RED00202(R2) MANUAL
Clamping Yoke Connector Specifications
Input / Output connections Signal connection plug
Tightening torque min. – max. 1,2 – 2,2Nm (blade 1,0x5,5 DIN5264 ) 0,4 – 0,5Nm (blade 0,6x3,5 PH1 PZ1)
Touch-safe protection acc. to DIN VDE 0470 IP20 plugged/ IP10 unplugged Not applicable
Clamping range, min. – max. 0,5 – 16mm² / AWG26 – AWG6 0,2 – 4,0mm² / AWG26 – AWG12
Solid, H05(07) V-U min. – max. 0,5 – 16mm² 0,2 – 4,0mm²
Stranded, H05(07) V-U min. – max. 6 – 16mm² Not applicable
Flexible, H05(07) V-U min. – max. 0,5 – 16mm² 0,2 – 4,0mm²
w. plastic collar ferrule, DIN 46228 pt 4 min. – max. 2,5 – 10mm² 0,2 – 2,5mm²
w. wire end ferrule, DIN 46228 pt 1, min. – max. 2,5 – 10mm² 0,2 – 4,0mm²
Plug gauge in accordance with EN 60999 a x b; ø 5,4 x 5,1mm; 5,3mm 2,8 x 2,4mm; 2,5mm
Pitch (P) 10,16mm 7,50mm
Wire Stripping Length (fine wired)
Nominal Cross Section Wire End Ferrule Stripping Length Wire End Ferrule Stripping Length
0,25mm² H0,25/5 5mm H0,25/10 HBL 8mm
0,5mm² H0,5/6 6mm H0,5/12 OR 8mm
1,0mm² H1,0/6 6mm H1,0/12 GE 8mm
2,5mm² H2,5/12 12mm H2,5/19D BL 14mm
4,0mm² H4,0/12 12mm H4,0/20 GDR 14mm
6,0mm² H6,0/20 12mm H6,0/20 SW 14mm
10,0mm² H10,0/12 12mm H10,0/22 EB 15mm
The length of ferrules is to be chosen depending on the rated voltage. The outside diameter of the plastic collar should not be larger than
Electrical Safety (Factory
Type and factory test are the manufacturer. While repeating damage can
happen to the power supply unit. For the field test (owner) follow the below instruction:
a) Use suitable test equipment, raising the voltage slowly.
b) Use only test voltages of 50/60Hz. The outputs are unearthed and
therefore they have no resistance to GND/PE.
c) If the residual voltage is ≥60Vdc, observe the safety standards.
Use only specially insulated screwdriver to trim the Ua/Ia.
1) ≥60Vdc = 1500Vdc