PR electronics 5700 Series User manual

PERFORMANCE
MADE
SMARTER
Product manual
5725
Programmable frequency indicator
TEMPERATURE | I.S. INTERFACES | COMMUNICATION INTERFACES | MULTIFUNCTIONAL | ISOLATION | DISPLAY
No. 5725V104-UK
From serial no.: 191059001

Communication
Display
I.S. Interface
Isolation
Multifunction
Temperature
Our compact, fast, high-quality 6 mm isolators are based on microprocessor technology to provide exceptional
performance and EMC-immunity for dedicated applications at a very low total cost of ownership. They can be
stacked both vertically and horizontally with no air gap separation between units required.
We deliver the safest signals by validating our products against the toughest safety standards. Through our
commitment to innovation, we have made pioneering achievements in developing I.S. interfaces with SIL 2 Full
Assessment that are both efficient and cost-effective. Our comprehensive range of analog and digital intrinsically
safe isolation barriers offers multifunctional inputs and outputs, making PR an easy-to-implement site standard.
Our backplanes further simplify large installations and provide seamless integration to standard DCS systems.
Our display range is characterized by its flexibility and stability. The devices meet nearly every demand for display
readout of process signals and have universal input and power supply capabilities. They provide a real-time
measurement of your process value no matter the industry and are engineered to provide a user-friendly and reliable
relay of information, even in demanding environments.
We provide inexpensive, easy-to-use, future-ready communication interfaces that can access your PR installed base
of products. All the interfaces are detachable, have a built-in display for readout of process values and diagnostics,
and can be configured via push-buttons. Product specific functionality includes communication via Modbus and
Bluetooth and remote access using our PR Process Supervisor (PPS) application, available for iOS and Android.
Our unique range of single devices covering multiple applications is easily deployable as your site standard. Having
one variant that applies to a broad range of applications can reduce your installation time and training, and greatly
simplify spare parts management at your facilities. Our devices are designed for long-term signal accuracy, low
power consumption, immunity to electrical noise and simple programming.
Our range of temperature transmitters and sensors provides the highest level of signal integrity from the
measurement point to your control system. You can convert industrial process temperature signals to analog, bus or
digital communications using a highly reliable point-to-point solution with a fast response time, automatic self-
calibration, sensor error detection, low drift, and top EMC performance in any environment.
Individually outstanding, unrivalled in combination
With our innovative, patented technologies, we make signal conditioning smarter and simpler. Our portfolio is composed of six
product areas, where we offer a wide range of analog and digital devices covering over a thousand applications in industrial
and factory automation. All our products comply with or surpass the highest industry standards, ensuring reliability in even
the harshest of environments and have a 5-year warranty for greater peace of mind.
6 Product Pillars
to meet your every need

5725V104-UK 3
Programmable frequency indicator
5725
Table of contents
Warning ................................................................................................ 4
Symbol identification .................................................................................... 4
Safety instructions ...................................................................................... 5
Front and back layout.................................................................................... 6
Application ............................................................................................. 7
Technical characteristics ................................................................................. 7
Mounting / installation................................................................................... 7
Applications ............................................................................................ 8
Order ................................................................................................... 9
Accessories ............................................................................................. 9
Electrical specifications .................................................................................. 9
Sensor error indication, inside and outside range .......................................................... 12
Connections ............................................................................................ 13
Block diagram ........................................................................................... 14
Configuration / operating the function keys ............................................................... 15
Additional features (from s/n > 121435001) .............................................................. 15
Additional features (from s/n > 181101000) .............................................................. 16
Routing diagram for 5725A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Routing diagram for 5725D .............................................................................. 19
Help text overview ...................................................................................... 21
Graphic depiction of the relay function setpoint ........................................................... 23
Installation instructions.................................................................................. 24
Document history ....................................................................................... 25

4 5725V104-UK
Warning
This device is designed for connection to hazardous electric voltages. Ignoring this warning can result in
severe personal injury or mechanical damage.
To avoid the risk of electric shock and fire, the safety instructions of this guide must be observed and
the guidelines followed. The specifications must not be exceeded, and the device must only be applied
as described in the following.
Prior to the commissioning of the device, this installation guide must be examined carefully.
Only qualified personnel (technicians) should install this device.
If the equipment is used in a manner not specified by the manufacturer, the protection provided by the
equipment may be impaired.
Warning
Until the device is fixed, do not connect hazardous voltages to the device. The following operations
should only be carried out on a disconnected device and under ESD safe conditions:
Troubleshooting the device.
Repair of the device and replacement of circuit breakers must be done by PR electronics A/S only.
Symbol identification
Triangle with an exclamation mark: Read the manual before installation and commissioning of the
device in order to avoid incidents that could lead to personal injury or mechanical damage. Warning /
demand. Potentially lethal situations.
The CE mark proves the compliance of the device with the essential requirements of the EU directives.
The UKCA mark proves the compliance of the device with the essential requirements of the UK
regulations.
The double insulation symbol shows that the device is protected by double or reinforced insulation.
GENERAL
HAZARD-
OUS
VOLTAGE

5725V104-UK 5
Safety instructions
Definitions
Hazardous voltages have been defined as the ranges: 75 to 1500 Volt DC, and 50 to 1000 Volt AC.
Technicians are qualified persons educated or trained to mount, operate, and also trouble-shoot technically correct and in
accordance with safety regulations.
Operators, being familiar with the contents of this manual, adjust and operate the knobs or potentiometers during normal
operation.
Receipt and unpacking
Unpack the device without damaging it and check whether the device type corresponds to the one ordered. The packing
should always follow the device until this has been permanently mounted.
Environment
Avoid direct sun light, dust, high temperatures, mechanical vibrations and shock, and rain and heavy moisture. If necessary,
heating in excess of the stated limits for ambient temperatures should be avoided by way of ventilation.
The device must be installed in pollution degree 2 or better.
The device is designed to be safe at least under an altitude up to 2 000 m.
The device is designed for indoor use.
Mounting
Only technicians, who are familiar with the technical terms, warnings, and instructions in the manual and who are able to
follow these, should connect the device. Should there be any doubt as to the correct handling of the device, please contact
your local distributor or, alternatively,
PR electronics A/S
www.prelectronics.com
Mounting and connection of the device should comply with national legislation for mounting of electric materials, i.e. wire
cross section, protective fuse, and location.
Stranded wire should be installed with an insulation stripping length of 5 mm or via a suitable insulated terminal such as a
bootlace ferrule.
Descriptions of Input / Output and supply connections are shown in the block diagram and side label.
The following apply to fixed hazardous voltages-connected devices:
The max. size of the protective fuse is 10 A and, together with a power switch, it should be easily accessible and close
to the device. The power switch should be marked with a label indicating that it will switch off the voltage
to the device.
Year of manufacture can be taken from the first two digits in the serial number.
Calibration and adjustment
During calibration and adjustment, the measuring and connection of external voltages must be carried out according to the
specifications of this manual. The technician must use tools and instruments that are safe to use.
Normal operation
Operators are only allowed to adjust and operate devices that are safely fixed in panels, etc., thus avoiding the danger of
personal injury and damage. This means there is no electrical shock hazard, and the device is easily accessible.
Cleaning
When disconnected, the device may be cleaned with a cloth moistened with distilled water.
Liability
To the extent the instructions in this manual are not strictly observed, the customer cannot advance a demand against PR
electronics A/S that would otherwise exist according to the concluded sales agreement.

6 5725V104-UK
Front and back layout
Picture 1: Front of 5725.
Picture 2: Back of 5725.

5725V104-UK 7
Programmable frequency indicator
5725
• Measures NPN, PNP, Contact, NAMUR, SO, Tacho and TTL sensors
• Programmable frequency input span of 0.001 Hz to 50 kHz
• The 5725D has two SPDT relays and one analog output
• Easy to read 4 digit, 14 segment LED display with scrolling help text
• Universally powered by 21.5…253 VAC or 19.2… 300 VDC
Application
• The 5725 measures, scales, and displays frequency signals found in many process speed and flow rate applications.
• The indicator can measure the period of the frequency, useful for displaying the elapsed time between events.
• The 5725D has two SPDT setpoint contacts and a 0/4...20 mA output for process control.
• The installed display provides IP65 environmental sealing, and additional protection is provided by the optional 8335
splash proof cover.
Technical characteristics
• 4 digit display w/13.8 mm high, 14 segment LED digits and adjustable decimal point.
• Indicator is scalable from -1999 to 9999
• Scrolling help text makes programming easy.
• Built-in excitation source for measuring NPN, PNP, NAMUR and SO sensors.
• Fast response time of 1 cycle + 100 ms, and excellent accuracy of better than 0.05% of selected range.
• The analog output current on the 5725D can be dampened from 0.1 to 60 seconds, and can handle up to 800 Ohms loop
load.
• The 5725 meets NAMUR NE21 recommendations, for high performance in harsh EMC environments.
• 2.3 kVAC galvanic isolation between input, output and supply.
• Excellent signal/noise ratio of > 60 dB.
Mounting / installation
• Easy to mount 1/8 DIN (48 x 96 mm) panel meter with IP65, (type 4X) sealing.
• Approved for marine applications.
• Fully push-button programmable.
• Password protected.

S0
44
43
42
41
∼
TTL
1122
32
31
1122
-
+
26
25
24
23
22
21
12
11
1122
∼
∼
8 5725V104-UK
Applications
21.6...253 VAC
or
19.2...300 VDC
Supply:
Output signals:
Input signals:
+ Supply 5...17 V
Contact
(NPN)
Special trig
current & voltage
Relay 1
Relay 2
+ Input
Tacho
Input gnd
TTL S0 NAMUR PNP NPN Tacho
Analog, 0/4...20 mA
+ Supply + Supply

5725V104-UK 9
Order
Type Version
5725 Standard
Analog output and 2 relays
: A
: D
Accessories
8335 = Splash proof cover
Electrical specifications
Environmental conditions:
Operating temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -20°C to +60°C
Storage temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -40°C to +85°C
Calibration temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20...28°C
Relative humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 95% RH (non-cond.)
Protection degree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP20
Installation in . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pollution degree 2 & overvoltage category II.
Mechanical specifications:
Dimensions (HxWxD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 x 96 x 120 mm
Cutout dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44.5 x 91.5 mm
Protection degree (mounted in panel) . . . . . . . . . . . . . . . . . . . . . . . IP65 / Type 4X, UL50E
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230 g
Wire size, pin 11-12 & 41-44, max. . . . . . . . . . . . . . . . . . . . . . . . . . 1 x 1.5 mm2/ AWG 30...16 stranded wire
Wire size, others, max. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 x 2.5 mm2/ AWG 30...12 stranded wire
Terminal connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Spring-cage
Vibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IEC 60068-2-6
2...13.2 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±1 mm
13.2...100 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±0.7 g
Common electrical specifications:
Supply voltage, universal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21.6...253 VAC, 50...60 Hz
or 19.2...300 VDC
Max. required power, 5725A / 5725D . . . . . . . . . . . . . . . . . . . . . . . 2.8 W / 3.6 W
Isolation voltage, test / operation . . . . . . . . . . . . . . . . . . . . . . . . . . 2.3 kVAC / 250 VAC
Signal / noise ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . > 60 dB
Input specifications:
Frequency range, f/I conversion function . . . . . . . . . . . . . . . . . . . . 0.001 Hz to 50 kHz
Low cut o frequency (default value) . . . . . . . . . . . . . . . . . . . . . . . 0.0009 Hz
Low cut o frequency, (LCOF=YES) . . . . . . . . . . . . . . . . . . . . . . . . . 0.5 Hz (2 s)
Max. frequency, with input filter ON . . . . . . . . . . . . . . . . . . . . . . . . 50 Hz
Time range, period time function . . . . . . . . . . . . . . . . . . . . . . . . . 999.9 s to 20 µs
Low cut o period time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1111 s
Min. period time with input filter ON . . . . . . . . . . . . . . . . . . . . . . . . 20 ms
Response time (0...90%, 100...10%) . . . . . . . . . . . . . . . . . . . . . . . . < 1 period + 100 ms
Accuracy values
Specification Absolute accuracy Temperature coecient
Input to Display & Relays ≤ ±0.05%
≤ ±0.01% / °C
Input to Analog Output ≤ ±0.1%
EMC - immunity influence. . . . . . . . . . . . . . . . . . . . . . . . . < ±0.5% of span
Extended EMC immunity:
NAMUR NE 21, A criterion, burst . . . . . . . . . . . . . . . . . . . . < ±1% of span

10 5725V104-UK
Input types:
NAMUR input - acc. to EN 60947-5-6:
Trig-level LOW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≤ 1.2 mA
Trig-level HIGH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≥ 2.1 mA
Input impedance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 k / < 1.5 nF
Breakage detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≤ 0.1 mA
Short-circuit detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≥ 6.9 mA
Sensor supply - pin 44, fixed. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.3 V
Tacho input:
Trig-level LOW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≤ - 50 mV
Trig-level HIGH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≥ + 50 mV
Input impedance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≥ 100 k / < 1.5 nF
Max. input voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 VAC pp
Sensor supply - pin 44, programmable . . . . . . . . . . . . . . . . . . . . . . . 5...17 V / 20 mA
NPN / PNP input:
Trig-level LOW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≤ 4.0 V
Trig-level HIGH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≥ 7.0 V
Input impedance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.48 k / < 1.5 nF
Sensor supply - pin 44, programmable . . . . . . . . . . . . . . . . . . . . . . . 5...17 V / 20 mA
TTL input:
Trig-level LOW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≤ 0.8 VDC
Trig-level HIGH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≥ 2.0 VDC
Input impedance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≥ 100 k / < 1.5 nF
Sensor supply - pin 44, programmable . . . . . . . . . . . . . . . . . . . . . . . 5...17 V / 20 mA
S0 input acc. to DIN 43864:
Trig-level LOW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≤ 2.2 mA
Trig-level HIGH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≥ 9.0 mA
Input impedance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 758 / < 1.5 nF
Sensor supply - pin 44, fixed. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 V
Special voltage input:
User programmable trig-levels. . . . . . . . . . . . . . . . . . . . . . . . . . . . -0.05...6.50 V
Hysteresis, min . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 mV
Input impedance, selectable:
High Z . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≥100 k / < 1.5 nF
Pull up and pull down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.48 k / < 1.5 nF
Sensor supply - pin 44, programmable . . . . . . . . . . . . . . . . . . . . . . . 5...17 V / 20 mA
Special current input:
User programmable trig-levels. . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.0...10.0 mA
Hysteresis, min . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.2 mA
Input impedance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 k / < 1.5 nF
Sensor supply - pin 44, programmable . . . . . . . . . . . . . . . . . . . . . . . 5...17 V / 20 mA
Output specifications:
Display:
Display readout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -1999...9999 (4 digits)
Decimal point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Programmable
Digit height . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13.8 mm
Display updating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.2 times / s
Display response time, programmable . . . . . . . . . . . . . . . . . . . . . . . 0.0...60.0 s
Input frequency outside range and
NAMUR input sensor error is indicated by . . . . . . . . . . . . . . . . . . . . . Explanatory text

0,10 A
1,00 A
0 V 50 V 100 V 150 V 200 V 250 V
CURRENT
U
RELAY
5725V104-UK 11
Current output (5725D):
Programmable signal ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0...20, 4...20 & 20...0, 20...4 mA
Load (max.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≤ 800
Current limit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≤ 28 mA
Load stability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≤ 0.01% of span / 100
Programmable response time . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.1...60.0 s
Sensor error indication, at NAMUR input:
selectable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 / 3.5 / 23 mA / none
Output limitation at outside range:
on 4...20 and 20...4 mA signals . . . . . . . . . . . . . . . . . . . . . . . . . . 3.8...20.5 mA
on 0...20 and 20...0 mA signals . . . . . . . . . . . . . . . . . . . . . . . . . . 0...20.5 mA
Relay outputs (5725D):
Relay function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setpoint
Hysteresis, in % / display counts . . . . . . . . . . . . . . . . . . . . . . . . . . 0...100% / 0...9999
On and O delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0...3600 s
Power On delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.0...60.0 s
Sensor error action . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Make / Break / Hold
Max. voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250 VAC / VDC
Max. AC current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 A
Max. AC power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500 VA
Max. DC current, resistive load:
@ Urelay ≤ 30 VDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 ADC
@ Urelay >30 VDC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [1380 x U-2
relay x 1.0085Urelay] ADC
Graphic depiction of [1380 x U-2
relay x 1.0085Urelay]:
Observed authority requirements
EMC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2014/30/EU & UK SI 2016/1091
LVD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2014/35/EU & UK SI 2016/1101
RoHS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2011/65/EU & UK SI 2012/3032
EAC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TR-CU 020/2011
Approvals
EU RO Mutual Recognition Type Approval . . . . . . . . . . . . . . . . . . . . . MRA000000Z
DNV, Ships & Oshore. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TAA0000102
c UL us, UL 508. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E248256
Urelay
50 V 150 V0 V 100 V 200 V 250 V
Current
0.10 A
0.40 A
0.80 A
0.20 A
1.00 A
0.60 A
2.00 A
3.00 A

12 5725V104-UK
Sensor error indication in 5725, only available for NAMUR input
Condition Out of range limit Relay
behaviour
Analog
output value
Display
redaout
Sensor input type =
NAMUR and sensor
error detection = ON
> 6.9 mA Set to user
defined value:
HOLD. ACTIVE. DEACTIVE
or NONE
Set to user-defined value
(23, 0, 3.5 mA
or NONE)
”SE.SH”
< 0.1 mA ”SE.BR”
Input ”out of range” indication
Valid measurement range: Out of range limit Display readout
f to I function:
0.001 Hz to 50 kHz
< 0.0009 Hz (18 min. 31 sec.)
or
0.5 Hz (2.0 s) if L.COF=YES
(Low cut-off frequency)
If In.Lo is set to 0.000 Hz:
”0.0”
If In.Lo is set ≥ 0.001 Hz:
”IN.LO” - flashing
> 50.5 kHz ”IN.HI” - flashing
Period time function:
20 µs to 999.9 s
> 1111 s (18 min. 31 sec.)
(Low cut off time) ”IN.HI” - flashing
< 19.8 µs ”IN.LO” - flashing
Sensor error indication, inside and outside range
Display out of range Indication
Valid display value range: Out of range limit Display readout
-1999 to 9999 < -1999 ”-1.9.9.9.” - flashing
> 9999 ”9.9.9.9.” - flashing
Hardware error indication
Error explanation Error cause Display readout
Error in internal communication
(SPI etc.)
Permanent error in intercommunication
between microcontrollers ”HW.ER” - flashing
Error in checksum test of the
configuration in RAM Error in RAM ”RA.ER”- flashing
Error in checksum test of the
configuration in EEPROM Error in EEPROM ”EE.ER”- flashing
Error in OK check or checksum
test of the calibration data in
FLASH
Error in FLASH or
Calibration has not been performed or
Calibration data in FLASH are corrupt
”NO.CA”- flashing
! Error indications in the display blink once a second. The help text explains the error.

5725V104-UK 13
Connections
mA +
-
41 42 44 45 46
43
41 42 44 45 46
43 41 42 44 45 46
43
41 42 44 45 46
43 41 42 44 45 46
43 41 42 44 45 46
43
31 32
41 42 44 45 46
43 41 42 44 45 46
43 41 42 44 45 46
43
11 12 21 22 24 25 26
23
R1 R2
+
∼
+
+
Output:
Input:
Special current Special voltage Tacho
PNP
Supply:
NPN Contact (NPN)
Current
S0 TTLNAMUR
Relays
S0 TTL
+ supply 8.3 V + supply 17 V
+ supply 5...17 V+ supply 5...17 V
+ supply 5...17 V+ supply 5...17 V
+ supply + supply

I+
21
22
23
11
12
31
32
24
25
26
CPU
EEPROM
5725A & D
11223344
44
46
45
43
42
41
R1
R2
mA
VREG
5...17 V
fin
14 5725V104-UK
Block diagram
I
Output
Common
Relay 1 N.O.
Relay 1 N.C.
Common
Relay 2 N.O.
Relay 2 N.C.
Supply
Supply
21.6...253 VAC
or
19.2...300 VDC
Option D
Gnd.
Option D
Freq.
detector

5725V104-UK 15
Configuration / operating the function keys
Documentation for routing diagram.
In general
When configuring the 5725, you will be guided through all parameters and you can choose the settings which fit the
application. For each menu there is a scrolling help text which is automatically shown in the display if no key has been
activated for appr. 5 seconds.
Configuration is carried out by use of the 3 function keys:
1will increase the numerical value or choose the next parameter
2will decrease the numerical value or choose the previous parameter
3will save the chosen value and proceed to the next menu
If a function does not exist in the hardware, all parametres belonging to that function will be skipped in order to make
configuration as simple as possible. The configuration will not be saved until the end of the menu structure when the display
shows - - - -.
Pressing and holding 3will return to the previous menu or return to the default state ("Monitor") without saving the changed
values or parameters.
If no key is activated for 2 minutes, the display will return to the default state ("Monitor") without saving the changed values
or parameters.
Further explanations
Fast setpoint adjustment and relay test (only 5725D)
These menus are interactive and allow you to adjust the setpoints while the display is measuring the input signal. The front
LEDs will then indicate when the relays change state, thus easing the setpoint adjustment in many situations. By activating 1
and 2simultaneously, a relay test will be initiated and the relay will change state. The setpoint adjustment will be saved by a
quick press of 3. Holding down 3for more that 0.5 seconds will return the display to the default state (”Monitor”) without
changing the setpoint.
Password protection
Using a password will block access to the menu and parameters.
If the configured password is not known, please contact PR electronics support - www.prelectronics.com/contact.
5725D only: There are two levels of password protection.
Passwords between 0000 and 4999 allow access to the fast setpoint adjustment and relay test menus (using this password
blocks access to all other parts of the menu).
Passwords between 5000 and 9999 block access to all parts of the menu, fast setpoint and relay test (current setpoint is still
shown).
Additional features (from s/n > 121435001)
Out of range indication at f/I function
Out of range min. limit is < 0.0009 Hz / (18 min. 31 sec.).
- if the In.Lo value is set to ”0.0” Hz the display readout will be ”0.0” when the ”out of range” min. limit is reached.
- if the In.Lo value is set different from ”0.0” Hz the display readout will be ”In.Lo” - flashing - when the ”out of range” min.
limit is reached.
Low cut-off filter
The 5725 frequency indicator has a selectable low cut-off filter, which sets the display and output to 0% when the measured
frequency is ≤ 0.5 Hz (2 s). This filter allows the display to ignore extremely low frequencies from flowmeters and encoders
which are sometimes present when the process is at idle.
Faster analog output
The analog output response time can be adjusted to a fast 0.1 second, allowing the analog output to track faster changing
input signals.

16 5725V104-UK
Additional features (from s/n > 181101000)
Programmable display response time
The response time of the 5725 display readout can be configured independently of the analog output response time.
This feature ensures a stable and easy readout of unstable or jittering input signals.

1 2 1 2 1 2 1 21 2 1 2
PASS
TT 21
0000
9999
IN
TT 2229
TACH
*1
TR.LO
TT 31
0.05
6.45
3
TR.HI
TT 33
0.00
6.50
S.SUP
TT 37
5.0
17.0
Z.IN
TT 3436
HI.Z
PLUP
PLDN
Power up
10.00
LANG
TT 07
CZ
ES
IT
SE
FR
DE
DK
UK
TTL
NPN
PNP
S0
NAMUR
mA
1 21 2
TR.LO
TT 31
0.0
9.80
TR.HI
TT 33
0.2
10..0
3
3
3
3
3
3
3
3
3
3
3
3
3 3 3 3
3
1 2
5725V104-UK 17
Routing diagram for 5725A
If no key is activated for 2 minutes, the display will return to the default state "Monitor" without saving configuration
changes.
1Increase value / choose next parameter
2Decrease value / choose previous parameter
3Save the chosen value and proceed to the next menu
Hold 3Back to previous menu / return to default state "Monitor" without saving.
"Monitor"
∼ 3 sec.
"Start"
Hold
"Start"
*1 Only displayed if password is enabled (E.PASS = YES).

1 2
1 2
1 2
1 2
1 2
IN.UN
TT 38/39
IN.LO
HZ/KHZ
0.000
49.99
IN.HI
HZ/KHZ
0.001
50.0
FILT
TT 48
NO
YES
L.COF
TT 47A
NO
YES
HZ 3 3
1 2 1 2 1 2
DEC.P
TT 49
1111
111.1
11.11
1.111
DI.HI
TT 51
1999
9999
DI.LO
TT 50
1999
9999
333
TT 40/41 TT 44/45
1 21 2
IN.LO
mS/S
0.020
999.8
IN.HI
mS/S
0.021
999.9
3
TT 42/43 TT 46/47
S3
3
1 2
E.PAS
TT 77
NO
YES
1 2
N.PAS
TT 78
0
9999
3
3
3
3
*1
*4 *9 *10
*5
1 2
DI.RP
TT 51A
0.0
60.0
3
18 5725V104-UK
*1 Only displayed if password is enabled (E.PASS = YES).
*5 Only visible if max. (IN.LO,IN.HI) value is ≤ 50 Hz (f/I)
or ≥ 20 ms (period time) Default if visible = YES, else
deactivated.
*10 Out of range limit is < 0.0009 Hz (18 min. 31 sec.) when
L.COF = NO.
Out of range limit is 0.5 Hz (2 sec.) when L.COF = YES.
"Start"
"Start"
*4 Displays either Hz/kHz or s/ms for 1 sec. before actual value
is displayed.
When value hits digit-limit while scrolling, either Hz/kHz or
s/ms is displayed again for 1 sec. to show the user that the
new range is active.
*9 Minimum IN.HI value is automatically limited to 1 display
count above IN.LO.

3 3
1 2 1 2 1 2 1 21 21 2 1 2
PASS
TT 21
0000
9999
IN
TT 2229
TACH
*1
TR.LO
TT 31
0.05
6.45
3
TR.HI
TT 33
0.00
6.50
S.SUP
TT 37
5.0
17.0
Z.IN
TT 3436
HI.Z
PLUP
PLDN
Power up
10.00
LANG
TT 07
CZ
ES
IT
SE
FR
DE
DK
UK
TTL
NPN
PNP
S0
NAMUR
mA
1 21 2
TR.LO
TT 31
0.0
9.80
TR.HI
TT 33
0.2
10..0
3
3
3
3
3
3
3
3
3
3
3
3 3 3 3
3
1 2
F.SET
TT 18
REL1
REL2
SETP
TT 19/20
1 2
0.0
100.0
1 2
1999
9999
If RELU
= PERC
3
*3
If RELU
= DISP
1 2
1 2 1 21 2 1 2
SETP
TT 57
0.0
100.0
ACT1
TT 58/59
INCR
DECR
ERR1
TT 37
HOLD
ACTI
DEAC
NONE
HYS1
TT 60
0.0
100.0
3 3 3 3
1 2 1 21 2
SETP
TT 57
1999
9999
ACT1
TT 58/59
INCR
DECR
HYS1
TT 60
0
9999
3 3 3
1 2
1 2
RELU
TT 52/53
PERC
DISP
REL1
TT 5456
TT 6769
SKIP
33
If RELU
= PERC
If RELU
= DISP
OFF
SET 3
3
*2 *7
*6
3
5725V104-UK 19
Routing diagram for 5725D
If no key is activated for 2 minutes, the display will return to the default state "Monitor" without saving configuration
changes.
1Increase value / choose next parameter
2Decrease value / choose previous parameter
3Save the chosen value and proceed to the next menu
Hold 3Back to previous menu / return to default state "Monitor" without saving.
"Start" "Start"
"Monitor"
∼ 3 sec.
"Start"
Hold
"Start"
Same procedure
for REL2
Fast setpoint adjustment and relay test
1Increase setpoint
2Decrease setpoint
3Save and exit the menu
1and 2simultaneously = change relay
state.

1 2
1 2
1 2
1 2
IN.UN
TT 38/39
IN.LO
HZ/KHZ
0.000
49.99
IN.HI
HZ/KHZ
0.001
50.0
L.COF
TT 47A
NO
YES
HZ 3 3
TT 40/41 TT 44/45
1 21 2
IN.LO
mS/S
0.020
999.8
IN.HI
mS/S
0.021
999.9
3
TT 42/43 TT 46/47
S3
3
1 2
E.PAS
TT 77
NO
YES
1 2
N.PAS
TT 78
0
9999
3
3
3
*1
*4 *9 *10
1 2 1 2 1 2
ON.DE
TT 65
0
3600
PO.DE
TT 70
0
60
OF.DE
TT 66
0
3600
1 2 1 2 1 2
A.OUT
TT 71
020
420
200
204
RESP
TT 76
0.1
60.0
O.ERR
TT 7275
NONE
0mA
3.5mA
23mA
3
3 3
*8
3
*3
*7
3
1 2
FILT
TT 48
NO
YES
1 2 1 2 1 2
DEC.P
TT 49
1111
111.1
11.11
1.111
DI.HI
TT 51
1999
9999
DI.LO
TT 50
1999
9999
333
*5
1 2
DI.RP
TT 51A
0.0
60.0
33
20 5725V104-UK
*1.4 Not visible if both relay functions are OFF.
*8
*1 Only displayed if password is enabled (E.PASS = YES).
*5 Only visible if max. (IN.LO,IN.HI) value is ≤ 50 Hz (f/I)
or ≥ 20 ms (period time) Default if visible = YES, else
deactivated.
*10 Out of range limit is < 0.0009 Hz (18 min. 31 sec.) when
L.COF = NO.
Out of range limit is 0.5 Hz (2 sec.) when L.COF = YES.
*4 Displays either Hz/kHz or s/ms for 1 sec. before actual value
is displayed.
When value hits digit-limit while scrolling, either Hz/kHz or
s/ms is displayed again for 1 sec. to show the user that the
new range is active.
*9 Minimum IN.HI value is automatically limited to 1 display
count above IN.LO.
"Start"
"Start"
Same procedure
for REL2
*2 5725D only.
*3 Password 5000...9999:
FastSet and Relay Test features disabled.
(FastSet menus show the actual setpoints).
*6 Range depends on selected display scaling.
*7 Only visible for NAMUR input.
0mA only visible for A.OUT = 020 or 200
3.5mA only visible for A.OUT = 420 or 204
This manual suits for next models
1
Table of contents
Other PR electronics Measuring Instrument manuals

PR electronics
PR electronics 4510 User manual

PR electronics
PR electronics 5714 User manual

PR electronics
PR electronics 5514 User manual

PR electronics
PR electronics 4511 User manual

PR electronics
PR electronics 5511 User manual

PR electronics
PR electronics 5714 User manual

PR electronics
PR electronics PReview 5515 User manual

PR electronics
PR electronics 5714 User manual

PR electronics
PR electronics PRetrans 5115 Series User manual

PR electronics
PR electronics 5714 User manual