RadonTec AlphaAir Freshbox 100 WiFi User manual

AlphaAir Freshbox 100 WiFi
With and without Radon sensor
Manual
March 2021

RadonTec GmbH
Hauptstraße 5
89426 Wittislingen - Germany
Tel: (+49) 9076 - 919 98 35
Website: radontec.de
Shop: radonshop.com
Version: 01

3
Manual –AlphaAir Freshbox 100 WiFi
Scope of Contents
1 Introduction......................................................................5
2 Safety instructions............................................................5
2.1 Safety precautions during unit installation ..............6
2.2 Safety instructions for operating the unit................8
3 Intended use...................................................................11
4 Scope of delivery ............................................................12
5 Technical data.................................................................12
6 Dimensions.....................................................................14
7 Design and operating logic.............................................15
8 Assembly and operation.................................................17
8.1 Mounting................................................................18
8.2 Mains connection...................................................25
8.3 Connecting additional control units.......................27
8.4 Connecting the humidity sensor or СО2-sensor ....28
8.5 Control....................................................................29
Remote control...............................................................31
9 Emergency stop..............................................................52
10 Error codes/warnings .................................................53
11 Troubleshooting .........................................................54
12 Maintenance and servicing ........................................55
13 Transport and storage................................................58
14 Disposal ......................................................................59
15 Two year warranty .....................................................59

5
Manual –AlphaAir Freshbox 100 WiFi
1 Introduction
The AlphaAir Freshbox 100 WiFi is a ventilation unit with pre-
heating coil, enthalpy exchanger and WiFi connection. It is
designed for controlled air exchange in detached houses,
offices, hotels, cafés, conference rooms and other residential
and commercial spaces. It is used for heat recovery from the
extract air to heat the supply air.
2 Safety instructions
Read the operating instructions carefully before
using and installing the single room heat recovery
unit.
Read the operating instructions carefully and keep
them for as long as you use the AlphaAir Freshbox
100 WiFi.
When handing over the unit control, the operating
instructions must be handed over to the operator
taking over the unit.
The installation and operation of the unit must be
carried out in accordance with this user manual and
with the provisions of all applicable local and national
building, electrical and technical regulations and
standards.

6
Manual –AlphaAir Freshbox 100 WiFi
The warnings contained in this user manual must be
taken particularly seriously as they contain important
information regarding personal safety.
Failure to follow the safety instructions may result in
injury or equipment damage.
2.1 Safety precautions during unit installation
Before any installation or repair
procedure, the unit must be
disconnected from the power supply.
The unit must be earthed!
Do not operate the unit outside the
temperature range specified in the user
manual or in aggressive or explosive
environments.
Do not use damaged equipment or
wiring to connect the unit to the mains.
Observe the specific safety regulations
for the use of power tools when installing
the appliance.

7
Manual –AlphaAir Freshbox 100 WiFi
Unpack the appliance with care.
Unauthorised modifications to the mains
cable are not permitted. Do not bend the
mains cable. Do not damage the mains
cable. Do not place any objects on the
mains cable.
Do not place any heaters or other devices
in the immediate vicinity of the mains
cable of the unit.
All assembly and maintenance work may
only be carried out by electricians with a
valid electrical work permit for electrical
work on the units up to 1000 V after
carefully studying these operating
instructions.
Make sure that the impeller and the housing are not
damaged before connecting the unit to the mains. The casing
installations must be free of foreign bodies that could damage
the impeller blades.
Take measures to prevent contact with the fan to avoid
physical damage during unit testing and commissioning.
Misuse of the product or unauthorised modification is not
permitted.

8
Manual –AlphaAir Freshbox 100 WiFi
Take measures to prevent smoke, carbon monoxide and
other combustion products from entering the room through
open chimney flues or other fire protection devices. There
must be sufficient air supply for proper combustion and
exhaust of gases through the chimney of fuel burning
appliances to prevent backflow. The maximum permissible
pressure difference per dwelling unit is 4 Pa.
The conveyed air must not be aggressive to steel at the
temperature specified in the table in the "Technical data"
section.
2.2 Safety instructions for operating the unit
Do not touch the controller or remote
control with wet hands. Do not perform
maintenance on the unit with wet
hands.
Do not wash the unit with water.
Protect the electrical parts of the unit
from water penetration.
Use the appliance only as intended by
the manufacturer. Do not connect
tumble dryers or similar appliances to
the appliance or to the ventilation
system!

9
Manual –AlphaAir Freshbox 100 WiFi
Do not place any containers with water,
e.g. vases, on the unit.
Do not sit on the unit and do not place
any objects on the unit.
All work on the electrical connections of
the unit, maintenance and repair work is
only permitted when the unit is de-
energised.
Do not allow children to operate the
unit.
Do not damage the mains cable while
the unit is in operation. Do not place any
objects on the mains cable.
Keep explosive and flammable products
away from the unit.

10
Manual –AlphaAir Freshbox 100 WiFi
Do not open the control panel.
In case of unusual noises, disconnect the
unit from the power supply and contact
the Service Centre.
If the unit is in continuous operation,
check the mounting safety regularly.
Do not close or block the intake or
exhaust air openings of the unit so as
not to disturb the normal air flow.
Make sure that the air flow of the unit is
not directed towards appliances with an
open flame or candles.
The unit is not intended to be used by children,
physically or mentally handicapped persons, persons
with sensory disorders or persons without
appropriate qualifications.
Installation and connection work may only be carried
out by suitably qualified personnel after receiving
appropriate safety instruction.
The installation site of the appliance must be secured
against access by unsupervised children..

11
Manual –AlphaAir Freshbox 100 WiFi
3 Intended use
The unit is not suitable for the ventilation of swimming pools,
saunas, greenhouses, summer gardens and other humid
rooms.
Thanks to heat recovery and its energy-saving properties, the
unit is one of the crucial elements for energy-efficient, modern
house construction. The unit is a component of a ventilation
system and is not designed for stand-alone operation. The unit
is designed for continuous operation with a permanent power
supply.
The conveyed medium must not contain explosive and
flammable substances, chemical vapours, sticky substances,
fibrous materials, dust, soot, oil particles and other harmful
substances such as poisons, pathogens.
The ventilation system can be used in closed rooms at
temperatures from +1 °C to +40 °C and a relative humidity of
max. 70 %.
The dew point temperature of the conveyed air must be 2-3 °C
below the temperature of the enclosure surface so that no
condensate can form inside the enclosure.
The unit belongs to class I electrical installations. Protection
class against ingress of foreign bodies and water:
- IP22 for the mounted ventilation unit,
- IP44 for the motor units.

12
Manual –AlphaAir Freshbox 100 WiFi
4 Scope of delivery
Please check the completeness of the scope of delivery using
the following parts list:
1x ventilation system
1x operating manual
1x Mounting template
1x Fastening set
1x Magnetic sheet
1x Key
1x spigot
5 Technical data
Max. Delivery rate
30
m3/h
44
m3/h
60
m3/h
75
m3/h
100
m3/h
Supply voltage, V/50
(60)
1~ 230 Hz
Max. Fan power
consumption
20 W
23 W
29 W
37 W
53 W
Sound pressure level at
a distance of 3 m
13 dBA
20 dBA
27
dBA
33
dBA
39
dBA

13
Manual –AlphaAir Freshbox 100 WiFi
Power consumption of
the preheating coil
700 W
Max. Power
consumption of the
ventilation system
3,6 A
Conveying medium
temperature
-20 to +40 °C
Material of the casing
Painted steel
Insulation
10 mm (foamed rubber)
Efficiency of heat
recovery
96 %
94 %
89 %
85 %
83 %
Type of heat exchanger
Countercurrent heat exchanger
Heat exchanger
material
Enthalpy membrane
Supply air filter
G4, F8 (optional: F8 activated carbon,
H13)
Exhaust air filter
G4
Diameter of the
connection spigot
Ø 100 mm
Weight
31 kg

14
Manual –AlphaAir Freshbox 100 WiFi
6 Dimensions

15
Manual –AlphaAir Freshbox 100 WiFi
7 Design and operating logic
The warm, used exhaust air enters the ventilation system from
the room, is cleaned in the exhaust air filter and flows through
the heat exchanger. It is then led outdoors by the extract air
fan via the exhaust air pipe.
The fresh outside air flows into the ventilation system and is
cleaned in the supply air filter. The air then continues to flow
through the heat exchanger and is led into the room by the
supply air fan.
In the heat exchanger, the heat from the warm extract air is
transferred to the cold outside air. Here, the two air flows are
completely separated from each other. The heat recovery
minimises heat loss in the cold season and thus saves heating
costs.

16
Manual –AlphaAir Freshbox 100 WiFi
The AlphaAir Freshbox 100 WiFi ventilation system is equipped
with a pre-heating coil. This ensures automatic protection
against overheating of the heating register. The pre-heating
coil is located upstream of the heat exchanger and serves to
protect the heat exchanger against frost.
If the supply air temperature is below -3 °C, the pre-heating
coil automatically ensures that the supply air is heated so that
the average temperature of the extract air downstream of the
heat exchanger is not below +5 °C.
No condensate forms in the AlphaAir Freshbox 100 WiFi with
an enthalpy heat exchanger because the humidity of the
extract air is transferred to the supply air via the enthalpy
membrane.
The shutters open automatically when the fan motors are
switched on and close when they are switched off.
It is possible to connect an additional extract air spigot to
remove air from other rooms, for example the bathroom. The
exhaust air spigot is included in the scope of delivery.

17
Manual –AlphaAir Freshbox 100 WiFi
8 Assembly and operation
Read these operating instructions carefully before
installing the unit!
Sufficient maintenance access must be considered
when mounting the unit.
The recommended minimum distances between the
ventilation unit and the walls are as follows

18
Manual –AlphaAir Freshbox 100 WiFi
Hole spacing template
8.1 Mounting
Before mounting, make sure that the fan housing
does not contain any foreign parts such as foil or
paper.
The unit must be mounted on a smooth surface.
Mounting the unit on an uneven surface will cause
distortion of the casing and malfunction of the unit.

19
Manual –AlphaAir Freshbox 100 WiFi
1. Mark the holes using the enclosed drilling template.
Fix the template to the wall at the required height with
adhesive tape.
Use the template to mark the holes for the ventilation
pipes, the attachment of the unit and the outlet of the
power cable.
Lay all cables and pipes to the installation site before
starting the installation work.
2. Remove the template and drill two core holes for the
ventilation pipes with a diameter of 120 mm. When
installing the ventilation system with a two-room
connection, prepare a hole for the connection bend and
the laying of the ventilation pipe in the wall.
The connection bend and the ventilation pipes are
available as accessories. Drill the holes with a diameter of
8 mm and a depth of 90 mm. Insert the dowels. Remove
the perforated fields for the ventilation pipes from the

20
Manual –AlphaAir Freshbox 100 WiFi
template and reattach the template with the adhesive
tape.
3. Cut the ventilation pipes to the required length:
On the outside wall, the ventilation pipe must protrude by
the length required for mounting the outside ventilation
bonnet. Details can be found in the installation
instructions for the ventilation bonnet.
The external bonnet is not included in the scope of
delivery of the ventilation system and is available as an
optional accessory.