
STEP SIX: Install Heat Shield.
Place the Heat Shield on the
valve with the notched vertical
face between the Valve and the
Burner Pan. Ensure that the Heat
Shield is over the Valve
Assembly as shown in Figure 8
Heat Shield
Fi
ure 8
Pilot Adjust Screw
WARNING! HEAT SHIELD MUST BE INSTALLED TO PREVENT PREMATURE VALVE FAILURE AND/OR
VOIDING OF VALVE MANUFACTURER'S WARRANTY
CAUTION: The safety control valve must be protected to a max ambient temperature of 175° F.
Excessive heat to the valve is indicated by melted plastic on the valve body.
STEP SEVEN: Connecting Accessory Controller:
Using the 20' accessory control wiring attached to the two outside terminals of the Valve Terminal Block (see
Figures 6 and 7), connect the Switch Control Accessory Option (Remote, Thermostat, Switch, etc.) to valve.
CAUTION: This is a millivolt system. DO NOT connect to 115 V line. Safety controls damaged by heat or
115 volt electricity are not covered by warranty.
Switch Control Accessory Options:
ULTRA-SONIC WIRELESS REMOTE (Model "F10-AB)
INFRARED WIRELESS REMOTE WITH THERMOSTAT (Model "IRRC")
WALLSWITCH (Model"WS-1")
WALL THERMOSTAT (Model "TS-1")
WALL TIMER (60 MINUTE TIMER) (Model "WT-1")
CRACKLER Sound Generator option for F10 AB or IRRC (Model "CF5")
• Accessory REMOTE LOG HOUSE (Model "RH") is available for use as a heat resistant "log" in which the receiver
portion of Wireless remote option F10 AB or IRRC may be located.
• Accessory CRACKLER LOG HOUSE (Model "CH") is available for use as a heat resistant "log" in which the
CRACKLER Sound Generator option for both the F10 AB and IRRC wireless remotes may be located.
LIGHTING
CAUTION! DAMPER AND GLASS DOORS MUST BE FULLY OPEN BEFORE LIGHTING OR BURNING FOR
PROPER VENTILATION AND TO PREVENT HEAT DAMAGE TO VALVE
F, FX & CS burners use Natural Gas. Fill Burner Pan with the white sand provided with burner.
FA, FA-X & CA burners use LP Gas. Fill Burner Pan with black volcanic ash provided with burner.
STEP ONE: Pilot Lighting:
NOTE: The Gas Dial has complete control of gas to pilot and burner. The Gas Dial cannot be turned to "OFF"
without first depressing dial in "PILOT" position and then rotating clockwise to "OFF". (see Figure 7)
1. Depress and turn Gas Dial to "OFF" position. (Figure 9)
2. Set Accessory Control to "OFF" (Remote Control) or to lowest
temperature setting (Thermostat)
3. Wait at least 5 minutes to allow gas which may have
accumulated around burner to escape.
4. Turn Gas Dial to "PILOT" position. (Figure 9)
5. Depress and hold Gas Dial until air is bled and gas flows to pilot.
6. Light pilot. Continue to hold in the Gas Dial until the Pilot flame Fi
ure 9 PILOT ADJUSTMENT CAP
"OFF" "PILOT" "ON"
-PILOT OFF ON
remains lit when knob is released (approximately 60 to 90 seconds). If Pilot does not remain lit, repeat steps 1
through 5and allow more time after Pilot Lighting before releasing knob.
7. Turn Gas Dial to "ON". (Figure 9)
1/2" Figure 10
Pilot
Flame
Thermogenerator
STEP TWO: Pilot Adjustment
1. The PILOT FLAME should be steady and soft blue surrounding
approximately 1/2 inch of the thermocouple tip (see Figure 10).
2. If pilot flame adjustment is necessary, use a narrow long stem screw driver
to turn PILOT ADJUST SCREW. The PILOT ADJUST SCREW is
located on the Gas Valve (see Figure 9). Turn clockwise for less flame,
counter clockwise for more flame.
3
fire-parts.com