Raychem QuickStat User manual

QuickStat ®Thermostat
Installation & Operation Manual
General Information
Use of this Manual
This manual covers the installation and operation of the Raychem®
QuickStat®thermostat and must be used with the following document:
• QuickNet®System Installation Manual (H57704)
Important: For the Tyco Thermal Controls warranty and agency approv-
als to apply, the instructions included in this manual and product pack-
ages must be followed.
Features
QuickStat is an electronic thermostat that must be used with the
Raychem QuickNet floor heating mats.
QuickStat provides the following features:
• IncludesanintegratedClassA,Ground-faultCircuitInterrupter(GFCI)
at120V.IftheQuickStatispoweredat208Vor240V,aseparate
GFCImustbeused.
• Operatesat120V,208V,240V50/60Hz.
• Switchesonyourheatingsystematpredeterminedtimesondifferent
days of the week.
• Offers4periods(calledevents)eachdaythatyoucansetatdifferent
temperatures.
• Comeswithapreprogrammedschedulethatissuitableformost
installations.However,youcancustomizethisprogramanytimeyou
wish.
• Allowsyoutoresetthethermostattofactorysettings.
• Changesthestarttimeofaheatingperiodautomaticallysothatthe
desired temperature is reached at the time that you set.
• Controlsthetemperatureofthefloorthroughatemperaturesensor
that is placed in the floor construction.
Specifications
Approvals
C US
LISTED
2D03
E255369
Technical Data
SupplyVoltage 120V,208V,240V±15%,50/60Hz
Maximum switching current 15 A
Wiring 12AWGto22AWG
GFCI ClassA,5mAtriplevel(at120Vonly)
Temperature control range 40 to 104°F (5 to 40°C)
Ambient temperature range
Thermostat 32 to 104°F (0 to 40°C)
GFCI –31to149°F(–35to65°C)
A
B
C
Kit contents
A 1 QuickStat thermostat
B 2 Mounting screws
C 1 Floor temperature sensor 10 ft (3m)

Installation
Important: This thermostat must be installed according to all national
and local electrical codes. The installation must be performed by quali-
fied personnel.
Locating the floor temperature sensor
The floor temperature sensor is installed under the floor surface. See
the QuickNet System Installation Manual (H57704), Section 6, for more
details.
Ifrequired,thesensorcablecanbeextendedtoabout300ft(91m).
Wiring the thermostat
WARNING:TURNOFFTHEPOWERTOTHECIRCUITATTHEMAIN
POWERPANELTOAVOIDELECTRICSHOCK.
WARNING:SHOCKHAZARD.TOPREVENTSHOCK,THEQUICKNET
FLOORHEATINGMATMUSTBECONNECTEDTOGROUND.
WARNING:SHOCKHAZARD.THISDEVICEDOESNOTPROTECT
AGAINSTELECTROCUTIONWHENPOWEREDAT208VOR240V.A
SEPARATEGROUNDFAULTCIRCUITINTERRUPTER(GFCICLASS
A) MUST BE USED.
WARNING:ENSURETHATTHELINEWIRESARECONNECTED
TOTHEPROPERTERMINALS.FAILURETODOSOCOULDCAUSE
SERIOUSBODILYINJURYORDEATH.
1. Connect power to the thermostat’s line terminals marked “L1 (L)”
and “L2 (N)”. For 120-V installations, be sure the neutral wire is
connected to “L2 (N)”.
2. Connect the floor heating cold lead to the load terminals marked
“Load 15 A Max”.
3. Connect the floor heating cold lead braid (ground) to the supply
ground in the electrical junction box.
4. Connect the floor temperature
sensor to the screw-less
terminals marked “Sensor”.
Push on the terminal spring
with a screwdriver and
insert the wires.
Mounting the thermostat in the electrical box
1. Use a screwdriver to remove the cover.
2. Mount the thermostat in the wall socket and re-attached the cover.
Thermostat Controls and Display Symbols
The following figure shows the thermostat controls:
Reset
GFCI
Test
R
Reset button
Red light indicating
ground-fault
Test button
Pin button for
adjusting clock
Adjustment up
OK - accept
Digital
display
Adjustment down
Reset button for
factory settings
The following figure shows the symbols that appear in the display
window while you are programming:
L1 (L)
L2 (N)
240/(120)VAC
15 A
Max.
QuickStat®
GFCI Class A
LINE
LOAD
SENSOR
1/4" (6 mm)
Strip length
Line (black)
Line 2 (red) or Neutral (white)
Cold lead
Cold lead
QuickStat Installation & Operation Manual
2
Supply
ground
Cold lead
ground
Wire nut
Clock function
Manual mode
Time and
temperature
Day number
4-event symbol:
Wake
Night
Out
Home
% switch-on time
Heating on
L1 (L)
L2 (N)
240/(120)VAC
16A
Max.
QuickStat
®
GFCI Class A
LINE
LOAD
SENSOR
CAUTION:
High Voltage - Disconnect
power supply before servicing
DUAL VOLTAGE 50/60 Hz
3840W/240VAC (16A)
1920W/2120VAC (16A)

Initializing the Thermostat
Setting the thermostat into operation
The first time you power up the thermostat, the time and day will flash
andmustbeset.Youwillalsoneedtoselectthetimescale(12hor24
h)andtemperaturescale(°For°C).Ifyouneedtoadjustthetimeor
day in the future, i.e. for for daylight savings time, simply insert a pin
into the hole ( ) and make the necessary adjustments. Setting time and
temperature scale can also be done in the Advanced Settings and Read-
Out section on page 5.
Setting the current time
Press the UP ( ) or DOWN ( ) buttons to set the correct time and
press the OK ( ) button.
Display Actions Result
Setting the current day
Then press the UP ( ) or DOWN ( ) button to set the correct day
of the week and press the OK ( ) button.
Display Actions Result
Setting the temperature and time preferences
Press the UP ( ) button to select 12 hour or 24 hour clock and to
select Fahrenheit or Celsius and press the OK ( ) button.
Display Actions Result
Testing GFCI (for 120 V only)
YoumusttesttheGFCItoverifycorrectinstallationandfunction.
To check the GFCI:
1. Testing can only be performed if the thermostat has a heating
demand.
2. Adjust the set point until the heating symbol ( ) appears, use the
( ) button, to increase the temperature. Wait 10 seconds to let
the thermostat adjust to the new set point.
3. Press the “TEST” button.
The test is successful if the red light on the thermostat lights, and the
displaysignsdisappear.Ifthisdoesnotoccur,checktheinstallation.
1.PresstheRESETbuttontoresettheGFCI.Theredlightshould
disappear and the display will return to normal appearance.
2. Press the OK ( ) button to cancel the previously set temperature.
3.Ifthetestfails,checkyourheatingcableandthethermostat.
IftheGFCItripsinnormaloperationwithoutpressingtheTESTbutton,
there could be a ground fault. To check whether it is a ground fault or
nuisancetripping,pressRESET.Iftheredlightturnsoffanddoesnot
come on again, it was nuisance tripping and the system is functioning
properly.Ifthegroundfaultcannotbereset,thereisagroundfault.
Check your heating cable, the sensor cable and the thermostat. Replace
if necessary.
Care and maintenance
YoushouldperformtheGFCItestmonthly.
Factory settings
The following table shows the default settings that are programmed into
thethermostatfromthefactory.Youcanacceptthefactorysettings,or
customizethemtomeetyourneeds.SeeProgrammingonpage4to
customizeyoursettings.
Ifyouwishtoresetthethermostattofactorysettings,simplypushthe
pin button marked “R” for 3 seconds and the thermostat returns to
factory settings. Time, day and scale for time (12h, 24h) and tempera-
ture (ºF, ºC) read-outs are also reset.
77ºF / 25ºC
68ºF / 20ºC
Day 1 - 5
Day 6 - 7
Time
4-event time and temperature
77ºF / 25ºC
68ºF / 20ºC
6:00 a.m.
77ºF / 25ºC6:00 a.m.
8:00 a.m.
4:00 p.m.
10:00 p.m.
4-event sequence
Hi-Low temp.
Scale
Adaptive control
5:2
104ºF / 41ºC
12 H / ºF
ON
OFF / OFF
68ºF / 20ºC11:00 p.m.
Other settings
Temperature
QuickStat Installation & Operation Manual
3

Daily Use of the Thermostat
4-event clock mode
Each day has been split into 4 events describing a typical day. When the
thermostat is in 4-event mode it will automatically adjust according to
the required temperature and required time. The factory preset program
has 5 days with 4 events, and 2 days with 2 events. For more details,
see Programming.
4-event clock mode:
The clock function symbol ( ) and one of the 4-event
symbols ( ) will be indicated.
For more details, see Programming.
Temporary override:
To temporarily override the temperature in the 4-event
schedule program, press the UP ( ) or DOWN ( )
button once, to show the temperature, and press again
to increase or decrease the temperature. The display will
flash for 5 seconds, and will then revert to the time. The
override will operate until the next programmed event
when the unit will resume the automatic program.
Cancel comfort mode:
To cancel the override state, press the OK ( )
button twice.
Permanent override:
During holidays, the scheduled 4-event program can be
overridden. Press the OK ( ) button, and then the UP ( )
or DOWN ( ) button until the override temperature is set.
The unit will operate at this temperature until you change
the temperature or cancel the permanent override state.
Cancel manual mode:
To cancel the permanent override state, press the OK ( )
button once, and the unit will resume automatic function.
Turning thermostat off:
To turn the thermostat OFF, press the DOWN ( ) button
until you reach 41ºF, press the OK ( ) button, then press
the ( ) once more.
DO NOT USE THE TEST BUTTON ON THE GFCI TO
SWITCH OFF THE HEATING SYSTEM. TheGFCIautomati-
cally resets after a power outage.
Programming
4-event time and temperature
The table below shows the default time and temperature settings, how-
ever, you can easily change each setting as needed. For example, in the
morning you may want the floor to be warm at 7:00 a.m. and the tem-
perature to be 80ºF, and so on for other events.
Simply follow these steps:
Press the OK ( ) button for 3 seconds and the start time displays.
Press the UP ( ) or DOWN ( ) button until you reach your desired
time. Press the OK ( )buttontoconfirm.Yourselectedtimedisplays.
Then, press the UP ( ) or DOWN ( ) button until you reach your
desired temperature. Press the OK ( )buttontoconfirm.Yourselected
temperature displays.
Repeat these two actions for the remaining events.
These settings will be valid with days 1-5 showing on the display. To
program the days 6 and 7, repeat the above. Days 6 and 7 are usually
Saturday and Sunday, and only have two events.
Thetemperaturecanbesetwithintherangeof41°Fto104°F.Itisalso
possible to select the heating OFF at that event by reducing the setting to
41ºF, and then pressing the ( ) once more.
QuickStat Installation & Operation Manual
4
Wake
settings
Out
settings
Day 6 - 7
Day 1 - 5 Time Temperature
Time Temperature
Press OK ( ) button for 3 seconds to begin programming
Home
settings
Night
settings
Wake
settings
Night
settings

Advanced Settings and Read-Out
Press both the UP ( ) and DOWN ( ) buttons together
for3seconds.“INFO”isdisplayed.
Press the UP ( ) button until you reach the desired
sub menu. Select the sub menu with the OK ( ) button.
Monitoring energy consumption
The thermostat calculates the average time it has been
switched on allowing you to monitor your energy con-
sumption. The thermostat displays the total switch-on
time as a percentage for the last 2 days, 30 days or 365
days.
Calculation of operational costs per day:
(switch-on time:100) x kW x kWh-price x 24 h per day
Example:
Read-out: 30% in the latest 365 days
Sizeofheatingsystem:1.2kW(asktheinstaller)
Cost of power: 0.2 USD/ kWh - Calculation:
(30:100) x 1.2 kW x 0.2 USD/ kWh x 24 h = 1.7 USD per day
2 days
30 days
365 days
Software version
Temperature sensor
Press the UP ( ) or DOWN ( ) button to show the dif-
ferent readouts.
No changes can be made here. Use the OK ( ) button to
end.
4-event sequence
The present event sequence flashes: Days 1-5, followed
by days 6-7. To change, press the UP ( ) button until
you have days 1-6 and then day 7 flashing, or all 7 days
are flashing. Select the required sequence with the OK ( )
button.
5-2: 4 events in 5 days +
2 events in 2 days.
6-1: 4 events in 6 days +
2 events in 1 day
7-0: 4 events in 7 days
Maximum and minimum allowed temperature range
The temperature setting range of 41ºF to 104ºF can be
limited to prevent a too high or too low temperature from
being selected.
Set the maximum allowed temperature.
Use the UP ( ) or DOWN ( ) button to
increase or reduce and the OK ( ) button
to accept.
Next “LoLi” is displayed.
Press the OK ( ) button to continue.
Set the minimum temperature that the
floor should never fall below. Use the UP
() or DOWN ( ) button to increase or
reduce and the OK ( ) button to accept.
Note:ItispossibletoselecttheheatingOFFasyour“LoLi”settingby
reducing the setting to 41ºF, and then pressing the ( ) once more.
Time and temperature scale selection
YoucanselecteitherForCscale,and12or24hourclock
as follows:
Press the UP ( ) or DOWN
() button to change settings.
Confirm the required scale
with the OK ( ) button.
Adaptive function
This function enables the thermostat to calculate when
it needs to switch ON so that the required temperature
is reached at the set time. With a start time of 7:00 a.m.
therefore, the thermostat may switch ON as early as 6:00
a.m. so that the desired temperature of 77ºF is achieved
by 7:00 a.m. Without this function set, the thermostat will
start to heat at the time you set.
Press the DOWN ( ) button to switch
between on and off.
Press the OK ( ) button to confirm.
Ending the programming sequence
Press the OK ( ) button to end programming and to
return to scheduled program.
QuickStat Installation & Operation Manual
5

Sensor Testing
Ifthesensorisdisconnectedorshort-circuited,theheatingsystemis
turned off. Test your sensor according to the following resistance table:
Error Codes
E0:Internalerror.Thethermostatmustbereplaced.
E2: External sensor short-circuited or disconnected.
Sensor
Temp (˚C) Temp (˚F) Value (ohm)
–10 –14 64000
0 32 38000
10 50 23300
20 68 14800
30 86 9700
QuickStat Installation & Operation Manual
6
© 2009 Tyco Thermal Controls LLC H57225 06/09
Worldwide Headquarters
Tyco Thermal Controls
307 Constitution Drive
Menlo Park, CA 94025-1164
USA
Tel (800) 545-6258
Tel (650) 216-1526
Fax (800) 527-5703
Fax (650) 474-7711
www.tycothermal.com
Canada
Tyco Thermal Controls
250 West St.
Trenton, Ontario
Canada K8V 5S2
Tel (800) 545-6258
Fax (800) 527-5703
Important: All information, including illustrations, is believed to be reliable. Users, however,
should independently evaluate the suitability of each product for their particular application.
Tyco Thermal Controls makes no warranties as to the accuracy or completeness of the
information, and disclaims any liability regarding its use. Tyco Thermal Controls' only
obligations are those in the Tyco Thermal Controls Standard Terms and Conditions of Sale
for this product, and in no case will Tyco Thermal Controls or its distributors be liable for
any incidental, indirect, or consequential damages arising from the sale, resale, use, or
misuse of the product. Specifications are subject to change without notice. In addition, Tyco
Thermal Controls reserves the right to make changes—without notification to Buyer—to
processing or materials that do not affect compliance with any applicable specification.
Tyco, QuickNet and QuickStat are trademarks of Tyco Thermal Controls LLC
or its affiliates.

Instructions d’installation et
d’opération du thermostat
QuickStat ®
Information générale
Utilisation de ce manuel
Ce manuel couvre l’installation et l’utilisation du thermostat Raychem®
QuickStat®, et doit être utilisé avec le document suivant :
• Manuel d’installation du système QuickNet®(H57704)
Important : La garantie de Tyco Thermal Controls et les homologations
ne sont valides que si les instructions de l’emballage et du présent
manuel sont respectées.
Caractéristiques
QuickStat est un thermostat électronique qui doit être utilisé avec les
tapis chauffants Raychem QuickNet.
Caractéristiques du thermostat QuickStat :
• Inclusuninterrupteur(GFCI)claseAà120V.SileQuickStatest
utiliséà208Vou240V,uninterrupteurdemiseàlaterreadditionnel
doit être utilisé.
• Fonctionnesous120V,208V,240V50/60Hz.
• Alimentevotresystèmechauffantàdesheuresprédéterminéespour
les différents jours de la semaine.
• 4périodes(ouévénements)parjourpourleréglagedetempératures
différentes.
• Programmestandardconvenantpourlaplupartdesinstallations.
• Ceprogrammepeutêtrepersonnaliséàvolonté.
• Réinitialisationpourretrouverlesréglagesd’usineduthermostat.
• Préchauffageautomatiquepourquelatempératuredésiréesoit
atteinteàl’heureprogrammée.
• Règlelatempératuredusolaumoyend’unesondeincorporéedansla
construction du plancher.
Spécifications
Approbations
C US
LISTED
2D03
E255369
A
B
C
Contenu de kit
A 1 thermostat QuickStat
B 2 vis de fixation
C 1 sonde de température de plancher avec fil de 3 m (10 pi)
Caractéristiques techniques
Tension d’alimentation 120 V, 208 V, 240 V ±15%,
50/60Hz
Capacité de commutation 15 A
Câblage Fils12AWGà22AWG
Disjoncteur différentiel Classe A , point de consigne 5
ma(à120vseulement)
Gammederéglagedelatempérature 5à40°C(40à104°F)
Gammedetempératureambiante
Thermostat 0à40°C(32à104°F)
Disjoncteur –35à65°C(–31à149°F)

8
L1 (L)
L2 (N)
240/(120)VAC
16A
Max.
QuickStat
®
GFCI Class A
LINE
LOAD
SENSOR
CAUTION:
High Voltage - Disconnect
power supply before servicing
DUAL VOLTAGE 50/60 Hz
3840W/240VAC (16A)
1920W/2120VAC (16A)
Installation
Important: L’installation de ce thermostat doit être conforme aux codes
de l’électricité national et local. Elle doit être faite par un technicien
qualifié.
Position de la sonde de température
La sonde de température doit être installée sous la surface du plancher.
Voir le manuel d’installation du système QuickNet (H57704), chapitre 6,
pour plus de détails. Si nécessaire, la longueur du câble de la sonde peut
être prolongée jusqu’1 m (300 pi).
Câblage du thermostat
ATTENTION:POURÉVITERLESCHOCSÉLECTRIQUES,ISOLERLE
CIRCUITD’ALIMENTATIONAUNIVEAUDUTABLEAUDEDISTRIBUTION
ÉLECTRIQUE.
ATTENTION:RISQUEDECHOC;POURÉVITERTOUTRISQUEDE
CHOCÉLECTRIQUE,LETAPISDECHAUFFAGEDUSOLDOITÊTRE
RELIÉÀLATERRE.
ATTENTION:RISQUEDECHOC.CEDISPOSITIFN’ESTPAS
PROTÈGÉCONTRELESCHOCSÉLECTRIQUES,LORSQUEÉNERGISÉÀ
208VOU240V.UNINTERUPTEURDEFUITEÀLATERRE(CLASSEA)
DOITÊTREUTILISÉ.
ATTENTION:ASSUREZVOUSQUELESFILSSOIENTRACCORDÉS
CORRECTEMENTAUXBORNIERS.IGNORERCECIPOURRAITCAUSER
DESDOMMAGESCORPORELSOUDÉCÈS.
1. Brancher les fils de l’alimentation secteur du thermostat aux bornes
marquées«L1(L)»et«L2(N)».Pourinstallationà120V,
s’assurerquelefilduneutresoitraccordéàlaborne“L2(N)”.
2.Raccordezlefilfroiddusystèmedechauffageauxbornesmarquées«
Load 15 A Max ».
3. Brancher le faisceau de fils froids du système de chauffage de sol
(terrre)àmiseàlaterredel’alimentationdanslaboîtedejonction
électrique.
4. Brancher la sonde de température
du plancher aux bornes sans
vis marquées « Sensor ».
Appuyer sur le ressort de la
borne avec un tournevis et
engager les fils dénudés.
Montage du thermostat dans la boîte électrique
1.Àl’aided’untournevis,retirerlecouvercle.
2. Monter le thermostat dans la prise murale et replacer le couvercle.
Commandes du thermostat et symboles affichés
La figure ci-dessousindique les commandes du thermostat :
La figure ci-dessous illustre les symboles qui apparaissent sur ’afficheur
pendant la programmation :
L1 (L)
L2 (N)
240/(120)VAC
15 A
Max.
QuickStat®
GFCI Class A
LINE
LOAD
SENSOR
6 mm (1/4 po)
Dénuder
Phase (noir)
Phase 2 (rouge) ou neutre (blanc)
Fil froid
Fil froid
Fonction horloge
Mode manuel
Heure et
température
Jourde
la semaine
Symboles 4 événements:
Réveil
Nuit
Départ
Retouràlamaison
% chauffage
Chauffage actif
Reset
GFCI
Test
R
Bouton de réarmement
Voyant rouge
signalant un court-
circuitàlaterre
Bouton de test.
Mini-bouton de
réglage de l'horloge
Bouton PLUS
Bouton OK - Accepter
Afficheur
BoutonMOINS
Mini-bouton
de réinitialisation
Instructions d’installation et d’opération du thermostat QuickStat
Mise à la terre
alimentation
Fil froid de mise
à la terre
Capuchon
de connexion

9
Initialisation du thermostat
Avant la mise en service du thermostat
Lorsquevousbranchezlethermostat,l’heureetlejourclignotentpour
vous rappeler qu’ils doivent être programmés. Après avoir réglé l’heure
etlejour,vouspouvezchoisirentrel’horloge12heuresou24heures
etl’échelledetempérature(°For°C).Sivousdevezréglerl’heureoule
jourdanslefutur,parexemplepourlepassageàl’heured’été,ilsuf-
fit d’intrduire une épingle dans le petit trou ( ) et de faire les réglages
nécessaires. Le mode d’application del’heure et l’échelle de température
peuvent également être changés dans la section Réglages avancés et
Affichage, page 5.
Setting the curent time
AppuezsurleboutonPLUS( )ouMOINS( )jusqu’àobtenir
l’heredésirée,appuyezsurleboutoOK( ).
Affichage Actions Résultat
Jour dela semaine
ÀlaidedesboutonsPLUS( )etMOINS( )choisissezlejourde
lasemaieactueletappuyezsurleboutoOK( ).
Affichage Actions Résultat
Réglage des préférences de température d’heure
AppuyezsurleboutonPLUS( ) pour sélectionner l’horloge 12
heures (AM/PM) ou l’horloge 24 heures, de même pour l’échelle
Fahrenheitoulsius,etappuyezsurleboutoOK( ).
Affichage Actions Résultat
Test du disjoncteur différentiel (Pour 120 V seulement)
Le test du disjoncteur permet de vérifier que l’installation est correcte et
que le système fonctionne normalement.
Pour tester le disjoncteur différentiel :
1. Le test ne peut se faire que si le thermostat détecte une demande
de chauffage.
2.Réglezlepointdeconsignejsqu’àcequelesymboledechauffage
()apparaisse;appuyezsurlebouton( ) pour augmenter la
température.Attendez10secondesquelethermostats’ajusteau
nouveau point de consigne.
3.Appuyezsurlebouton«TEST».
Siletestestnormal,levoyantrougeGFCIs’allumeetl’affichagedu
thermostatdisparaît.Sicen’estpaslecas,vérifiezl’installation.
1.AppuyezsurleboutonRESETderéarmementdudisjoncteur.Le
voyantrougedoits’éteindreetl’affichage,réaparaître.
2.AppuyezsurleboutonOK( ) pour annuler le changement de
température de consigne.
3.Silerésultatdutestn’estpasnormal,vérifiezlecâbledechauff-
age et le thermostat.
Si le disjoncteur différentiel se déclenche en fonctionnement normal
(sansquevousayezappuyésurleboutonTEST),ilpeuts’agird’un
court-circuitàlaterre.Pourdéterminers’ils’agitd’undéfautoud’une
faussealarme,appuyezsurleboutonderéarmement(RESET).Silevoy-
ant rouge s’éteint et ne se rallume pas, c’était une fausse alarme et votre
système fonctionne normalement. Si le disjoncteur ne peut pas être
réarmé,ilyaprobablementuncourt-circuitàlaterre.
Vérifiezlecâbledechauffage,lecâbledelasondeetlethermostat.
Remplaceztoutélémentdéfectueux.
Essais et entretien
Le disjoncteur différentiel devrait être testé une fois par mois.
Réglages d’origine
Le tableau ci-après indique les réglages par défaut qui ont été program-
més en usine pour le thermostat. Si ces réglages ne vous conviennent
pas,vouspouvezleschangeràvolonté.Voir«Programmation », page 4
pour personnaliser votre thermostat.
Pourréinitialiserlethermostatàsaconfigurationd’origine,enfoncezune
pointedanslepetitboutonmarqué«R»etmaintenez-lependant3sec-
ondes.Lethermostatrevientàsesréglagesd’origine.L’heure,lejouret
le type d’heure (12 heures, 24 heures), ainsi que l’échelle de température
(ºF, ºC) sont également réinitialisés.
77 ºF / 25 ºC
68 ºF / 20 ºC
Jours 1 - 5
Jours 6 - 7
Heure
Séquence 4 événements Heure et Température
77 ºF / 25 ºC
68 ºF / 20 ºC
6:00 a.m.
77 ºF / 25 ºC6:00 a.m.
8:00 a.m.
4:00 p.m.
10:00 p.m.
Séquence 4 événements
Temp. maxi/mini
Échelle
Mode adaptatif
5:2
104 ºF / 41 ºC
12 H / ºF
ON
OFF / OFF
68 ºF / 20 ºC11:00 p.m.
Autres réglages
Température
Instructions d’installation et d’opération du thermostat QuickStat

10
Utilisation quotidienne du thermostat
Mode horloge 4 événements
Chaque jour est divisé en 4 événements préréglés. Si le thermostat est
en mode 4 événements, il commande automatiquement la température
requise au moment programmé. Le programme d’origine, réglé en usine,
comporte5joursà4événementset2joursà2événements.Pourplsde
détails, voir « Prgrammation ».
Mode 4 événements :
Le symbole de la fonction horloge ( ) et l’un des 4
symboles d’événement ( ) s’affichent.
Pour plus de détails, voir « Progammation ».
Mode confort temporaire :
Pour changer manuellement la température du
programmeà4éénements,appuyezsurleboutonPLUS
()ouleboutonMOINS( ) une fois pour faire appa-
raîtrelatempératureetutilisezleboutonappropriépour
augmenter ou diminuer sa valeur. L’affichage clignote
pendant5secondesetl’heureréapparaît.Lechangement
n’est valide que jusqu’au prochain événement programmé,
aprèsquoilethermostatrevientàsonprogrammeautoa-
tique.
Annulation du mode confort :
Pourannulerlemodeconfor,appuyezdeuxfoissurle
bouto OK ( ).
Mode manuel permanent :
Pendantlesvacances,leprogrammenormalà4événe-
mentspeutêtrdésactivé.AppuyezsurlebotonOK(
) puis sur lebouton PLUS ( )ouleboutonMOINS( )
pour fixer la température désirée. Le thermostat fonction-
neraàcettetempératurejusqu’àcequevouslachangiez
ouquevousannuliezlemodepermanent.
Annulation du mode manuel permanent :
Pourannulerlemodemanuelpermanet,appuyezunefois
sur le bouton OK ( ) : le thermostat reprend son fonction-
nement automaique.
Arrêt complet du chauffage :
Pourarrêterlecauffage,appuyezsurleboutonMOINS
()jusqu’àcequelatempératureatteigne41ºF,puis
appuyezsuleboutonOK( )etànouveausur( ).
N’UTILISEZ PAS LE BOUTON TEST DU DISJONCTEUR
DIFFÉRENTIEL POUR COUPER LE CHAUFFAGE. Le dis-
joncteur différentiel se réarme automatiquement après une
panne de courant.
Programmation
Heures et températures 4 événements
Le tableau ci-après illustre les réglages par défaut des heures et des
températures.Vouspouvezcependantleschangeràvolonté.Parexem-
ple,lematinvouspouvezvouloirqueleplanchersoitchaudà7heures
a.m. et que la température soit de 80 ºF, et ainsi de suite pour les autres
événements. Pour programmer le rmostat :
AppuyezsurleboutonOK( )pendant3secondespourfaireapparaître
l’heure début.
UtiezlesboutonsPLUS( )etMOINS( ) pour fixer l’he désirée.
AppuyezsurleboutonOK( ) pour confirmer. L’heure sélectionnée est
affichée.
AppuyezensuitesurleutonPLUS( )ouleboutonMOINS( ) pour
fixerlatempératdésirée.AppuyezsurleboutonOK( ) pour confirmer.
La température sélectionnée est affichée.
Répétezcesdeuxséquencesd’opérationspourlesautresévénements.
Ces réglages seront appliqués aux jours 1-5 indiqués sur l’affichage.
Pourprogrammerlesjours6et7,répétezlesopérationsci-dessus.Les
jours 6 et 7 correspondent normalement au samedi et au dimanche et ne
comportent que deux événements.
Latempératurepeutêtrerégléeentre41°Fet104ºF.Ilestégalement
possible d’arrêter le chauffage d’un événement en réduisant la tempéra-
tureà41ºFenappuyantànouveausurlebouton( ).
Instructions d’installation et d’opération du thermostat QuickStat

11
Réglages et affichages avancés
AppuyezsurlesdeuxboutonsPLUS( )etMOINS( )
pendant3secondes:l’afficheurindiqueINFO».
AppuyezsurleboutonPLUS( )jusqu’àl’affichagedu
sous-enudésiré.AppuyezsurleboutonOK( ) pour
sélectionner le sous-menu affiché.
Surveilance de votre consommation d’énergie
Le thermostat calcule la durée moyenne de chauffage pour
vous permettre de calculer votre consommation d’énergie.
La valeur affichée est le pourcentage du temps total de
chauffage au cours des deux derniers jours, des 30
derniers jours ou des 365 derniers jours.
Calcul des frais de chauffage par jour :
(% chauffage/100) x kW x prix kWh x 24 h par jour
Exemple:
Affichage : 30 % au cours des 365 jours écoulés
Puissancedechauffage:1,2kW(demandezàvotre
installateur)
Coût de l’électricité: 0,10 $Can/ kWh - Calcul :
(30/100) x 1,2 kW x 0,1 $Can/ kWh x 24 h = 0,86 $
par our
AppuezsurleboutonPLUS( )ouMOINS( ) pour voir
les différents affichages.
Vousnepouvezfaireaucunchangementdnscemode.
AppuyezsurleboutonOK( ) pour qutter le mode.
Séquence à 4 événements
La séquence actuelle est affichée par le clignotement des
jours:1-5,suivisde6-7.Pourchangerlaquence,appuyez
sur le bouton PLUS ( ) jusqu’àcequelesjours1-6
clignotent, puis les 7 ensemble. Pour choisir la séquence
quivoconvent,appuyezsurleboutonOK( ).
5-2: 4 événements sur
5 jours +
2 événements sur
2 jours.
6-1: 4 événements sur
6 jours +
2 événements sur 1 jour
7-0: 4 événements sur 7 jours
Réglage de lagamme de températures maximum-minimum
Lagammedetempératurestotale,de41ºFà104ºF,peut
être limitée pour éviter que quelqu’un sélectionne une
températures trop haute ou trop basse.
Pour régler la température maximum
ermise, appuye sur les boutons PLUS ( )
ouMOINS( ) pour augmenter ou réduire
latempéature,puisappuyezsurlebouton
OK ( ) pour confirmer.
L’afficheur indique« LoLi ».
AppuyezsurleboutonOK( ) pour
continuer.
Vouspouvezmaintenantsélectionner
la température minimale au-dessus de
laquelle le plancher ne descenra jamais.
UtiisezlesboutonsPLUS( )etMOINS
( ) pour agmenter ou réduire, et le
bouton OK ( ) pour accepter.
Remarque:Pourcoupercomplètementlechauffage,sélectionnezpour
«LoLi»unevaleurdetempératurede41ºF,appuyezsurOKpour
cofirmeretappuyezencoreunefoissur( ).
Choisirl’horloge et l’échelle de température
Pour choisir l’indication en ºF ou en ºC, et l’horloge 12
heuresu24heures,procédezcommesu:
Appu sur le bouton PLUS
()ouMOINS( ) pour changer
d’option.
Acceptezlavaleurichéeen
appuyant su le bouton OK ( ).
Mode adaptatif
Ce mode permet au thermostat de calculer lui-même la
durée du préchauffage pour la température désirée. Si
vousavezfixéuneheurededébutde7:00a.m.,lether-
mostatallumera(parexemple)lechauffageà6:00a.m.
pourquelatempératurede77ºFsoitatteinteà7:00a.m.
Sicemoden’estpasactivé,lethermostatcommenceraà
chaufferàl’heurequevousavezprogramée.
AppuyezsurleboutonMOINS( )
pour alterner entre ON (activé) et OFF
(dsactivé).
AppuyezsurleboutonOK( ) pour
continuer
Fin de la séquence de progrmmation
AppuyezsurleboutonOK( ) pour sortir du mode pro-
grammation et revenir au fonctionnement programmé
normal.
2 days
30 days
365 days
Software version
Temperature sensor
Instructions d’installation et d’opération du thermostat QuickStat

Sonde
Temp (˚C) Temp (˚F) Valeur (ohm)
–10 –14 64000
0 32 38000
10 50 23300
20 68 14800
30 86 9700
12
Instructions d’installation et d’opération du thermostat QuickStat
Avertissement important: Toute l’information donnée ici, y compris les illustrations, est, à
notre connaissance, exacte. Il incombe cependant à l’utilisateur de s’assurer indépendam-
ment que chaque produit convient à l’application envisagée. Tyco Thermal Controls ne peut
affirmer que ces renseignements sont exacts et complets et, en conséquence, décline toute
responsabilité quant à leur utilisation. Les seules obligations acceptées par Tyco Thermal
Controls sont celles qui figurent explicitement dans les conditions générales de vente du
produit en question, à l’exclusion de toute responsabilité de Tyco Thermal Controls ou de
ses distributeurs à l’égard de dommages incidents, indirects ou consécutifs découlant de
la vente, de la revente ou de l’utilisation normale ou abusive du produit. Les spécifications
techniques peuvent être modifiées sans préavis. De plus, Tyco Thermal Controls se réserve
le droit de changer ses procédés de fabrication et les matériaux entrant dans la composition
du produit sans en aviser l’acheteur, dans la mesure où cela n’affecte pas la conformité à
l’une quelconque des spécifications applicables.
Tyco, QuickNet and QuickStat sont des marques de commerce de
Tyco Thermal Controls LLC ou de ses sociétés affiliées.
Worldwide Headquarters
Tyco Thermal Controls
307 Constitution Drive
Menlo Park, CA 94025-1164
USA
Tel (800) 545-6258
Tel (650) 216-1526
Fax (800) 527-5703
Fax (650) 474-7711
www.tycothermal.com
Canada
Tyco Thermal Controls
250 West St.
Trenton, Ontario
Canada K8V 5S2
Tel (800) 545-6258
Fax (800) 527-5703
© 2009 Tyco Thermal Controls LLC H57725 06/09
Vérification de la sonde de température
Si la sonde est déconnectée ou en court-circuit, le système de chauffage
ne fonctionnera pas. L’état de la sonde peut être vérifié en mesurant sa
résistane conformément au tableau ci-dessous.
Codes d’erreur
E0 : Erreur interne. Le thermostat doit être remplacé.
E2 : Sonde externe en court-circuit ou déconnecté.
Other manuals for QuickStat
1
Table of contents
Languages:
Other Raychem Thermostat manuals
Popular Thermostat manuals by other brands

Source 1
Source 1 S1-THSU302-S Owner's Manual & Installation Instructions

OJ Electronics
OJ Electronics MSW4-10 Instruction

Beretta
Beretta SUN 1 N instruction manual

Honeywell
Honeywell T822K owner's manual

Carrier
Carrier ComfortVu TB-24-HM Installation and operation guide

Siemens
Siemens RDG100 Series Basic documentation