.3
DECS200 REQUIREMENTS..............................................................................................................................11
- AUXILIARY POWER SUPPLY..............................................................................................................................11
- EXCITATION ON / OFF ........................................................................................................................................11
- ALARM RESET.....................................................................................................................................................12
3.4
DECS200 NEW FEATURES ..............................................................................................................................12
- PREPOSITION (OPTIONAL) ................................................................................................................................12
- AUTO / MANU MODE (OPTIONAL)......................................................................................................................12
- COMMUNICATION PORT RS485 (OPTIONAL)...................................................................................................12
- OTHERS NEW FEATURES..................................................................................................................................13
4
PARAMETERS CONVERSION: DECS125-15 TO DECS200............................................................... 14
4.1
SETTINGS TRASNFER & P.I.D. PRESET.........................................................................................................14

POWERDIST AUST PTY LTD 3/14
DONE BY: CDP / JHI REV 1 DATE: 01/05/12
1 MECHANICAL LAYOUT
1.1 DECS125-15, DECS63-15, DECS32-15
Dimensions are indicated in inches and in millimetres in brackets.

POWERDIST AUST PTY LTD 4/14
DONE BY: CDP / JHI REV 1 DATE: 01/05/12
1.2 DECS200
- PROJECTION MOUNTING:

POWERDIST AUST PTY LTD 5/14
DONE BY: CDP / JHI REV 1 DATE: 01/05/12
- FRONT DOOR MOUNTING (BRACKET):

POWERDIST AUST PTY LTD 6/14
DONE BY: CDP / JHI REV 1 DATE: 01/05/12
2 TERMINAL BLOCK CROSS REFERENCES
TERMINAL
DECS125-15
TERMINAL
DECS200 REMARKS
POWER INPUT
-
C1 (GND)
To be connecte to the chassis groun .
A
C2 (A)
B
C3 (B)
C
C4 (C
)
FIELD OUTPUT
F+
C5 (F+)
F-
C6 (F-)
VOLTAGE
SENSING
E1
A1 (E1)
E2
A2 (E2)
E3
A3 (E3)
BUS SENSING
BUS1
A4 (B1)
BUS3
A5 (B3)
CURRENT
SENSING
CTB1
B1 (CTB 1A)
CTB1 has to be connecte on B1 or
B2 (CTB 5A)
B2 as per your roop CT secon ary.
CTB2
B3 (CTB COM)
CROSS CURRENT
COMPENSATION
B4 (CTCC 1A)
A e icate CT is recommen e for
B5 (CTCC 5A)
the CCC with the DECS200. Please refer
B6 (CTCC COM)
to chapter 3.2 for more etails.
PARALLELING
CONTROL
52L
A35
(52L/M)
52M
A36
(COM)
VAR/PF
CONTROL
52J
A37
(52J/K)
52K
A38
(COM)
EXTERNAL
ADJUST
6U
A29
(RAISE)
7
A30
(COM)
6D
A31
(LOWER)
AUX. ADJUST
(Biasing)
A8 (GND)
Accessory input can be a
A A9 (V+)
4
-
20mA
signal
if preferre
. Refer to
chapter 3.2
B
A10
(V-)
for more etails.
ALARM
ALRM-
A15
Relay 1
3 programmable output relays are
ALRM+
A16
available if require .
AUXILIARY
POWER SUPPLY
B7 BATT+
An auxiliary power supply is require
B8 BATT-
with the DECS200, refer to the
B9 L
chapter 3.3 for more etails.
B10
N
START / STOP
A21
START
A start / stop signal is require
A22
with the DECS200, refer to the
A23
STOP
chapter 3.3 for more etails.
A24

POWERDIST AUST PTY LTD 7/14
DONE BY: CDP / JHI REV 1 DATE: 01/05/12
3 ELECTRICAL DRAWINGS
3.1 SAME FEATURES: DECS125-15 / DECS200
- FIELD OUTPUT
Continuous output: 125Vdc, 15Adc. The DECS-200 output is 125V/15ADC which is suitable to replace the
power output of the DECS32-15, DECS63-15 & DECS125-15.
Forcing output (10s): 200Vdc, 30Adc.
- VOLTAGE SENSING
DECS125-15 DECS200
Voltage sensing single or 3 phases, range from 100Vac to 500Vac with 50Hz (120 to 600Vac with 60Hz).
- CURRENT SENSING
DECS125-15 DECS200
Current sensing: secondary CT 1A or 5A.
- BUS SENSING
DECS125-15 DECS200
Voltage matching single phase, range from 100Vac to 500Vac with 50Hz (120 to 600Vac with 60Hz).
This manual suits for next models
1