Pure H2O quatreau Series User manual

Collection
PRODUCT MANUAL
Q-C-20/50
Q-CS-20/50

————————————————————
CONTENTS
PRODUCT MANUAL
————————————————————
Safety, Introduction & Specification 2
Installation & Commissioning 4
Soda Flow Rate Adjustment & 6
Unit Cleaning
Schematics 7
Fault Finding 10
Spare Parts 12
Removal, Transportation & Disposal 13
Ventilation Kit 14
EC Conformity 15
————————————————————
SAFETY
The unit should be isolated
from the electricity supply
before removal of any panels.
————————————————————
INTRODUCTION
————————————————————
The Q-C and Q-CS units are direct chill
cooler systems designed to provide
chilled water by passing water through
a stainless steel water coil in the “cold
block”. Additionally Q-CS units are
designed to provide chilled carbonated
water.
————————————————————
SPECIFICATION
————————————————————
See tables below and opposite for the the
models-
• Q-C-20
• Q-CS-20
• Q-C-50
• Q-CS-50
INTRODUCTION & SPECIFICATION

INTRODUCTION & SPECIFICATION

——————————————————————————————————————————
INSTALLATION AND COMMISSIONING
——————————————————————————————————————————
Locate the machine in a suitable enclosure, ensuring that there is suitable ventilation.
Care must be taken to ensure that hot air from the exhaust vent is not recirculated into
the air intake. This will have an adverse effect on performance and will reduce fridge life.
During operation air is drawn into the unit through the ventilation openings in the base
(and unit sides for the Q-C20) and then exhausted through the ventilation openings to
the rear of the unit.
MODEL: Q-C-20 / Q-C-50
MODEL: Q-CS-20 / Q-CS-50
INSTALLATION & COMMISSIONING

————————————————————
MODEL: Q-C-20 / Q-C-50
NOTE: At this stage do not connect the
unit to the electrical supply.
————————————————————
• Using 1/4” PE pipe, connect the
‘Water Out’ port, found on the front
right of the chiller, to the inlet on the
Quatreau system. This is located on
the left side of the system as you look
at it.
• Connect the ‘Water In’ port of
the chiller to the H2O port of the
Quatreau system.
• Check that the interconnection to the
Quatreau tap is fixed in place then
dispense water from the Quatreau
tap to purge air from the chiller.
• Once all air has been purged from
the system, connect the unit to the
electrical supply and turn on. The
compressor and fan will start
• After approximately 5-10 minutes,
the compressor and fan will stop as
the chiller has reached its normal
operating temperature.
NOTE: The time taken for the chiller to
reach operating temperature will vary
depending on ambient temperature,
humidity and the temperature of the
incoming water supply.
————————————————————
MODEL: Q-CS-20 / Q-CS-50
NOTE: At this stage do not connect the
unit to the electrical supply.
————————————————————
• Connect the ‘Water In’ port of the
chiller to the “H2O OUT” port of the
Quatreau Boiler system.
• Connect the Co2 Cannister (Set at
40-45 psi – 3 Bar).
• Turn water on.
• Using the Quatreau Tap, activate
the chilled water function until all
the air has been purged from the
system and a clean flow of water is
observed.
• Power system on and then
Immediately Select and then
Deselect the Sparkling Function. This
will allow the pump to receive the
water it needs.
• Once the pump has finished running
10-20 Seconds, power down the
Chiller Unit.
• Purge Co2 Water through the tap for
10 Seconds by selecting the Sparkling
Function.
• Power system on again and then
Immediately Select and then
Deselect the Sparkling Function. This
will allow the pump to receive the
water it needs.
• After approximately 10 minutes,
the compressor and fan will stop as
the chiller has reached its normal
operating temperature.
• The Chiller carbonator Unit is
commissioned.
INSTALLATION & COMMISSIONING

————————————————————
SODA FLOW RATE ADJUSTMENT & UNIT
CLEANING
————————————————————
The Soda flow rate is factory set to
dispense at 30 ml per second at a
gas pressure of 2.7BarG. However, if an
alternative flow rate is required follow the
steps below:
1. Locate the flow adjuster screw on the
side of the unit.
2. To increase the flow rate turn the
screw anti-clockwise.
3. To reduce flow rate turn the screw
clockwise.
4. Adjustments can be made with either
a large flat head screw driver or with a
6mm Alan Key.
5. It is recommended to make
incremental changes of no more
than a 1/8th of a turn at a time until
desired flow rate is achieved.
————————————————————
GENERAL CLEANING – OUTER CASING
————————————————————
Important: It is recommended that the
procedure should be performed at least
every 6 months.
Condenser
At regular intervals, determined by local
environmental conditions, the condenser
should be thoroughly cleaned with a
small stiff brush and/or a vacuum cleaner.
Do not use screwdrivers or other sharp
implements which may puncture the
tubes and damage the fins.
Warning: Failure to clean the condenser
can shorten the life of the compressor
causing premature failure of the unit.
Outer Panels
Clean the outside panels, pay particular
attention to the edges of the panels
where spillage could have ingressed
and the area around the base of the
unit. If necessary, remove the unit and
thoroughly clean around the base and
floor.
Sanitisation
Important: It is recommended that the
procedure is performed during initial
installation and at least every year at time
of service.
————————————————————
PREPARE THE UNIT
————————————————————
For this procedure you will need a
Pureh2o3 sterilisation system from The
Pureh2o Company.
1. Disconnect the power supply to the
chiller unit.
2. solate the water inlet to the chiller unit,
disconnect and insert into the ‘feed
in’ port on the Pureh2o3 sterilisation
system.
3. Connect the outlet of the Pureh2o3
system back into the chiller.
To sterilize the internal pipe work.
1. Activate the chilled water flow at the
tap.
2. Apply power to the Pureh2o3 system.
3. Allow chilled water to flow for 30
seconds.
4. Stop the chilled water flow.
5. Immediately disconnect the power to
the Pureh2o3 system.
6. Wait for 5 minutes then repeat the
process.
The O3 (ozone) emitted in this procedure
will effectively sterilise the internal pipe
work without the need for chemicals.
Recommission the Unit
Reverse steps 1 – 3, and allow the unit to
complete a cooling cycle.
FLOW ADJUSTMENT AND CLEANING

SCHEMATICS
————————————————————
MODEL Q-C-20/50
ELECTRICAL & WATER CIRCUITS
————————————————————

SCHEMATICS
————————————————————
MODEL Q-CS-20/50
ELECTRICAL & WATER CIRCUITS
————————————————————

FAULT FINDING
MODEL Q-C-20/50
——————————————————————————————————————————
SYMPTOM POSSIBLE CAUSE CORRECTIVE ACTION
——————————————————————————————————————————
No water Frozen block Thermostat capillary not fully inserted
dispensing into chiller block. Replace if necessary.
Thermostat out of calibration or faulty.
Replace if necessary
——————————————————————————————————————————
Warm Drinks Insufficient air flow Check that the condenser and air inlet are
through the fridge. not blocked or obstructed.
Check supply to the cooling fan. If supply
present replace fan.
If supply not present move on to the
compressor. (The supply to the fan and the
compressor are linked).
—————————————————————————————————
Compressor not Thermostat out of calibration or faulty.
running Replace if necessary.
—————————————————————————————————
Fridge failure If compressor & fan are running and there is
no cooling, return for repair.try.——————
————————————————————————————————————
Poor quality Incorrect CO2 pressure Check CO2 bottle, regulator and non-.
carbonation return. Supply pressure should be 40psi (2.7
bar),adjust or replace as necessary.
——————————————————————————————————————————
————————————————————
FAULT FINDING
————————————————————
Prior to any fault finding, please ensure all
water connections to the chiller are sound
and that the incoming water is turned on.
Also ensure that all electrical connections
to the chiller and in the chiller are secure
and in good condition, and that the
power is on.
If the above are satisfied, ensure that the
chiller has had adequate time to reach
operating temperature.
NOTE: When checking electrical
connections ensure the unit is
disconnected from the mains power
supply.

FAULT FINDING
MODEL Q-CS-20/50
——————————————————————————————————————————
SYMPTOM POSSIBLE CAUSE CORRECTIVE ACTION
——————————————————————————————————————————
No water Frozen block Temperature probe not fully inserted
dispensing into chiller block.
Temperature probe out of calibration or
faulty. Replace if necessary.
PCB Faulty. Replace if necessary.
——————————————————————————————————————————
No carbonated No CO2 pressure, Check CO2 bottle, regulator and non-
water check by return valve. Supply pressure shoudl be
operating pressure 40psi (2.7bar), adjust or replace as
relief valve on necessary.
carbonator can
—————————————————————————————————
Carbonator Can Check carbonator probe for possible short
not filling circuit to ground.
Check for pump timeout, cycle power off &
on then purge carbonator.
Check supply to water pump (230V AC), if
voltage present & pump inoperative -
replace pump.
If voltage not present & pump is not timed
out, check control board fuses. If necessary
replace control board.
——————————————————————————————————————————
Poor quality Incorrect CO2 pressure Check CO2 bottle, regulator and non-.
carbonation return. Supply pressure should be 40psi (2.7
bar),adjust or replace as necessary.
—————————————————————————————————
Air in carbonator Isolate the power supply and operate the
can carb water tap until gas is expelled. Allow.
gas to expel for 5 seconds. Switch on power
supply and allow the can to refil.
——————————————————————————————————————————

MODEL Q-CS-20/50
——————————————————————————————————————————
SYMPTOM POSSIBLE CAUSE CORRECTIVE ACTION
——————————————————————————————————————————
Poor quality Residue in carbonator After prolonged use, a surface film can
carbonation can develop within the carbonator can. This
can be removed by flushing the system
using a solution of citric acid.
—————————————————————————————————
Carbonator can If pump runs continuously, check
is overfilled connections to can level probe, if problem
persists replace the PCB.
——————————————————————————————————————————
Warm drinks Insufficient cooling air Check that the condenser is not blocked.
flow through the fridge Check supply to cooling fans (230V AC).
If supply present replace fans.
If supply not present move on to the
compressor. The supply to the fans and the
compressor are linked.
—————————————————————————————————
Compressor not Fridge overheat. Switch off the unit and
running allow to cool and ensure the condenser is
not blocked, the cooling fan is working and
there is sufficient ventilation. If overheating
persists return for repair.
If no overheat is found check voltage to
compressor (230V AC).
If voltage not present check the
temperature probes and replace if
required.
If voltage not present check control board
fuses. If necessary replace control board.
—————————————————————————————————
Control Check control board and main plug fuses.
not operating If necessary replace control board.
—————————————————————————————————
Fridge failure If compressor & fan are running and there
is no coling, return for repair.
—————————————————————————————————
FAULT FINDING

FAULT FINDING
————————————————————
SPARE PARTS
MODEL Q-CS-20/50 AND Q-CS-20/50
————————————————————

TRANSPORTATION AND DISPOSAL
————————————————————
REMOVAL, TRANSPORTATION & DISPOSAL
————————————————————
Important: Before removal from the
installation, ensure all electrical,
product and gas connections are
disconnected.
DISPOSAL OF SCRAP UNITS
It is illegal to simply scrap a refrigeration
unit. Before a unit can be scrapped
it must first have the gas removed by
a specialist using special equipment.
Please contact Pure H2O, who will be
happy to provide a quotation for disposal.
TRANSPORTATION
Important: This unit must be transported
in an upright position.
As with all refrigeration systems, irreparable
damage can be caused by laying the
unit on its side or even transporting upside
down. Where the unit is transported by
a carrier, the carton should always be
marked in a conspicuous manner, the
correct upright position in which it must be
handled.
If a unit has been transported incorrectly
it should be placed in the correct upright
position and left for 24 hours before
attempting to run the system.
Failure to observe the above precautions
could seriously damage the system, and
would void any warranty.

VENTILLATION KIT INSTALL
————————————————————
VENTILATION KIT INSTALLATION
————————————————————

EC CONFORMITY
————————————————————
EC DECLARATION OF CONFORMITY
————————————————————

The Pure H2O Company Ltd, Unit 21 Boundary Business Centre, Boundary Lane,
Woking, Surrey GU21 5DH United Kingdom pureh2o.co.uk
Q-C-20/50 & Q-CS-20/50 0619
Quatreau is a registered trademark of the Pure H2O Company Limited.
Copyright © 2019 The Pure H2O Company Limited. All rights reserved.
This manual suits for next models
4
Table of contents
Other Pure H2O Water Filtration System manuals
Popular Water Filtration System manuals by other brands

Panasonic
Panasonic ET-RFE300C operating instructions

Lancaster
Lancaster 7-LWT-UV009 Installation, operating and service manual

Crystal Mountain
Crystal Mountain SmartFlo SF-1 Replacement manual

ControlOMatic
ControlOMatic MegaChlor operating instructions

Insignia
Insignia NS-WFPTCC1 Quick setup guide

Miele
Miele DKF 11-R operating instructions