QEED QA-POWER-M User manual

SINGLE PHASE POWER METER
Isolated V/I converter -RS485 Modbus - Datalogger QA-POWER-M
SINGLE PHASE POWER METER
Isolated V/I converter -RS485 Modbus - Datalogger
Single-phase power meter
RMS
,and Voltage/Current Isolated.
Signal
Converter 1000 VDC / 600 VAC
,
10 A AC/DC
,
Variable frequency
measurement
.
Configurable via USB
,DIN rail mounting,
4 kV galvanic
isolation,
universal supply AC/DC. Configurable alarm contact,
RS485
Modbus and Analog output
.
DATALOGGING via USB
with pen drive
stick memory and download storage data on excel importable files.
RTC
Real Time Clock
integrated.
INPUT
VOLTAGE:Up to 1000 V DC / 600 V AC fully configurable via USB.
CURRENT: Up to 10 A AC/DC direct (more by using external CT).
101 2016
APPLICATION
Photovoltaic: parallel string voltage monitoring.
Energy Management: direct communication via RS485 Modbus to
all Master Modbus devices.
High Voltage AC/DC converter.
High Current AC/DC converter using external CT.
Local and Remote monitoring at the same time.
OUTPUT
CURRENT:0...20 mA programmable, max load 600 ohm.
VOLTAGE: 0...10 V programmable, min load resistence 2 kohm.
RS485 MODBUS:bus connection on the basis of the module or
terminal, dip-switch for setting address and baudrate.
CONTACT OUTPUT:Optomos contact, programmable NO alarm
contact by free interface software FACILE QA-POWER, retransmission
or storage.
QA-POWER-M
Pen Drive USB Datalogger !
POWER SUPPLY 10..40 Vdc, 20-28 Vac, 50-60 Hz
ABSORPTION Maximum 2.5 VA
PROTECTION INDEX IP20
ACCURACY
WORKING FREQUENCY DC or 1...400 Hz
TEMPERATURE COEFFICIENT < 200 ppm/°C
WORKING TEMPERATURE -15...+65°C
STORAGE TEMPERATURE -40°C... +85°C
ISOLATION 4 kV input, 1.5 kV between output,
RS485 and power supply.
HUMIDITY
ALTITUDE
terminals, RS485 bus and Supply connection ready on the
base of module (connector not included, on request).
CONNECTIONS Removable terminals 5.08 mm
CE STANDARDS
EN61000-6-4/2006 + A1 2011;
EN64000-6-2/2005;
EN61010-1/2010.
DIMENSIONS 17.5 x 100 x 112 mm (terminal excluded)
DATA LOGGER
Non-volatile memory. Log on USB OnTheGo port by Pen
Drive stick memory. RTC RealTime Clock integrated allows
you to manage the log with date and time.
CONFIGURATION
By free software FACILE QA-POWER-M to configure all of
the conversion parameters like span, zero, alarm contact
and log via USB port or via RS485. Dip-switch for setting
modbus address and baudrate.
MOUNTING DIN rail mounting with removable
Up to 2000 m s.l.m.
10...90% not condensing
MEASURE
0,5% F.S.
Irms, Vrms, Watt, Var, Va, Vpk, Ipk, Frequency,
Cosφ
, Energy bidirectional, THD
ENGLISH

INSTRUCTION MANUAL QA-POWER-M
INSTRUCTION MANUAL QA-POWER-M
DESCRIPTION:
The QA-POWER-M is an isolated VOLTAGE and CURRENT converter and SINGLE PHASE NETWORK ANALYZER. The module has a programmable
analog output (voltage or current) and a digital output (optomos). Thanks to the presence of the RS485 serial port can perform advanced
functions such as I / O Module with Modbus RTU protocol. The QA-POWER-M behaves as a slave device by placing Current or Voltage Input, n°1
AO and n°1 DO.
201 2016
ENGLISH
ELECTRICAL CONNECTIONS
POWER SUPPLY:
10...40 Vdc or 20...28 Vac - Connectors 16 and 17, or by T-BUS connector (optional tool)
on the base of the module (see the picture placed on the bottom of this page).
VOLTAGE/CURRENT INPUT (DIRECT INSERTION):
the input Voltage (LINE) has to be connected on terminals 2 (+) and 8, the Load has to
be connected on terminals 1 (+) and 6.
FOR VOLTAGE: up to 600 V AC, 1000 V DC.
FOR CURRENT: up to 10 A AC/DC.
You can set the measurement range as per your need using the FACILE QA- POWER-M
software or by RS485 using the modbus registers.
INSERTION WITH EXTERNAL CT:
ANALOG OUTPUT:
for Voltage analog output, connect terminals 31 and 29 (positive).
For ACTIVE current analog output, connect terminals 29 (positive) and 30. For PASSIVE
current analog output, connect terminals 30 (positive) and 31. Analog output supply:
13 Vdc, max 30 mA.
DIGITAL OUTPUT:
relay Output is an Optomos contact. Connection are with terminals 25 and 26. The
contact can be used like an pulse output (you can set by FACILE the value of the pulse)
or like Alarm contact (you can set the associated parameter by FACILE).
SERIAL OUTPUT RS485:
available on connectors 32 (GND), 33 (B-), 34 (A+), or by T-BUS connector to be mounted
on the module.
T-BUS CONNECTION (OPTION), needs T-BUS connector:
it may be affixed to the accessory T-BUS based on the module to bring both power and
serial communication. The number of modules supported by the bus is a function of the
power supply used (check the absorption of the modules).
the input Voltage (LINE) has to be connected on
terminals 2 (+) and 8 (as for the direct insertion).
The external CT (current transformer), must be
connected as follows:
- S1 terminal of the CT connected to the terminal 6;
- S2 terminal of the CT connected to the terminal 8.
For the connection of the LOAD to the CT, follow the
wiring diagram on the left side (INPUT P1 side and
OUTPUT P2 side.
WITH THIS CONFIGURATION, SET THE CURRENT
RATIO VIA FACILE SOFTWARE (SEE PAGE 3).

SETTING THE DEVICE VIA SOFTWARE FACILE QA-POWER-M
It is possible to use the program without connecting to the module,
in this mode you can SAVE the configuration on your PC, which can
then be sent to the QA-POWER-M at a later time.
SERIAL PORTS AVAILABLE:
Check the available COM ports, press the UPDATE button. Your PC
will assign a virtual COM connection with the QA-POWER-M. Press
START CONNECTION WITH THE DEVICE. It will confirm you the
connection was successful with the module. If the connection does
not happen, please check the RS485 serial connection (A +, B-), the
position of the dip-switches (switching off and on the device) and
the COM generated automatically by the device. After connecting,
you can proceed with the configuration of the device.
CURRENT RATIO, PULSE MANAGEMENT, FILTERS & CUT-OFF
SETTINGS:
This step on the FACILE QA-POWER-M software allow to to define the
Current Ratio in case of external CT presence, otherwise you can
measure direct current AC/DC up to 10 A.
The Pulse weight of the digital output can be setted by the WEIGHT
IMPULSE FOR ENERGY CALC (Wh).
RMS FILTER and AVERAGE FILTER COEFFICIENT are two different types
of filters that allow you to introduce a delay of the answer in order
to have more stabilty of the reading.
CUT OFF settings: you can set the cut off values for VOLTAGE,
CURRENT and POWER measurement. Under these value setted the
measurement will be Zero.
SETTING THE DEVICE VIA SOFTWARE FACILE QA-POWER-M
The programming of the module QA-POWER-M may be performed in two different ways:
· via the interface program free FACILE QA-POWER-M through the microUSB port on the module or via RS485 connection;
· via the RS485 serial connection (from terminal or T-Bus).
The QA-POWER-M has two microprocessors, you can configure the module by connecting it to the USB port of your PC without
the power lead, this is possible because the microprocessor that manages the configuration is powered directly from the USB port.
To use the program FACILE QA-POWER-M, log onto our website www.qeed.it in the PRODUCTS page, on the right menu, click on
DOWNLOAD SOFTWARE and then click FACILE QA-POWER-M, you can install the program on your PC. Once downloaded, install it
in the desired directory and run the program.
301 2016
ENGLISH

ANALOG OUTPUT: the first drop-down menu in the upper left allow you
to associate the analog output to a single selectable Vrms, Irms, Active
Power, Reactive Power, Apparent Power, Cosφ, Frequency.The mode
of the analog output is VOLTAGE or CURRENT. The QA-POWER-M has the
ability to scale the input and output as required, then select the
measurement range of input (INPUT BEGIN SCALE and INPUT END SCALE)
to assign to the analog output signal (OUTPUT BEGIN SCALE and
OUTPUT END SCALE ). Depending on the choices made in the two menu
will change the units of measurement values in the input and output. If
you select the MANUAL CONTROL VIA MODBUS, you can manage the
module as if it were an AO (Analog Output), thus freeing the analog
output from the input selected. The analog output will be handled via
RS485 Modbus RTU (see register map).
DIGITAL OUTPUT:the digital output default set is NOT ACTIVE. If you
want to ACTIVE the digital output please set it on the right window.
ALLARM / FAIL ANALOG OUTPUT: it is possible to use the analog output
to control any supervening anomaly Hardware HW FAIL, FAIL RTC Real
Time Clock anomaly that stores the date and time, FAIL EEPROM for the
anomaly on the microprocessor, FAIL LOG if an anomaly occurred during
data acquisition, UNDER RANGE scale of measurement set, OVER RANGE
scale of measurement set. It is possible to select multiple items in the
menu. In case of alarm the analog output will go to 21 mA or 10.5 V
depending on the selection made in the previous window.
ALARM WINDOW: you can activate the ALARM functionality (in the gray
box), on the digital output or on the analog output, or both
simultaneously. In this window you can manage HOW andWHEN activate
the alarm by selecting the options from the dropdown menu: MORE
THAN A THRESHOLD, LESS THAN A THRESHOLD, NOT BETWEEN TWO
THRESHOLD, BETWEEN TWO THRESHOLD. We therefore have the
possibility to insert the values of THRESHOLD and the value of
HYSTERESIS. In the case where it is selected the value of a Higher
threshold when the signal falls below, the alarm switched off at the
threshold value minus the value of hysteresis. In the event that you have
chosen the value of a Minor threshold, when the value exceeds the
threshold plus the hysteresis value, the alarm is disactivated. In the case
where it is selected between two thresholds, the hysteresis is external.
In case you have selected Not included between two thresholds, the
hysteresis is internal.
ALARM / FAIL DIGITAL OUTPUT: it is possible to use the digital output
to control any supervening anomaly Hardware HW FAIL, FAIL RTC Real
Time Clock anomaly that stores the date and time, FAIL EEPROM for the
anomaly on the microprocessor, FAIL LOG if an anomaly occurred during
data acquisition, UNDER RANGE scale of measurement set, OVER RANGE
scale of measurement set. It is possible to select multiple items in the
menu. By clicking on the "ENABLE ENERGY PULSE" is enabled the pulse.
STATE DIGITAL ALARM / FAIL allows you to define the status of contact
in case of alarm (NOT ACTIVE or ACTIVE).
FAIL MESSAGE / ANOMALY:
FAIL HW: problems in the measurement chain (electrical
connections, microprocessor that manages the
measurement, sensor disconnected or faulty).
FAIL LOG: problem on recording data (without the
availability of stick usb memory stick usb not recognized).
FAIL RTC: problem on backup battery (dead or defective).
FAIL EEPROM: problem microprocessor configuration (not
calibrated module, takes no configuration).
MODBUS COMUNICATION:
This is the last window of the device configuration. The left
column contains the parameters to be set for the
communication speed BAUDRATE (from 1200 to 115200),
the PARITY (None, Odd, Even), the STOP BIT (1 or 2), the
Modbus address to be assigned to the device . You do not
need to configure these parameters for the use of the
module with digital / analog output. It is possible to use
the module with RS485 serial output with Modbus output
analog and digital simultaneously.
LOGGING :
On the right side of the window you can enable the feature
LOG for the acquisition of data on usb pendrive. You can
name the log file by associating the extension .Xls, .Xlsx,
.Csv, .Txt, .Dat, .Logs. The default file is in text format. The
minimum sampling time is 1 second, the maximum is about
18 hours.
SETTING THE DEVICE VIA SOFTWARE FACILE QA-POWER-M
SETTING THE DEVICE VIA SOFTWARE FACILE QA-POWER-M
401 2016
ENGLISH

DATALOGGER QA-POWER-M
DATALOGGER QA-POWER-M
501 2016
Serial
Number Data (yyyy-mm-dd)
& Time Status
ID Vpk Ipk Vrms Irms P Q S Cosφ Freq Energy
Total Energy
-Output
value Output
type
Energy
+
12345678 2015/03/12-14-23-25 0 270 0 123 85.7 0.91 52 21 0
12345678 2015/03/12-14-23-26 0 270 0 123 88.3 0.92 52.6 21 0
12345678 2015/03/12-14-23-27 0 273 0 123 87.8 0.92 52.4 21 0
12345678 2015/03/12-14-23-28 0 273 0 123 88.1 0.93 52.1 21 0
The QA-POWER-M provides, on a local memory type PEN DRIVE USB (USB KEY) connected to the module via the microusb port, a series of information
concerning the operation of the module, alarm status, type of input, the output type, the reading of the measured data, the measure of the output value
from the module.
For each row correspond to a precise time reference. The module is equipped with an RTC RealTime Clock powered by a backup battery that lets you record
data with YEAR / MONTH / DAY / HOUR-MIN-SEC.
The first number listed is the SERIAL NUMBER of the module, which allows it to be uniquely identified.
The second column give you information about: DATE (YEAR / MONTH / DAY / HOUR-MIN-SEC).
It is then reported the STATUS ID (Registry STATE) in binary mode to 16 bit. The binary number corresponds to the Modbus register 40005 that represents
the state of the machine (Status: bit 0 = fail global, bit 1 = alarm, bit 2 = over range, bit 3 = under range, bit 4= ?, bit 5=dout status, bit 6 = fail hw, bit 7=fail
log, bit 8=fail rtc, bit 9=fail eeprom).
The following coloumns are Vpk, Ipk, Vrms, Irms, Active Power (P), Reactive Power (Q), Apparent Power (S), Cosφ, Frequency, Energy Total,
Energy +, Energy -, Output Value, Output type ( bit 0=Voltage/Current, bit 1-4=input Vrms, Irms, Active Power, Reactive Power, Apparent Power,
Cosφ, Frequency, bit 5 = fail ur, bit 6 = fail or, bit 7 = fail hw, bit 8 = fail log, bit 9 = fail rtc, bit 10 = fail eeprom, bit 11 = fail alarm, bit 12-13 = 1 threshold
over/1 threshold min/2 thresholds external/2 threshold internal, bit 14= Manual mode), this value follows the setting made via FACILE or via RS485.
HOW TO IMPORT LOG DATA FROM EXCEL VERSION BEFORE 2003:
it‘s possible to import the data stored on the USB Memory Stick at any time (even if the log is not finished). Once you open the file with Excel (or Open
Office), you will have to act on the functionality of the program for wrapping the data as described above. To do this, you can perform the following steps:
select the first column, go to the option data, click on TEXT COLUMN, then choose the option that provides for the separation of the data by tabs or commas,
the next step endorse the option POINT and COMMA.
LIVE DATA USING FACILE QA-POWER-M:
once confirmed the configuration, the FACILE QA-POWER-M allow you to see the
data reading by the device directly. Please remind that you have to supply the device
by external power supply .
ENGLISH

QUICK GUIDE QA-POWER-M
QUICK GUIDE QA-POWER-M
601 2016
MODBUS ADDRESS CONFIGURATION AND BAUD RATE
BY DIP-SWITCH
Through the dip-switch on the front panel of the module,
you can change the Modbus address and baud rate.
In the case in which all the dip switches are set to zero, the
module will take the calibration from EEPROM, otherwise
it will take parameters from a dip-switch.
In order to assign addresses more than 62 assignments
you need to take advantage of the interface software
FACILE QA-POWER-M. In order to assign values of baud
rates different from those selectable dip you should take
advantage of the interface software FACILE QA-POWER-M.
For changing the addresses and the baud rate it can also
be done by writing directly on the related registers.
POWER SUPPLY
10...40 Vdc or 20...28 Vac - Connectors 16 and 17, or by
T-BUS connector (optional tool) on the base of the
module.
POWER SUPPLY by T-BUS CONNECTION (T-BUS
connector required):
it is possible to mount the accessory T-BUS to carry both
power and serial communication. The number of modules
supported by the function of the power supply bus is used
(check the absorption of the modules).
INTERFACE PROGRAM FACILE QA-POWER-M
FACILE QA-POWER-M is the configuration software for
QA-POWER-M module.
The software is free and downloadable from the website:
www.qeed.it/category/software/facile-qa-power-m/ .
To communicate with the module you have to connect
via USB port directly on your PC.
You can configure the module via RS485 using the
registers’ map on the website www.qeed.it at the page of
device QA- POWER- M.
This document is the property of DEM S.p.A. Duplication or
reproduction is prohibited. The contents of this document
correspond to the products and technologies described. This
information may be amended or supplemented by technical
and commercial requirements.
Disposal of Electrical & Electronic Equipment (Applicable throughout the European Union and other European countries with separate
collection programs) This symbol, found on your product or on its packaging, indicates that this product should not be treated as household
waste when you wish to dispose of it. Instead, it should be handed over to an applicable collection point for the recycling of electrical and
electronic equipment. By ensuring this product is disposed of correctly, you will help prevent potential negative consequences to the
environment and human health, which could otherwise be caused by inappropriate disposal of this product. The recycling of materials will
help to conserve natural resources. For more detailed information about the recycling of this product, please contact your local city office,
waste disposal service or the retail store where you purchased this product.
LEDS - FRONT SIGNALS:
Power: power presence on the device.
Fail: presence of a failure/error on the device. It is
activated in the case have been activated by FAIL
messages on FACILE QA-POWER-M. One or more
events FAIL are active.
Rx, Tx: the module is communicating via RS485
(LED blinking).
Dout: digital output active.
MOUNTING INSTRUCTIONS:
To mount the card on DIN rail, we recommend to
place the top of the form on the edge of the bar
omega, then pushing the bottom until it clicks. The
module is equipped with a slider fastening that will
be pushed forward in order to ensure the perfect
fastening of the module on the bar.
NOTE: through the hole on the case of QA - POWER
- M (shown in the figure ) , you can access an internal
DIP SWITCH .Turning up the " DIP 1”you can activate
the dynamic terminating of the Modbus .
ENGLISH
Table of contents
Other QEED Measuring Instrument manuals