PIM60.241
Feb. 2022 / Rev. 2.0 DS-PIM60.241-EN www.pulsp wer.c m 3 / 17
All parameters are specified at 24V, 2.5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless therwise n ted.
1. Intended Use
This device is designed f r installati n in an encl sure and is intended f r c mmercial use, such as in industrial c ntr l,
pr cess c ntr l, m nit ring, measurement, Audi /Vide , inf rmati n r c mmunicati n equipment r the like.
D n t use this device in equipment, where malfuncti ning may cause severe pers nal injury r threaten human life with ut
additi nal appr priate safety devices, that are suited f r the end-applicati n. If this device is used in a manner utside f
its specificati n, the pr tecti n pr vided by the device may be impaired.
D n t use this device n AC 100V mains with m re than 1.9A l ad when the applicati n is sensitive t sh rt utput v ltage
dips during mains interrupti ns even with a length sh rter than 20ms.
2. Installati n Instructi ns
DANGER Risk of electrical shock, fire, personal injur or death.
– Turn p wer ff bef re w rking n the device. Pr tect against inadvertent re-p wering.
– D n t pen, m dify r repair the device.
– Use cauti n t prevent any f reign bjects fr m entering the h using.
– D n t use in wet l cati ns r in areas where m isture r c ndensati n can be expected.
– D n t t uch during p wer- n, and immediately after p wer- ff. H t surfaces may cause burns.
Obe the following installation instructions:
This device may nly be installed and put int perati n by qualified pers nnel. This device d es n t c ntain serviceable
parts. The tripping f an internal fuse is caused by an internal defect. If damage r malfuncti n sh uld ccur during
installati n r perati n, immediately turn p wer ff and send unit t the fact ry f r inspecti n.
Install device in an encl sure pr viding pr tecti n against electrical, mechanical and fire hazards. Install the device nt a
DIN rail acc rding t EN 60715 with the input terminals n the b tt m f the device.
Make sure that the wiring is c rrect by f ll wing all l cal and nati nal c des. Use appr priate c pper cables that are
designed f r a minimum perating temperature f +60°C f r ambient temperatures up t +45°C, +75°C f r ambient
temperatures up t +60°C and +90°C f r ambient temperatures up t +70°C. Ensure that all strands f a stranded wire
enter the terminal c nnecti n.
The device is designed f r p lluti n degree 2 areas in c ntr lled envir nments. N c ndensati n r fr st is all wed. The
encl sure f the device pr vides a degree f pr tecti n f IP20. The encl sure d es n t pr vide pr tecti n against spilled
liquids.
The device is designed f r verv ltage categ ry II z nes. Bel w 2000m altitude the device is tested f r impulse withstand
v ltages up t 4kV, which c rresp nds t OVC III acc rding t IEC 60664-1.
The device is designed as “Class f Pr tecti n” II equipment acc rding t IEC 61140.
The device is suitable t be supplied fr m TN, TT r IT mains netw rks. The c ntinu us v ltage between the input terminal
and the PE p tential must n t exceed 300Vac. A disc nnecting means shall be pr vided f r the input f the device.
The device is designed f r c nvecti n c ling and d es n t require an external fan. D n t bstruct airfl w and d n t
c ver ventilati n grid!
The device is designed f r altitudes up t 5000m (16 400ft). Ab ve 2000m (6560ft) a reducti n in utput current is required.
Keep the f ll wing minimum installati n clearances: 40mm n t p, 20mm n the b tt m, 0mm left and right side. Increase
the 0mm t 15mm in case the adjacent device is a heat s urce.
The device is designed, tested and appr ved f r branch circuits up t 20A with ut additi nal pr tecti n device. If an
external fuse is utilized, d n t use circuit breakers smaller than 6A B- r 4A C-Characteristic t av id a nuisance tripping
f the circuit breaker.
The maximum surr unding air temperature is +70°C (158°F). The perati nal temperature is the same as the ambient r
surr unding air temperature and is defined 2cm bel w the device. The device is designed t perate in areas between 5%
and 95% relative humidity.