PR electronics 5714 User manual

Programmable displays with a wide se-
lection of inputs and outputs for display of temperature,
volume and weight, etc. Feature linearisation, scaling,
and difference measurement functions for programming
via PReset software.
Interfaces for analogue and digital
signals as well as HART® signals between sensors / I/P
converters / frequency signals and control systems in Ex
zone 0, 1 & 2 and for some modules in zone 20, 21 & 22.
Galvanic isolators for analogue and digital
signals as well as HART® signals. A wide product range
with both loop-powered and universal isolators featuring
linearisation, inversion, and scaling of output signals.
PC or front programmable modules with
universal options for input, output and supply. This range
offers a number of advanced features such as process
calibration, linearisation and auto-diagnosis.
A wide selection of transmitters for DIN
form B mounting and DIN rail modules with analogue
and digital bus communication ranging from application-
specific to universal transmitters.
Displays
Temperature
Isolation
Ex interfaces
Universal
DK
UK
FR
DE
Side 1
Page 23
Page 45
Seite 67
SIGNALS THE BEST
5714
Programmable
LED Indicator
No. 5714V101-IN (1003)
From ser. no. 060137001

1
PROGRAMMERBART LED-INSTRUMENT
PREVIEW 5714
INDHOLDSFORTEGNELSE
Advarsler ............................................................................ 2
Sikkerhedsregler ................................................................. 3
Overensstemmelseserklæring ............................................ 5
Front - og bagsidelayout .................................................... 6
Anvendelse ......................................................................... 7
Teknisk karakteristik ........................................................... 7
Montage / installation ......................................................... 7
Applikationer ...................................................................... 8
Bestillingsskema ................................................................. 9
Elektriske specifikationer.................................................... 9
Følerfejlsdetektering i og uden for område ........................ 13
Tilslutninger ........................................................................ 14
Blokdiagram ....................................................................... 15
Rutediagram ....................................................................... 16
Rullende hjælpetekster ....................................................... 18
Programmering / betjening af trykknapper ........................ 20
Grafisk afbildning af relæfunktionen setpunkt ................... 21

23
SIKKERHEDSREGLER
DEFINITIONER:
Farlige spændinger er defineret som områderne: 75...1500 Volt DC og
50...1000 Volt AC.
Teknikere er kvalificerede personer, som er uddannet eller oplært til at kunne
udføre installation, betjening eller evt. fejlfinding både teknisk og sikkerheds-
mæssigt forsvarligt.
Operatører er personer, som under normal drift med produktet skal indstille og
betjene produktets trykknapper eller potentiometre, og som er gjort bekendt
med indholdet af denne manual.
MODTAGELSE OG UDPAKNING:
Udpak modulet uden at beskadige det. Kontrollér ved modtagelsen, at modul-
typen svarer til den bestilte. Indpakningen bør følge modulet, indtil dette er
monteret på blivende plads.
MILJØFORHOLD:
Undgå direkte sollys, kraftigt støv eller varme, mekaniske rystelser og stød, og
udsæt ikke modulet for regn eller kraftig fugt. Om nødvendigt skal opvarmning,
udover de opgivne grænser for omgivelsestemperatur, forhindres ved hjælp af
ventilation.
Alle moduler hører til Installationskategori II, Forureningsgrad 1 og Isolations-
klasse II.
INSTALLATION:
Modulet må kun tilsluttes af teknikere, som er bekendte med de tekniske
udtryk, advarsler og instruktioner i manualen, og som vil følge disse.
Hvis der er tvivl om modulets rette håndtering, skal der rettes henvendelse til
den lokale forhandler eller alternativt direkte til:
PR electronics A/S, Lerbakken 10, 8410 Rønde, Danmark tlf: +45 86 37 26 77.
Installation og tilslutning af modulet skal følge landets gældende regler for
installation af elektrisk materiel bl.a. med hensyn til ledningstværsnit, for-sikring
og placering.
Beskrivelse af indgang / udgang og forsyningsforbindelser findes på blokdia-
grammet og sideskiltet.
For moduler, som er permanent tilsluttet farlig spænding, gælder:
For-sikringens maximale størrelse er 10 A og skal sammen med en afbryder
placeres let tilgængeligt og tæt ved modulet. Afbryderen skal mærkes
således, at der ikke er tvivl om, at den afbryder spændingen til modulet.
SIGNATURFORKLARING
Trekant med udråbstegn: Advarsel / krav. Hændelser der kan føre til
livs truende situationer.
CE-mærket er det synlige tegn på modulets overensstemmelse med
EU -direktivernes krav.
ADVARSEL
Dette modul er beregnet for tilslutning til livsfarlige elektriske
spændinger. Hvis denne advarsel ignoreres, kan det føre til
alvorlig legemsbeskadigelse eller mekanisk ødelæggelse.
For at undgå faren for elektriske stød og brand skal manualens
sikkerhedsregler overholdes, og vejledningerne skal følges.
Specifikationerne må ikke overskrides, og modulet må kun
benyttes som beskrevet i det følgende.
Manualen skal studeres omhyggeligt, før modulet tages i brug.
Kun kvalificeret personale (teknikere) må installere dette modul.
Hvis modulet ikke benyttes som beskrevet i denne manual, så
forringes modulets beskyttelsesforanstaltninger.
ADVARSEL
Der må ikke tilsluttes farlig spænding til modulet, før dette
er fastmonteret, og følgende operationer bør kun udføres på
modulet i spændingsløs tilstand og under ESD-sikre forhold:
Fejlfinding på modulet.
Reparation af modulet må kun foretages af PR electronics A/S.
GENERELT
FARLIG
SPÆNDING

45
OVERENSSTEMMELSESERKLÆRING
Som producent erklærer
PR electronics A/S
Lerbakken 10
DK-8410 Rønde
hermed at følgende produkt:
Type: 5714
Navn: Programmerbart LED instrument
er i overensstemmelse med følgende direktiver og standarder:
EMC-direktivet 2004/108/EF og senere tilføjelser
EN 61326-1
For specifikation af det acceptable EMC-niveau henvises til modulets
elektriske specifikationer.
Lavspændingsdirektivet 2006/95/EFog senere tilføjelser
EN 61010-1
Rønde, 22. december 2009 Kim Rasmussen
Producentens underskrift
UL-INSTALLATIONSKRAV:
Til brug på en plan overflade i en type 1-kapsling
Brug kun 60/75°C kobberledninger
Max. omgivelsestemperatur ........................ 60°C
Max. ledningskvadrat, pin 41...46 ............... AWG 30-16
Max. ledningskvadrat, øvrige ...................... AWG 30-12
UL fil-nummer.............................................. E248256
KALIBRERING OG JUSTERING:
Under kalibrering og justering skal måling og tilslutning af eksterne spændinger
udføres i henhold til denne manual, og teknikeren skal benytte sikkerhedsmæs-
sigt korrekte værktøjer og instrumenter.
BETJENING UNDER NORMAL DRIFT:
Operatører må kun indstille eller betjene modulerne, når disse er fast installeret
på forsvarlig måde i tavler el. lignende, så betjeningen ikke medfører fare for liv
eller materiel. Dvs., at der ikke er berøringsfare, og at modulet er placeret, så
det er let at betjene.
RENGØRING:
Modulet må, i spændingsløs tilstand, rengøres med en klud let fugtet med
destilleret vand.
ANSVAR:
I det omfang instruktionerne i denne manual ikke er nøje overholdt, vil kunden
ikke kunne rette noget krav, som ellers måtte eksistere i henhold til den indgå-
ede salgsaftale, mod PR electronics A/S.

67
PROGRAMMERBART LED-INSTRUMENT
PREVIEW 5714
• 4-cifret 14-segment LED-display
• Indgang for mA, V, potentiometer, RTD og TC
• 2 relæer og analog udgang
• Universel forsyningsspænding
• Programmerbar via fronttaster
Anvendelse:
• Instrument til digital visning af strøm- / spændings- / temperatur- eller 3-leder
potentiometersignaler.
• Styring af procesforløb med 2 sæt potentialefri skiftekontakter og analog
udgang.
• Til lokal visning i ekstreme vådrumsmiljøer med påmonteret specialdesingnet
frontafdækning.
Teknisk karakteristik:
• 4-cifret LED-display med 13,8 mm 14-segment cifre. Max. displayvisning
-1999...9999 med fri kommaplacering og relæ ON- / OFF-indikering.
• Med funktionstasterne på instrumentets front kan alle driftsparametre tilpas-
ses enhver applikation.
• PReview 5714 kan leveres færdigkonfigureret efter specifikation, klar til styring /
visualisering af et procesforløb.
• Via menupunkt kan hjælpetekster vælges på 8 sprog.
• For relæudgangene er tiden til test af installationen minimeret via et menu-
punkt, hvor hvert enkelt relæ kan aktiveres / deaktiveres uafhængigt af ind-
gangssignalet.
Montage / installation:
• Designet for panelmontage i tavlefront. En inkluderet gummipakning skal
monteres mellem udskæringshul og displayfront for opnåelse af tæthedsgrad
IP65 (NEMA 4). En specialdesignet stænktæt afdækning til ekstra beskyttelse
leveres som ekstraudstyr.
FRONT- OG BAGSIDELAYOUT
Billede 1: 5714 set fra fronten
Billede 2: 5714 set fra bagsiden.

+
-
12
11
26
25
24
23
22
21
1 2
32
31
1 2
+
-+
-
46
45
44
43
42
41
4 3 2
TC
1 2
+
-
89
NB.: Den stænktætte afdækning skal bestilles separat. Bestillingsnr. 8335
Elektriske specifikationer:
Specifikationsområde:
-20°C til +60°C
Fælles specifikationer:
Forsyningsspænding, universel ................... 21,6...253 VAC, 50...60 Hz eller
19,2...300 VDC
Forbrug:
Isolationsspænding, test / drift ................... 2,3 kVAC / 250 VAC
Signal- / støjforhold ..................................... Min. 60 dB (0...100 kHz)
Reaktionstid (0...90%, 100...10%), programmerbar:
Temperaturindgang................................ 1...60 s
Strøm- / spændingsindgang ................. 0,4...60 s
Kalibreringstemperatur ................................ 20...28°C
Nøjagtighed, størst af generelle og basisværdier:
Generelle værdier
Indgangstype Absolut
nøjagtighed Temperatur-
koefficient
Alle ≤ ±0,1% af visning ≤ ±0,01% af visning / °C
Type Egetforbrug Maxforbrug
5714A 2,2 W 2,5 W
5714B 2,7 W 3,0 W
5714C 2,7 W 3,0 W
5714D 3,2 W 3,5 W
Bestillingsskema: 5714
Type Version
5714 Standard................: A
2 relæer ................: B
Analog udgang . . . . . . . . . . . : C
Analog udgang og 2 relæer : D
Applikationer
Indgangssignaler:
Strøm
Potentio-
meter
Spæn-
ding
RTD -
Forbindelse, ledere
Udgangssignaler:
2 skifterelæer
Analog, 0/4...20 mA
Forsyning:
21,6...253 VAC
eller
19,2...300 VDC
2-Trådstransmitter

10 11
Kabelmodstand pr. leder, RTD (max.) ......... 50 Ω
Følerstrøm, RTD .......................................... Nom. 0,2 mA
Virkning af følerkabelmodstand
(3- / 4-leder), RTD ....................................... < 0,002 Ω / Ω
Følerfejlsdetektering, RTD ........................... Ja
Kortslutningsdetektering, RTD .................... < 15 Ω
TC indgang:
Koldt loddestedskomp. (CJC)
via intern føler ......................................... ±(2,0°C + 0,4°C * Δt)
Δt = intern temperatur - omgivelsestemperatur
Følerfejlsdetektering, alle TC-typer ............. Ja
Følerfejlsstrøm:
under detektering .................................... Nom. 2 µA
ellers ........................................................ 0 µA
Strømindgang:
Måleområde ................................................ 0...20 mA
Programmerbare måleområder ................... 0...20 og 4...20 mA
Indgangsmodstand ..................................... Nom. 20 Ω + PTC 25 Ω
Følerfejlsdetektering:
strømsløjfebrud 4...20 mA ..................... Ja
Spændingsindgang:
Måleområde ................................................ 0...12 VDC
Programmerbare måleområder ................... 0...1, 0,2...1,
0...10 og 2...10 VDC
Indgangsmodstand ..................................... Nom. 10 MΩ
Hjælpespænding:
2-trådsforsyning (klemme 46...45) ......... 25...15 VDC / 0...20 mA
Ledningskvadrat, klemme 41...46 (max.) .... 1 x 1,5 mm2 flerkoret ledning
Ledningskvadrat, øvrige (max.) ................... 1 x 2,5 mm2 flerkoret ledning
Relativ luftfugtighed .................................... < 95% RH (ikke kond.)
Mål (HxBxD) ................................................ 48 x 96 x 120 mm
Udskæringsmål .......................................... 44,5 x 91,5 mm
Kapslingsklasse (monteret i tavlefront) ....... IP65
Vægt ............................................................ 230 g
RTD- og potentiometerindgang:
Indgang for RTD-typer:
Pt10, Pt20, Pt50, Pt100, Pt200, Pt250, Pt300, Pt400, Pt500, Pt1000
Ni50, Ni100, Ni120, Ni1000
Indgangs-
type Min.
værdi Max.
værdi
Standard
Pt100
Ni100
Potentiometer
-200°C
-60°C
10 Ω
+850°C
+250°C
100 kΩ
IEC60751
DIN 43760
-
Basisværdier
Indgangstype Basis-
nøjagtighed Temperatur-
koefficient
mA ≤ ±4 µA ≤ ±0,4 µA / °C
Volt ≤ ±20 µV ≤ ±2 µV / °C
Potentiometer ≤ ±0,1 Ω ≤ ±0,01 Ω / °C
Pt100 ≤ ±0,2°C ≤ ±0,02°C / °C
Ni100 ≤ ±0,3°C ≤ ±0,03°C / °C
TC-type: E, J, K,
L, N, T, U
≤ ±1°C
≤ ±0,05°C / °C
TC-type: R, S,
W3, W5, LR
≤ ±2°C
≤ ±0,2°C / °C
TC type: B
160...400°C
≤ ±4.5°C
≤ ±0.45°C / °C
TC type: B
400...1820°C
≤ ±2°C
≤ ±0.2°C / °C
EMC-immunitetspåvirkning ................................. < ±0,5% af visning
Type Min.
værdi Max.
værdi
Standard
B
E
J
K
L
N
R
S
T
U
W3
W5
LR
+0°C
-100°C
-100°C
-180°C
-200°C
-180°C
-50°C
-50°C
-200°C
-200°C
0°C
0°C
-200°C
+1820°C
+1000°C
+1200°C
+1372°C
+900°C
+1300°C
+1760°C
+1760°C
+400°C
+600°C
+2300°C
+2300°C
+800°C
IEC 60584-1
IEC 60584-1
IEC 60584-1
IEC 60584-1
DIN 43710
IEC 60584-1
IEC 60584-1
IEC 60584-1
IEC 60584-1
DIN 43710
ASTM E988-90
ASTM E988-90
GOST 3044-84

12 13
Udgange:
Display:
Displayvisning.............................................. -1999...9999 (4 cifre)
Kommaplacering ......................................... Programmerbar
Cifferhøjde ................................................... 13,8 mm
Display opdatering ...................................... 2,2 gange / s
Indgang uden for indgangsområde
indikeres med .............................................. Beskrivende tekster
Strømudgang:
Signalområde (span) ................................... 0...20 mA
Programmerbare signalområder ................. 0...20, 4...20,
20...0 og 20...4 mA
Belastning (max.) ......................................... 20 mA / 800 Ω / 16 VDC
Belastningsstabilitet .................................... ≤ 0,01% af span / 100 Ω
Følerfejlsdetektering .................................... 23 / 0 / 3,5 mA, Ingen
NAMUR NE 43 Up- / Downscale ................ 23 mA / 3,5 mA
Begrænsning af udgang:
på 4...20 og 20...4 mA signaler ............. 3,8...20,5 mA
på 0...20 og 20...0 mA signaler ............. 0...20,5 mA
Strømbegrænsning ...................................... ≤ 28 mA
Relæudgange:
Relæfunktion ............................................... Setpunkt
Hysterese, i % / display counts .................. 0,1...25% / 1...2999
On- og Off-forsinkelse ................................. 0...3600 s
Følerfejlsdetektering .................................... Bryde / Slutte / Hold
Max. spænding ........................................... 250 VRMS
Max. strøm .................................................. 2 A / AC
Max. AC effekt ............................................. 500 VA
Max. strøm ved 24 VDC .............................. 1 A
Marinegodkendelse:
Det Norske Veritas, Ships & Offshore ......... Standard for Certification No.2.4
GOST R godkendelse:
VNIIM, Cert. no. ........................................... Se www.prelectronics.dk
Overholdte myndighedskrav: Standard:
EMC 2004/108/EF ....................................... EN 61326-1
LVD 2006/95/EF .......................................... EN 61010-1
UL, Standard for Safety .............................. UL 508
Følerfejlsdetektering i og uden for område:
Uden for område visning (IN.LO, IN.HI):
Ved overskridelse af A/D-konverterens eller polynomiets gyldige område.
Indgang Område Visning Grænse
VOLT
0...1 V / 0,2...1 V IN.LO < -25 mV
IN.HI > 1,2 V
0...10 V / 2...10 V IN.LO < -25 mV
IN.HI > 12 V
CURR 0...20 mA / 4...20 mA IN.LO < -1,05 mA
IN.HI > 25,05 mA
POTM - IN.LO < -0,5%
IN.HI > 100,5%
TEMP TC / RTD IN.LO < temperaturområde -2°C
IN.HI > temperaturområde +2°C
Følerfejlsdetektering (SE.BR, SE.SH):
Indgang Område Visning Grænse
CURR Strømsløjfebrud (4..20mA) SE.BR <= 3,6 mA; > = 21 mA
TEMP
TC SE.BR > ca. 750 kohm / (1,25 V)
RTD, 2-leder
Ingen SE.SH for Pt10, Pt20 og Pt50
SE.BR > ca. 15 kohm
SE.SH < ca. 15 ohm
RTD, 3-leder
Ingen SE.SH for Pt10, Pt20 og Pt50
SE.BR > ca. 15 kohm
SE.SH < ca. 15 ohm
RTD, 4-leder
Ingen SE.SH for Pt10, Pt20 og Pt50
SE.BR > ca. 15 kohm
SE.SH < ca. 15 ohm
Display under min. / over max. visning (-1.9.9.9, 9.9.9.9):
Indgang Område Visning Grænse
CURR Alle -1.9.9.9 Displayværdi <-1999
9.9.9.9 Displayværdi >9999
VOLT Alle -1.9.9.9 Displayværdi <-1999
9.9.9.9 Displayværdi >9999
POTM - -1.9.9.9 Displayværdi <-1999
9.9.9.9 Displayværdi >9999
Følerfejlcheck i modelvarianter:
Model: Konfiguration Følerfejlsdetektering:
5714A Altid: ON
5714B ERR1=NONE, ERR2=NONE: OFF
Ellers: ON
5714C O.ERR=NONE: OFF
Ellers: ON
5714D ERR1=NONE, ERR2=NONE, O.ERR=NONE. OFF
Ellers: ON

+
-
+
-
+
-Tx +
-
31 32
41 42 43 44 45 4641 42 43 44 45 4641 42 43 44 45 46
41 42 43 44 45 46 41 42 43 44 45 46 41 42 43 44 45 46
41 42 43 44 45 46 41 42 43 44 45 46
+
-mA
11 12
R2
R1
21 22 23 24 25 26
I+
11
12
31
32
CPU
AD
EEPROM
PTC
20 Ω
5714
1 2 3 4
46
45
44
43
42
41
+V
4 3 2
21
22
23
24
25
26
R1
R2
1
3
2
Tx
+
+
+
mA
14 15
TILSLUTNINGER
RTD, 2-leder RTD, 3-leder RTD, 4-leder
PotentiometerSpænding
TC 2-trådstransmitter Strøm
Strøm Relæer
Indgange:
Udgange:
Forsyning:
Visning ved hardwarefejl
Fejlsøgning Visning Årsag
Test af intern kommunikation uC / ADC HW.ER Permanent fejl i ADC
Test af intern CJC-føler CJ.ER CJC-føler defekt
Checksum test af den aktuelle konfiguration i RAM RA.ER Fejl i RAM
Checksum test af den aktuelle konfiguration i Eeprom EE.ER Fejl i EEPROM
! Alle fejlvisninger i display blinker 1 gang pr. sekund, samt suppleres med tilhørende hjælpetekst.
BLOKDIAGRAM
Forsyning
Forsyning
21,6...253 VAC
eller
19,2...300 VDC
I
Udgang
Version D
2-trådsforsyning
> 15 VDC
Indgang +,
mA
Indgang gnd.
RTD,
ledere
Fælles
Relæ 1 N.O.
Relæ 1 N.C.
Fælles
Relæ 2 N.O.
Relæ 2 N.C.
Gnd.
Potm.
TC
0,2 mA
Int.
CJC

16
Power up
50.0
3
F.SET
REL1
REL2 3
1.0
1.2
1 2 1 2
SETP
-1999
9999
/OFF 3
1 2
DI.LO REL.U
DI.HI
1.1
0000
9999
1 2
3
CURR 3RANG
4-20
0-20
1 2
VOLT 3RANG 3
1 2
0-10
2-10
0.2-1
0.0-1
IN
1 2
DEC.P
1111
1.1.1.1
1 2
POTM CA.LO CA.HI
YES
NO
1 2
YES
NO
1 2
3
TEMP TYPE
3
PT.TY
TC
CON.W
TC.TY
1 2
PT 3
10
-
1000
1 2
4W
3W
2W
1 2
NI NI.TY CON.W
50
-
1000
1 2
4W
3W
2W
1 2
1 2
3
3
3
3
3
PASS
LANG
3
1 2
3
3a999
9999
1 2
3a999
9999
1 2
3PERC
DISP
1 2
3
1.3
REL.1
SET
SKIP
OFF
1 2
3
SETP
a999
9999
1 2
3
ACT1
INCR
DECR
1 2
3
HYS1
1
2999
1 2
3
ERR1
HOLD
ACTI
DEAC
NONE
1 2
3
ON.DE
0000
3600
1 2
3
OF.DE
0000
3600
1 2
3
3
1.5
REL.2
SET
SKIP
OFF
1 2
3
SETP
a999
9999
1 2
3
ACT2
INCR
DECR
1 2
3
HYS2
1
2999
1 2
3
ERR2
HOLD
ACTI
DEAC
NONE
1 2
3
ON.DE
0000
3600
1 2
3
OF.DE
0000
3600
1 2
3
3
1.5
A.OUT
4-20
0-20
20-4
20-0
1 2
3
O.LO
a999
9999
1 2
3
O.HI
a999
9999
1 2
3
O.ERR
3.5mA
0mA
23mA
NONE
1 2
3
RESP
0.0
60.0
1 2
3
E.PAS
YES
NO
1 2
3
N.PAS
0000
9999
1 2
3
NO
----
1.51.7 1.7
1.6
1.4
DEC.P
TC.B TC.E TC.J TC.K TC.L
TC.N TC.R TC.S TC.T TC.U
TC.W3 TC.W5 TC.LR
1111
111.1
1 2
3
3
UNIT
3'C
'F
1 2
3
3
1.6 1.6
1.4
3
DE_DK
ES_FR
IT_SE
UK_CZ
3
16 17
1.0 = Normaltilstand
1.1 = Kun hvis beskyttet
med password.
1.2 = Kun hvis FastSet
er aktiveret.
1.3 = FastSet og relætest
blokeret ved password
5000 ...9999.
1.4 = ingen relæudgange
1.5 = Ikke for indgangssignaler:
Potentiometer, 0...20 mA
og spænding
1.6 = Ingen analog udgang
1.7 = Kun for temperaturindgang
RUTEDIAGRAM
Hvis ingen taster har været aktiveret i 2 minutter, returnerer displayet til
normaltilstanden 1.0 uden at gemme eventuelle konfigurationsændringer.
1 Forøgelse af værdi / vælg næste parameter
2 Formindskelse af værdi / vælg forrige parameter
3 Accepter valget og gå til næste menu
Holde 3 går til forrige menu / returnerer til 1.0 uden at gemme
Holde
Til 1.0
Til normaltilstand 1.0
Hurtig setpunktsindstilling
og test af relæer.
1 Forøgelse af setpunkt
2 Formindskelse af setpunkt
3 Gem og forlad menuen
1 og 2 samtidig = relæ skifter tilstand

18 19
RULLENDE HJÆLPETEKSTER
Display i Normal tilstand xxxx, Hardwarefejl:
SE.BR --> KABELBRUD
SE.SH --> KORTSLUTTET FØLER
IN.HI --> INDGANG OVER MAX. VAERDI
IN.LO --> INDGANG UNDER MIN.-VAERDI
9.9.9.9 --> DISPLAY OVER MAX.-VISNING
-1.9.9.9 --> DISPLAY UNDER MIN.-VISNING
HW.ER --> HARDWARE-FEJL
EE.ER --> FEJL I EEPROM -
KONTROLLER OPSAETNING
RA.ER --> FEJL I RAM
CJ.ER --> FEJL PAA CJC-FØLER
Hurtig setpunktsindstilling (Enabled):
F.SET
REL1 --> HURTIG SETPUNKTSINDSTIL. -
VAELG RELAE
REL2 -->
SETP
xxxx --> RELAE-SETPUNKT - TRYK OK
FOR AT GEMME
Hurtig setpunktsindstilling (Disabled):
SETP
xxxx --> RELAE-SETPUNKT - READ ONLY
Konfigurationsmenuer:
LANG
DE --> DE - WAEHLE DEUTSCHEN HILFETEXT
DK --> DK - VAELG DANSK HJAELPETEKST
ES --> ES - SELECCIONAR TEXTO DE
AYUDA EN ESPANOL
FR --> FR - SELECTION TEXTE D’AIDE
EN FRANCAIS
IT --> IT - SELEZIONARE TESTI DI
AIUTO ITALIANI
SE --> SE - VALJ SVENSK HJALPTEXT
UK --> UK - SELECT ENGLISH HELPTEXT
CZ --> CZ - VYBER CESKOU NAPOVEDU
PASS
xxxx --> ANGIV KORREKT PASSWORD
IN
C.LIN* --> TEKST INDTASTET AF BRUGER I PRESET
CURR --> STRØM INDGANG
VOLT --> SPAENDINGS-INDGANG
POTM --> POTENTIOMETER INDGANG
TEMP --> TEMPERATURFØLER INDGANG
RANG Når strøm er valgt:
0-20 --> INDGANGSOMRAADE I mA
4-20 --> INDGANGSOMRAADE I mA
RANG Når spænding er valgt:
0-10 --> INDGANGSOMRAADE I VOLT
2-10 --> INDGANGSOMRAADE I VOLT
0.0-1 --> INDGANGSOMRAADE I VOLT
0.2-1 --> INDGANGSOMRAADE I VOLT
CA.LO
YES --> KALIBRER POTENTIOMETER LAV
NO --> KALIBRER POTENTIOMETER LAV
CA.HI
YES --> KALIBRER POTENTIOMETER HØJ
NO --> KALIBRER POTENTIOMETER HØJ
DEC.P
1111 --> KOMMAPLACERING
111.1 --> KOMMAPLACERING
11.11 --> KOMMAPLACERING
1.111 --> KOMMAPLACERING
DI.LO
xxxx --> DISPLAYVISNING MIN.
DI.HI -->
xxxx --> DISPLAYVISNING MAX.
REL.U
PERC --> INDSTIL SETPUNKT I PROCENT
DISP --> INDSTIL SETPUNKT I DISPLAYVISNING
TYPE
PT --> VAELG PT SOM FØLER TYPE
NI --> VAELG NI SOM FØLER TYPE
TC --> VAELG TC SOM FØLER TYPE
PT.TY
10 --> VAELG PT FØLER TYPE
20 --> VAELG PT FØLER TYPE
50 --> VAELG PT FØLER TYPE
100 --> VAELG PT FØLER TYPE
200 --> VAELG PT FØLER TYPE
250 --> VAELG PT FØLER TYPE
300 --> VAELG PT FØLER TYPE
400 --> VAELG PT FØLER TYPE
500 --> VAELG PT FØLER TYPE
1000 --> VAELG PT FØLER TYPE
NI.TY
50 --> VAELG NI FØLER TYPE
100 --> VAELG NI FØLER TYPE
120 --> VAELG NI FØLER TYPE
1000 --> VAELG NI FØLER TYPE
CONN Når Pt og Ni føler er valgt
2W --> VAELG 2-LEDER FØLERTILSLUTNING
3W --> VAELG 3-LEDER FØLERTILSLUTNING
4W --> VAELG 4-LEDER FØLERTILSLUTNING
TC.TY
TC. B --> VAELG TC FØLER TYPE
TC. E --> VAELG TC FØLER TYPE
TC. J --> VAELG TC FØLER TYPE
TC. K --> VAELG TC FØLER TYPE
TC. L --> VAELG TC FØLER TYPE
TC. N --> VAELG TC FØLER TYPE
TC. R --> VAELG TC FØLER TYPE
TC. S --> VAELG TC FØLER TYPE
TC. T --> VAELG TC FØLER TYPE
TC. U --> VAELG TC FØLER TYPE
TC.W3 --> VAELG TC FØLER TYPE
TC.W5 --> VAELG TC FØLER TYPE
TC.LR --> VAELG TC FØLER TYPE
DEC.P Når temperatur er valgt
1111 --> KOMMAPLACERING
111.1 --> KOMMAPLACERING
UNIT
°C --> VISNING OG RELAE-
INDSTILLING I CELSIUS
°F --> VISNING OG RELAE-
INDSTILLING I FAHRENHEIT
REL1
SET --> GAA TIL INDSTILLING AF RELAE 1
SKIP --> SPRING OVER INDSTILLING AF RELAE 1
OFF --> RELAE 1 DEAKTIVERET
SETP
xxxx --> RELAE-SETPUNKT
ACT1
INCR --> AKTIVER VED STIGENDE SIGNAL
DECR --> AKTIVER VED FALDENDE SIGNAL
HYS1
xxxx --> RELAE-HYSTERESE
ERR1
HOLD --> HOLD RELAE VED FEJL
ACTI --> AKTIVER RELAE VED FEJL
DEAC --> DEAKTIVER RELAE VED FEJL
NONE --> UDEFINERET STATUS VED FEJL
ON.DE
xxxx --> RELAE ON-FORSINKELSE I SEKUNDER
OF.DE
xxxx --> RELAE OFF-FORSINKELSE I SEKUNDER
REL2
SET --> GAA TIL INDSTILLING AF RELAE 2
SKIP --> SPRING OVER INDSTILLING AF RELAE 2
OFF --> RELAE 2 DEAKTIVERET
SETP
xxxx --> RELAE-SETPUNKT
ACT2
INCR --> AKTIVER VED STIGENDE SIGNAL
DECR --> AKTIVER VED FALDENDE SIGNAL
HYS2
xxxx --> RELAE-HYSTERESE
ERR2
HOLD --> HOLD RELAE VED FEJL
ACTI --> AKTIVER RELAE VED FEJL
DEAC --> DEAKTIVER RELAE VED FEJL
NONE --> UDEFINERET STATUS VED FEJL
ON.DE
xxxx --> RELAE ON-FORSINKELSE I SEKUNDER
OF.DE
xxxx --> RELAE OFF-FORSINKELSE I SEKUNDER
A.OUT
0-20 --> UDGANGSOMRAADE I mA
4-20 --> UDGANGSOMRAADE I mA
20-0 --> UDGANGSOMRAADE I mA
20-4 --> UDGANGSOMRAADE I mA
O.LO
xxxx --> DISPLAYVAERDI FOR UDGANG MIN.
O.HI
xxxx --> DISPLAYVAERDI FOR UDGANG MAX.
O.ERR
23mA --> NAMUR NE43 OPSKALERING VED FEJL
3,5mA --> NAMUR NE43 NEDSKALERING VED FEJL
0mA --> NEDSKALERING VED FEJL
NONE --> UDEFINERET UDGANG VED FEJL
RESP
xxx,x --> REAKTIONSTID FOR ANALOG
UDGANG I SEK.
E.PAS
NO --> AKTIVER PASSWORD-BESKYTTELSE
YES --> AKTIVER PASSWORD-BESKYTTELSE
N.PAS
xxxx --> VAELG NYT PASSWORD

t
10
10
20
20
30
30
40
40
50
50
60
60
70
70
80
80
90
90
100
100
0
t
Off N.C.
On N.C. On N.C.
10
10
20
20
30
30
40
40
50
50
60
60
70
70
80
80
90
90
100
100
0
Off N.O. Off N.O.
On N.O.Off N.O. Off N.O.On N.O.
Off N.C.On N.C. On N.C.
20 21
PROGRAMMERING / BETJENING
AF TRYKKNAPPER
Dokumentation til rutediagram
Generelt:
Når man påbegynder en opsætning, bliver brugeren ledt gennem alle opsæt-
ningsparametre og må vælge netop den konfiguration, der passer til appli-
kationen. Til hver valgmenu findes en rullende hjælpetekst som vil blive vist i
displayet, hvis ingen taster har været aktiveret i ca. 5 sekunder.
Programmeringen udføres ved hjælp af de 3 taster 1 2 og 3. 1 tasten for-
øger talværdien / vælger næste parameter. 2 tasten formindsker talværdien /
vælger forrige parameter. 3 tasten accepterer valget og går til næste menu.
Hvis en funktion ikke findes i hardwaren springes alle parametre tilhørende
funktionen over, så programmeringen er så simpel som mulig. Opsætningen
gemmes først til allersidst i menustrukturen, når displayet viser - - - -.
Ved at holde 3 tasten nedtrykket gås til forrige menu / bakkes der til normaltil-
stand (1.0) uden at gemme de ændrede tal / parametre.
Hvis ingen taster har været aktiveret i 2 minutter, vil displayet returnere til nor-
maltilstand (1.0) uden at gemme de ændrede tal / parametre.
Uddybende forklaringer:
Hurtig setpunktsindstilling og test af relæer: Menuerne er interaktive, så man
kan indstille setpunkterne, medens displayet foretager måling af indgangssig-
nalet, og se på lysdioderne, hvornår relæerne skifter tilstand . Dette vil i man-
ge situationer lette setpunktsindstillingen. Ved at aktivere 1 og 2 samtidigt
inden for ca. 0,5 sekund aktiveres en relætest, og relæet vil skifte tilstand.
Setpunktsændringen gemmes ved kortvarigt at aktivere 3 tasten. Holdes 3
tasten nedtrykket i mere end ca. 0,5 sekund, returneres til normaltilstand (1.0)
uden at gemme setpunktsændringen.
Passwordbeskyttelse: Det er muligt at vælge passwordbeskyttelse i to niveau-
er. Ved password mellem 0000 og 4999 er hurtig setpunktsindstilling og relæ-
test aktiveret. Vælges password mellem 5000 og 9999 er hurtig setpunktsind-
stilling og relætest blokeret, men menuerne vil vise det aktuelle setpunkt. Der
findes et default password 2008, som kan åbne for programmeringsmenu-
erne.
Grafisk afbildning af relæfunktionen setpunkt:
RelæenhederRelæenheder
Setpunkt = 50
Hysterese = 10
Hysterese = 10
Setpunkt = 50
Relæaktion: Stigende Relæaktion: Faldende

22 23
PROGRAMMABLE LED INDICATOR
PREVIEW 5714
TABLE OF CONTENTS
Warnings ............................................................................ 24
Safety instructions .............................................................. 25
Declaration of Conformity .................................................. 27
Front and back layout ........................................................ 28
Applications ........................................................................ 29
Technical characteristics .................................................... 29
Mounting ............................................................................ 29
Applications ........................................................................ 30
Order .................................................................................. 31
Electrical specifications ...................................................... 29
Sensor error detection ....................................................... 35
Connections ....................................................................... 36
Block diagram .................................................................... 37
Routing diagram ................................................................. 38
Scrolling help text .............................................................. 40
Configuration / operating the function keys ...................... 42
Graphic depiction of the relay function setpoint .............. 43

24 25
SYMBOL IDENTIFICATION
Triangle with an exclamation mark: Warning / demand. Potentially
lethal situations.
The CE mark proves the compliance of the module with the essential
requirements of the directives.
WARNING!
This module is designed for connection to hazardous electric
voltages. Ignoring this warning can result in severe personal
injury or mechanical damage. To avoid the risk of electric shock
and fire, the safety instructions of this manual must be observed
and the guidelines followed. The specifications must not be
exceeded, and the module must only be applied as described
in the following. Prior to the commissioning of the module, this
manual must be examined carefully. Only qualified personnel
(technicians) should install this module.
If the equipment is used in a manner not specified by the
manufacturer, the protection provided by the equipment may be
impaired.
WARNING!
Until the module is fixed, do not connect hazardous voltages to
the module.
The following operations should only be carried out on a
disconnected module and under ESD safe conditions:
Troubleshooting the module.
Repair of the module must be done by PR electronics A/S
only.
GENERAL
HAZARD -
OUS
VOLTAGE
SAFETY INSTRUCTIONS
DEFINITIONS:
Hazardous voltages have been defined as the ranges: 75 to 1500 Volt DC, and
50 to 1000 Volt AC.
Technicians are qualified persons educated or trained to mount, operate, and
also troubleshoot technically correct and in accordance with safety regulations.
Operators, being familiar with the contents of this manual, adjust and operate
the knobs or potentiometers during normal operation.
RECEIPT AND UNPACKING:
Unpack the device without damaging it. The packing should always follow the
device until this has been permanently mounted. Check at the receipt of the
device whether the type corresponds to the one ordered.
ENVIRONMENT:
Avoid direct sunlight, dust, high temperatures, mechanical vibrations and shock,
as well as rain and heavy moisture. If necessary, heating in excess of the stated
limits for ambient temperatures should be avoided by way of ventilation.
All modules fall under Installation Category II, Pollution Degree 1, and Insulation
Class II.
MOUNTING:
Only technicians who are familiar with the technical terms, warnings, and
instructions in the manual and who are able to follow these should connect the
module.
Should there be any doubt as to the correct handling of the module, please
contact your local distributor or, alternatively,
PR electronics A/S, Lerbakken 10, DK-8410 Rønde, Denmark,
tel: +45 86 37 26 77.
Mounting and connection of the module should comply with national legislation
for mounting of electric materials, i.a. wire cross section, protective fuse, and
location. Descriptions of Input / Output and supply connections are shown in
the block diagram and side label.

26 27
The following apply to fixed hazardous voltages-connected modules:
The max. size of the protective fuse is 10 A and, together with a power
switch, it should be easily accessible and close to the module. The
power switch should be marked with a label telling it will switch off the
voltage to the module.
UL INSTALLATION REQUIREMENTS:
For use on a flat surface of a type 1 enclosure
Use 60/75°C copper conducters only
Max. ambient temperature ..................... 60°C
Max. wire size, pins 41...46 .................... AWG 30-16
Max. wire size, others ............................ AWG 30-12
UL file number ........................................ E248256
CALIBRATION AND ADJUSTMENT:
During calibration and adjustment, the measuring and connection of external
voltages must be carried out according to the specifications of this manual. The
technician must use tools and instruments that are safe to use.
NORMAL OPERATION:
Operators are only allowed to adjust and operate modules that are safely fixed
in panels, etc., thus avoiding the danger of personal injury and damage. This
means there is no electrical shock hazard, and the module is easily accessible.
CLEANING:
When disconnected, the module may be cleaned with a cloth moistened with
distilled water.
LIABILITY:
To the extent the instructions in this manual are not strictly observed, the
custom er cannot advance a demand against PR electronics A/S that would
otherwise exist according to the concluded sales agreement.
DECLARATION OF CONFORMITY
As manufacturer
PR electronics A/S
Lerbakken 10
DK-8410 Rønde
hereby declares that the following product:
Type: 5714
Name: Programmable LED indicator
is in conformity with the following directives and standards:
The EMC Directive 2004/108/EC and later amendments
EN 61326-1
For specification of the acceptable EMC performance level, refer to the
electrical specifications for the module.
The Low Voltage Directive 2006/95/EC and later amendments
EN 61010-1
Rønde, 22 December 2009 Kim Rasmussen
Manufacturer’s signature

28 29
FRONT AND BACK LAYOUT
Picture 1: Front of PReview 5714.
Picture 2: Back of PReview 5714.
PROGRAMMABLE LED INDICATOR
PREVIEW 5714
• 4-digit 14-segment LED indicator
• Input for mA, V, potentiometer, RTD and TC
• 2 relays and analogue output
• Universal voltage supply
• Front key programmable
Application:
• Display for digital readout of current, voltage, temperature or potentiometer
signals.
• Process control with 2 pairs of potential-free relays and / or analogue output.
• For local readout in extremely wet atmospheres with a specially designed
splash-proof cover.
Technical characteristics:
• 4-digit LED indicator with 13.8 mm 14-segment characters. Max. display
read out -1999...9999 with programmable decimal point, relay ON / OFF indi-
cation.
• All operational parameters can be adjusted to any application by use of the
front keys.
• PReview 5714 is available fully-configured acc. to specifications ready for
process control and visualisation.
• Help texts in eight languages can be selected via a menu item.
• In versions with relay outputs the user can minimise the installation test time
by activating / deactivating each relay independently of the input signal.
Mounting:
• To be mounted in front panel. The included rubber packing must be mounted
between the panel cutout hole and the display front to obtain IP65 (NEMA 4)
tightness. For extra protection in extreme environments, PReview 5714 can
be delivered with a speially designed splash-proof cover as accessory.

+
-
12
11
26
25
24
23
22
21
32
31
1 2
1 2
+
-+
-
46
45
44
43
42
41
4 3 2
TC
1 2
+
-
30 31
Applications
Input signals:
Current
Potentio-
meter
Output signals:
2 changeover relays
Analogue, 0/4...20 mA
Supply:
21.6...253 VAC
or
19.2...300 VDC
Voltage
RTD -
Connection, wires
2-wire transmitter
NB! Please order the splash-proof cover seperately. Order No. 8335.
Electrical specifications:
Specifications range:
-20°C to +60°C
Common specifications:
Supply voltage, universal ............................ 21.6...253 VAC, 50...60 Hz or
19.2...300 VDC
Consumption
Isolation voltage, test / operation .............. 2.3 kVAC / 250 VAC
Signal- / noise ratio .................................... Min. 60 dB (0...100 kHz)
Response time (0...90 %, 100...10 %), programmable:
Temperature input ................................. 1...60 s
Current / voltage input.......................... 0.4...60 s
Calibration temperature.............................. 20...28°C
Accuracy, the greater of general and basic values:
General values
Input type Absolute
accuracy Temperature
coefficient
All ≤ ±0.1% of reading ≤ ±0.01% of reading / °C
Type Internal consumption Max. consumption
5714A 2.2 W 2.5 W
5714B 2.7 W 3.0 W
5714C 2.7 W 3.0 W
5714D 3.2 W 3.5W
Type Version
5714 Standard...................: A
2 relays....................: B
Analogue output. . . . . . . . . . . . .: C
Analogue output and 2 relys . . .: D
Order: 5714

32 33
Auxiliary supplies:
2 wire supply (pin 46...45) ........................... 25...15 VDC / 0...20 mA
Wire size, pin 41...46 (max.) ........................ 1 x 1.5 mm2 stranded wire
Wire size, others (max.) ............................... 1 x 2.5 mm2 stranded wire
Relative humidity ......................................... < 95% RH (non cond.)
Dimensions (HxWxD) ................................... 48 x 96 x 120 mm
Cutout dimensions ...................................... 44.5 x 91.5 mm
Protection degree (mounted in panel) ......... IP65
Weight ......................................................... 230 g
RTD and potentiometer input:
Input for RTD types:
Pt10, Pt20, Pt50, Pt100, Pt200, Pt250, Pt300, Pt400, Pt500, Pt1000
Ni50, Ni100, Ni120, Ni1000
Cable resistance pr. wire, RTD (max.) ......... 50 Ω
Input
type Min.
value Max.
value
Standard
Pt100
Ni100
Potentiometer
-200°C
-60°C
10 Ω
+850°C
+250°C
100 kΩ
IEC60751
DIN 43760
-
Sensor current, RTD .................................... Nom. 0.2 mA
Effect of sensor cable resistance
(3- / 4-wire), RTD ......................................... < 0.002 Ω / Ω
Sensor error detection, RTD ....................... Yes
Short curcuit detection, RTD....................... < 15 Ω
TC input:
Cold junction compensation (CJC)
via internal sensor ................................. ±(2.0°C + 0.4°C * Δt)
Δt = internal temperature - ambient temperature
Sensor error detection, all TC types ........... Yes
Sensor error detection ................................ Yes
Sensor error current:
when detecting ...................................... Nom. 2 µA
else ........................................................ 0 µA
Current input:
Measurement range .................................... 0...20 mA
Programmable measurement ranges .......... 0...20 and 4...20 mA
Input resistance ........................................... Nom. 20 Ω + PTC 25 Ω
Sensor error detection:
loop break 4...20 mA ............................. Yes
Voltage input:
Measurement range .................................... 0...12 VDC
Programmable measurement ranges .......... 0...1 / 0,2...1 /
0...10 / 2...10 VDC
Input resistance ........................................... Nom. 10 MΩ
Type Min.
value Max.
value
Standard
B
E
J
K
L
N
R
S
T
U
W3
W5
LR
0°C
-100°C
-100°C
-180°C
-200°C
-180°C
-50°C
-50°C
-200°C
-200°C
0°C
0°C
-200°C
+1820°C
+1000°C
+1200°C
+1372°C
+900°C
+1300°C
+1760°C
+1760°C
+400°C
+600°C
+2300°C
+2300°C
+800°C
IEC 60584-1
IEC 60584-1
IEC 60584-1
IEC 60584-1
DIN 43710
IEC 60584-1
IEC 60584-1
IEC 60584-1
IEC 60584-1
DIN 43710
ASTM E988-90
ASTM E988-90
GOST 3044-84
Basic values
Input type Basic
accuracy Temperature
coefficient
mA ≤ ±4 µA ≤ ±0.4 µA / °C
Volt ≤ ±20 µV ≤ ±2 µV / °C
Potentiometer ≤ ±0.1 Ω ≤ ±0.01 Ω / °C
Pt100 ≤ ±0.2°C ≤ ±0.02°C / °C
Ni100 ≤ ±0.3°C ≤ ±0.03°C / °C
TC type:
E, J, K, L, N, T, U
≤ ±1°C
≤ ±0.05°C / °C
TC type: R, S,
W3, W5, LR
≤ ±2°C
≤ ±0.2°C / °C
TC type: B
160...400°C
≤ ±4.5°C
≤ ±0.45°C / °C
TC type: B
400...1820°C
≤ ±2°C
≤ ±0.2°C / °C
EMC immunity influence ..................................... < ±0,5% of reading

34 35
Outputs:
Display:
Display readout ........................................... -1999...9999 (4 digits)
Decimal point .............................................. Programmable
Digit height .................................................. 13.8 mm
Display updating ......................................... 2.2 times / s
Input outside input range is
indicated by ................................................. Explanatory text
Current outout:
Signal range (span) ...................................... 0...20 mA
Programmable signal ranges ...................... 0...20 / 4...20 /
20...0 / 20...4 mA
Load (max.) .................................................. 20 mA / 800 Ω / 16 VDC
Load stability ............................................... ≤ 0.01% of span / 100 Ω
Sensor error detection ................................ 0 / 3.5 / 23 mA / none
NAMUR NE 43 up / downscale .................. 23 mA / 3.5 mA
Output limitation:
on 4...20 and 20...4 mA signals............. 3,8...20.5 mA
on 0...20 and 20...0 mA signals............. 0...20.5 mA
Current limit ................................................. ≤ 28 mA
Relay outputs:
Relay function.............................................. Setpoint
Hysteresis, in % / display counts ............... 0.1...25% / 1...2999
On and Off delay ......................................... 0...3600 s
Sensor error detection ................................ Make / Break / Hold
Max. voltage ................................................ 250 VRMS
Max. current ................................................ 2 A / AC
Max. AC power ........................................... 500 VA
Max. current at 24 VDC............................... 1 A
Marine approval:
Det Norske Veritas, Ships & Offshore ......... Standard for Certification No. 2.4
GOST R approval:
VNIIM, Cert. no. ........................................... See www.prelectronics.com
Observed authority requirements: Standard:
EMC 2004/108/EC ...................................... EN 61326-1
LVD 2006/95/EC .......................................... EN 61010-1
UL, Standard for Safety .............................. UL 508
Sensor error check in 5714 variants
Variant: Configuration Sensor error detection:
5714A Always: ON
5714B ERR1=NONE, ERR2=NONE: OFF
else: ON
5714C O.ERR=NONE: OFF
else: ON
5714D ERR1=NONE, ERR2=NONE, O.ERR=NONE: OFF
else: ON
Sensor error detection / sensor error detection outside range:
Outside range readout (IN.LO, IN.HI):
If the valid range of the A/D converter or the polynomial is exceeded
Input Range Readout Limit
VOLT
0..1 V / 0.2..1 V IN.LO < -25 mV
IN.HI > 1.2 V
0..10 V / 2..10 V IN.LO < -25 mV
IN.HI > 12 V
CURR 0..20 mA / 4..20 mA IN.LO < -1.05 mA
IN.HI > 25.05 mA
POTM - IN.LO < -0.5%
IN.HI > 100.5%
TEMP TC / RTD IN.LO < temperature range
IN.HI > temperature range
Sensor error detection (SE.BR, SE.SH):
Input Range Readout Limit
CURR Loop break (4..20mA) SE.BR <= 3.6 mA; > = 21 mA
TEMP
TC SE.BR > ca. 750 kohm / (1,25V)
Pt100 2-wire
No SE.SH for Pt10, Pt20 and Pt50
SE.BR > ca. 15 kohm
SE.SH < ca. 15 ohm
Pt100 3-wire
No SE.SH for Pt10, Pt20 and Pt50
SE.BR > ca. 15 kohm
SE.SH < ca. 15 ohm
Pt100 4-wire
No SE.SH for Pt10, Pt20 and Pt50
SE.BR > ca. 15 kohm
SE.SH < ca. 15 ohm
Display readout below min. / above max. (-1.9.9.9, 9.9.9.9):
Input Range Readout Limit
CURR All -1.9.9.9 Display readout <-1999
9.9.9.9 Display readout >9999
VOLT All -1.9.9.9 Display readout <-1999
9.9.9.9 Display readout >9999
POTM - -1.9.9.9 Display readout <-1999
9.9.9.9 Display readout >9999

+
-
+
-
+
-Tx +
-
31 32
41 42 43 44 45 4641 42 43 44 45 4641 42 43 44 45 46
41 42 43 44 45 46 41 42 43 44 45 46 41 42 43 44 45 46
41 42 43 44 45 46 41 42 43 44 45 46
+
-mA
11 12
R2
R1
21 22 23 24 25 26
I+
Gnd.
11
12
31
32
CPU
AD
EEPROM
0.2 mA
PTC
20 Ω
5714
1 2 3 4
46
45
44
43
42
41
TC+V
4 3 2
21
22
23
24
25
26
R1
R2
1
3
2
Tx
+
+
+
mA
36 37
CONNECTIONS
RTD, 2-wire RTD, 3-wire RTD, 4-wire
PotentiometerVoltage
TC 2-wire transmitter Current
Current Relays
Inputs:
Output:
Supply:
I
Output
Common
Relay 1 N.O.
Relay 1 N.C.
Common
Relay 2 N.O.
Relay 2 N.C.
Supply
Supply
21.6...253 VAC
or
19.2...300 VDC
Version D
Int.
CJC
2-wire supply
> 15 VDC
Input +,
mA
Input gnd.
RTD,
wires
Potm.
BLOCK DIAGRAM
Readout at hardware error
Error search Readout Error cause
Test of internal communication uC / ADC HW.ER Permanent error in ADC
Test of internal CJC sensor CJ.ER CJC sensor defect
Check-sum test of the configuration in RAM RA.ER Error in RAM
Check-sum test of the configuration in EEPROM EE.ER Error in EEPROM
! Error indications in the display blink once a second. The help text explains the error.
Other manuals for 5714
3
Table of contents
Languages:
Other PR electronics Measuring Instrument manuals

PR electronics
PR electronics 4511 User manual

PR electronics
PR electronics PRetrans 5115 Series User manual

PR electronics
PR electronics 5511 User manual

PR electronics
PR electronics 5514 User manual

PR electronics
PR electronics 5700 Series User manual

PR electronics
PR electronics 5714 User manual

PR electronics
PR electronics PReview 5515 User manual

PR electronics
PR electronics 5714 User manual

PR electronics
PR electronics 4510 User manual

PR electronics
PR electronics 5202 User manual