Real Time Automation 460BMSAWS-NNA1 Specification sheet

Real Time Automation, Inc.
1
1-800-249-1612
Firmware Version 8.8.22
460BMSAWS-NNA1
Protocol Gateway
Product User Guide

Real Time Automation, Inc.
2
1-800-249-1612
Trademarks
CompactLogix, ControlLogix, & PLC-5 are registered trademarks of Rockwell Automation, Inc. EtherNet/IP is a trademark of the ODVA.
MicroLogix, RSLogix 500, and SLC are trademarks of Rockwell Automation, Inc. Microsoft, Windows, and Internet Explorer are registered
trademarks of Microsoft Corporation. BACnet®is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning
Engineers (ASHRAE). All other trademarks and registered trademarks are the property of their holders.
Limited Warranty
Real Time Automation, Inc. warrants that this product is free from defects and functions properly.
EXCEPT AS SPECIFICALLY SET FORTH ABOVE, REAL TIME AUTOMATION, INC. DISCLAIMS ALL OTHER WARRANTIES, BOTH
EXPRESSED AND IMPLIED, INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A
PARTICULAR APPLICATION. THIS LIMITED WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHER
RIGHTS, WHICH VARY FROM STATE TO STATE.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements
associated with any particular application, Real Time Automation, Inc. cannot assume responsibility or liability for actual use based on the
examples and diagrams. Except as specifically set forth above, Real Time Automation and its distributors and dealers will in no event be liable
for any damages whatsoever, either direct or indirect, including but not limited to loss of business profits, income, or use of data. Some states
do not allow exclusion or limitation of incidental or consequential damages; therefore, the limitations set forth in this agreement may not apply
to you.
No patent liability is assumed by Real Time Automation with respect to use of information, circuits, equipment, or software described in this
manual.
Government End-Users
If this software is acquired by or on behalf of a unit or agency of the United States Government, this provision applies: The software (a) was
developed at private expense, is existing computer software, and was not developed with government funds; (b) is a trade secret of Real Time
Automation, Inc. for all purposes of the Freedom of Information Act; (c) is “restricted computer software” submitted with restricted rights in
accordance with subparagraphs (a) through (d) of the Commercial “Computer Software-Restricted Rights” clause at 52.227-19 and its
successors; (d) in all respects is proprietary data belonging solely to Real Time Automation, Inc.; (e) is unpublished and all rights are reserved
under copyright laws of the United States. For units of the Department of Defense (DoD), this software is licensed only with “Restricted Rights”:
as that term is defined in the DoD Supplement of the Federal Acquisition Regulation 52.227-7013 (c) (1) (ii), rights in Technical Data and
Computer Software and its successors, and: Use, duplication, or disclosures is subject to restrictions as set forth in subdivision (c) (1) (ii) of the
Rights in Technical Data and Computer Software clause at 52.227-7013. If this software was acquired under GSA schedule, the U.S.
Government has agreed to refrain from changing or removing any insignia or lettering from the Software or documentation that is provided or
from producing copies of the manual or media. Real Time Automation, Inc.
© 2024 Real Time Automation, Inc. All rights reserved.

Real Time Automation, Inc.
3
1-800-249-1612
Revision History ............................................................................................................................................6
Overview.......................................................................................................................................................8
Hardware Platforms......................................................................................................................................9
Hardware –NNA1 ...................................................................................................................................10
Powering the Gateway............................................................................................................................10
Port Configuration...................................................................................................................................11
RS232 pinouts: ........................................................................................................................................11
RS485 pinouts: ........................................................................................................................................11
TTL pinouts:.............................................................................................................................................12
Mounting with a DIN Rail............................................................................................................................13
Installing..................................................................................................................................................13
Removing ................................................................................................................................................13
Accessing the Main Page.............................................................................................................................14
Committing Changes to the Settings ..........................................................................................................16
Main Page ...................................................................................................................................................17
Device Configuration...................................................................................................................................18
Network Configuration ...............................................................................................................................19
BACnet MS/TP Subordinate Configuration.................................................................................................20
BACnet MS/TP Subordinate Configuration-Data Groups ...........................................................................21
BACnet MS/TP Subordinate Configuration: Manual Configure Mode....................................................23
BACnet MS/TP Subordinate Object Configuration –Analog Objects .....................................................24
BACnet MS/TP Subordinate Object Configuration –Binary Objects ..........................................................25
BACnet MS/TP Subordinate Object Configuration –CharacterString Value Objects.................................26
BACnet MS/TP Subordinate Object Configuration –Group Names .......................................................27
MQTT Client Configuration.........................................................................................................................28
Amazon Web Services (AWS) Configuration...........................................................................................28
Configuring Subscribe and Publish Topics ..............................................................................................29
Additional AWS Requirements................................................................................................................30
How to FTP files into theRTA gateway........................................................................................31
AWS IoT Core Service Setup........................................................................................................................33
AWS IoT Core Service Things Configuration ...........................................................................................35
Certificate setup..................................................................................................................................36

Real Time Automation, Inc.
4
1-800-249-1612
Attach policies to certificate ...............................................................................................................38
Testing AWS Communication .....................................................................................................................42
Send data from AWS to RTA gateway (Subscribe Topic) ....................................................................43
Send data from RTA gateway to AWS (Publish Topics) ......................................................................44
QT Publish Trigger.......................................................................................................................................47
Mapping - Transferring Data Between Devices ..........................................................................................48
Display Mapping and Values.......................................................................................................................49
Display Data ............................................................................................................................................49
Display String...........................................................................................................................................52
Display String use case................................................................................................................................54
Data and String Mapping –Auto-Configure................................................................................................55
Data Mapping –Explanation.......................................................................................................................56
Data Mapping –Adding Diagnostic Information ........................................................................................57
String Mapping –Explanation.....................................................................................................................62
Mapping –Auto-Configure Mode to Manual Configure Mode ..................................................................63
Mapping –Manual Configure Mode to Auto-Configure Mode ..................................................................64
View as Text ................................................................................................................................................65
Data Mapping..........................................................................................................................................65
String Mapping........................................................................................................................................65
Base Triggering –Data Validiation Triggering.........................................................................................66
Security Configuration ................................................................................................................................68
Security Configuration-Security Levels ...................................................................................................69
Security - Log In.......................................................................................................................................70
Security - Log Out....................................................................................................................................70
Email Configuration ....................................................................................................................................71
Alarm Configuration....................................................................................................................................72
Diagnostics –Alarm Status......................................................................................................................74
Alarms –Active .......................................................................................................................................74
Alarms –Clear.........................................................................................................................................75
Change of State (COS) Configuration..........................................................................................................76
Diagnostics Info...........................................................................................................................................77
Diagnostics Mapping...............................................................................................................................77
Diagnostics –BACnet MS/TP Slave .............................................................................................................78

Real Time Automation, Inc.
5
1-800-249-1612
Diagnostic –MQTT Client............................................................................................................................82
LED Configuration .......................................................................................................................................84
Configuration Files ......................................................................................................................................85
Export Configuration...............................................................................................................................85
Import Configuration ..............................................................................................................................85
Save and Replace Configuration Using SD Card..........................................................................................87
Saving Configuration Using SD Card........................................................................................................87
Replacing Configuration Using SD Card ..................................................................................................87
Intelligent Reset Button..............................................................................................................................88
Utilities........................................................................................................................................................89

Real Time Automation, Inc.
6
1-800-249-1612
Revision History
Version
Date
Notes
8.4.5
11/18/2019
Features Added
1. Released OPC UA Server (US) Protocol
2. Ability to now Import/Export Template Files with out an FTP session
Bug Fixes
3. Updated Profinet Server (PS) on N34 hardware Platform
4. Updated Wi-Fi software
8.6.0
2/28/20
Bug Fixes
1. Omron Plc Communication fixes for EtherNet/IP
2. Profinet GSDML Substitute values fix
8.7.4
9/1/20
Features Added:
1. BMS, BM, DFM, DS, DM, TCP, USB, PBS have been ported to the latest base software
2. TCP,BMS,BM now Available on N2E and N2EW hardware Platform
3. New ASCII Mode Available on TCP/A/USB/WI protocols
4. User Guides updated with more examples
Bug Fixes:
1. Improved Data Mapping and String Mapping performance
2. Improved functionality/performance on EC,ETC,ES,MC,MS,BS,BC, A,,WI,PS protocols
8.7.22
4/6/21
Features Added:
1. Support for RSLogix Versions 32 + with unsigned data type support
2. ETC now support Long integer files (L files) for MicroLogix PLCS that support them
3. SC now supports data block (DB) access
8.7.53
4/28/21
Features Added:
5. Added support for the NNBU hardware platform
6. Improved RFIDeas scanner support
7. Updated MM and MRS to use Modbus RTU Client and Modbus RTU Server terminology

Real Time Automation, Inc.
7
1-800-249-1612
Version
Date
Notes
8.9.22
2/5/24
Features Added:
1. Added priority-based reads for client protocols
2. Added improved diagnostic timers for client protocols
3. Reduced minimum delay between messages to zero ms on client protocols
4. Added support for USB serial connections
5. Added support for multiple connections on EtherNet/IP Adapter
6. Added 100ms and 1000ms heartbeat values for diagnostic use
7. Added configurable data size to EtherNet/IP adapter and DeviceNet Slave
8. Added support for TTL communications on N34, NNA1, NNA4, N2E, and N2EW
hardware
9. Added support for JSON payloads to MQTT
10. Added Network Bitmap Status to ASCII, USB, and TCP protocols
Bug Fixes:
11. Fixed COV Subscription Issues on BACnet MS/TP
12. Fixed timing issues affecting gateway performance
13. Fixed a bug where the Run Idle Header on the output instance for EtherNet/IP
Scanner was not checked by default

Real Time Automation, Inc.
8
1-800-249-1612
Overview
The 460BMSAWS-NNA1 gateway Get your BACnet MS/TP BMS connected to Amazon Web Services
(AWS) IoT Core. By following this guide, you will be able to configure the 460BMSAWS-NNA1 gateway.
Number of ASCII devices is dependent on the Hardware and Product number of the 460 gateway.
For further customization and advanced use, please reference the appendices located online at:
http://www.rtautomation.com/product/460-gateway-support/.
If at any time you need further assistance, do not hesitate to call Real Time Automation support.
Support Hours are Monday-Friday 8am-5pm CST
Toll free: 1-800-249-1612
Email: support@rtautomation.com

Real Time Automation, Inc.
9
1-800-249-1612
Hardware Platforms
The 460 Product Line supports a number of different hardware platforms. There are differences in how
they are powered, what serial settings are supported, and some diagnostic features supported (such as
LEDs). For these sections, be sure to identify the hardware platform you are using.
To find which hardware platform you are using:
1) Look on the front or back label of the unit for the part number.
2) On the webpage inside the gateway, navigate to the dropdown menu under Other and select
Utilities. Click the Listing of Revisions button. The full part number is displayed here.
Once you have the full part number, the platform will be the number following the “-N”:

Real Time Automation, Inc.
10
1-800-249-1612
Hardware –NNA1
Powering the Gateway
1) Connect a 12-24 VDC power source to the gateway, Red Wire = (+) Black Wire = (-).
a) The unit draws 175mA @ 12 V.

Real Time Automation, Inc.
11
1-800-249-1612
Port Configuration
The Port Configuration page is where you set port specific parameters. These settings must match the
settings of the device(s) that you are connecting to.
Only 1 mode can be configured for this hardware. Below are the wiring pinouts for each mode.
When you have completed your port configuration, click the Save Parameters button.
RS232 pinouts:
RS485 pinouts:

Real Time Automation, Inc.
12
1-800-249-1612
TTL pinouts:

Real Time Automation, Inc.
13
1-800-249-1612
Mounting with a DIN Rail
Installing
Follow these steps to install your interface converter.
1) Mount your DIN Rail.
2) Hook the bottom mounting flange under the DIN Rail.
3) While pressing the 460BMSAWS-NNA1 against the rail, press up to engage the spring loaded lower clip
and rotate the unit parallel to the DIN Rail.
4) Release upward pressure.
Removing
Follow these steps to remove your interface converter.
1) Press up on unit to engage the spring loaded lower clip.
2) Swing top of the unit away from DIN Rail.
DIN Rail
Spring Loaded Lower Clip

Real Time Automation, Inc.
14
1-800-249-1612
Accessing the Main Page
The following steps will help you access the browser based configuration of the gateway. By default,
DHCP is enabled. If the gateway fails to obtain an IP address over DHCP it will Auto IP with 169.254.X.Y.
For more information on your Operating system network setting refer to the Accessing Browser
Configuration document from our support web site.
1) Scan the QR code on the back of the unit or navigate to www.rtautomation.com/460-gateway-support
and download IPSetup.exe.
2) Run the IPSetup.exe program.
3) Find unit under “Select a Unit”.
a. Change Gateway’s IP address to match that of your PC if DHCP has failed.
i. You will know DHCP has failed if the gateway’s IP address is AutoIP at 169.254.X.Y.
ii. If successful, it will say DHCP’d at ex: 192.168.0.100 or however your DCHP Client is set up.
b. If you do not see the gateway in this tool, then your PC is most likely set up as a static IP.
i. Change your PC’s network settings to be DHCP. If DHCP fails, then it will change to be on the
169.254.x.y network.
ii. Relaunch the IP Setup tool to see if gateway can be discovered now.
4) Click Launch Webpage. The Main page should appear.
Default setting is set to DHCP. If DHCP fails, default IP Address is 169.254.x.y

Real Time Automation, Inc.
15
1-800-249-1612
Error: Main Page Does Not Launch
If the Main Page does not launch, please verify the following:
1) Check that the PC is set for a valid IP Address
a. Open a MS-DOS Command Prompt
b. Type “ipconfig” and press enter
c. Note the PC’s IP Address, Subnet, and Default Gateway
2) The gateway must be on the same Network/Subnet as the PC whether it’s setup for DHCP or Static.
Once you have both devices on the same network, you should be able to ping the gateway using a MS-
DOS Command Prompt.
The Screenshot above shows a gateway that is currently set to a static IP Address of 192.168.0.100.
If you are able to successfully ping your gateway, open a browser and try to view the main page of the
gateway by entering the IP Address of the gateway as the URL.

Real Time Automation, Inc.
16
1-800-249-1612
Committing Changes to the Settings
All changes made to the settings of the gateway in Configuration Mode will not take effect until the
gateway is restarted via the webpage. Changes will not be stored if the gateway’s power is removed
prior to a reboot.
NOTE: The gateway does not need to be restarted after every change. Multiple changes can be made
before a restart, but they will not be committed until the gateway is restarted.
When all desired changes have been made, press the Restart Now button.
The webpage will redirect to our rebooting page shown below:
The reboot can take up to 20 seconds.
If the IP address has not been modified, the gateway will automatically redirect to the main page.
If the IP address was modified, a message will appear at the top of the page to instruct the user to
manually open a new webpage at that new IP.

Real Time Automation, Inc.
17
1-800-249-1612
Main Page
The main page is where important information about your gateway and its connections are displayed.
Mode (orange box below):
Running Mode:
•Protocol communications are enabled
•Configuration cannot be changed during Running Mode. If changes are needed, click the
Configuration Mode button shown in the green box below
Configuring Mode:
•Protocol communication is stopped and no data is transmitted
•Configuration is allowed
Navigation (green box below):
You can easily switch between modes and navigate between pages (Configuration, Diagnostics, and
Other pages) using the buttons on the left hand side.

Real Time Automation, Inc.
18
1-800-249-1612
Device Configuration
The device configuration area is where you assign the device description parameter. Changes can only
be made when the gateway is in Configuration Mode.
Once you are done configuring the Description, click the Save Parameters button.

Real Time Automation, Inc.
19
1-800-249-1612
Network Configuration
The network configuration area is where you assign the IP address and other network parameters.
Changes can only be made when the gateway is in Configuration Mode.
Once you are done configuring the Network Settings, click the Save Parameters button.
If you are changing the IP Address of the gateway, the change will not take effect until the unit has been
rebooted. After reboot, you must enter the new IP Address into the URL.
It is recommended to leave the DNS Gateway set to 0.0.0.0 and the Ethernet Link as
Auto-Negotiate. If configuring the gateway to use E-mail, the DNS Gateway must be
set.

Real Time Automation, Inc.
20
1-800-249-1612
BACnet MS/TP Subordinate Configuration
Click the BACnet MS/TP Subordinate button to access the primary configuration page for this device.
1) Enter a Device Label. This is an internal device alias used during data mapping.
2) Serial Port: Select which serial port is being used for communication. This port must be
configured on the Port Configuration page. If it has not yet been configured, it will display
Disabled after the Port descriptions in this dropdown.
3) Enter a unique MAC ID for the gateway. This MAC ID must be unique on the BACnet MS/TP
network.
4) Max Master: Enter the maximum MAC ID that the gateway will communicate with on the
BACnet MS/TP network. This value should be equal or greater than the largest MAC ID on the
MS/TP network.
5) Enter a unique Instance identifier for the gateway. This value must be unique across the BACnet
network.
6) Inactivity Timeout: Enter the amount of time, in milliseconds, the gateway should wait before a
timeout state is declared. If the BACnet MS/TP Manager does not initiate communication within
this time frame the BACnet MS/TP LED will flash red and the timeout counter will increment.
Enter zero to disable this feature.
7) Enter a Name, Description and Location for the gateway. These are used to identify the gateway
on the BACnet MS/TP network.
8) Bit Pack: Select the formatting of the Binary Input/Output. Automap will use this packing size to
map binary objects to/from the other protocol.
NOTE: For optimal performance, the MAC IDs on the BACnet MS/TP network should be sequential,
starting from 0. The Max Master should be set to the highest MAC ID on the BACnet MS/TP network.
Table of contents
Other Real Time Automation Gateway manuals

Real Time Automation
Real Time Automation 460BCQT-NNA4 Specification sheet

Real Time Automation
Real Time Automation 460BMQT-NNA4 Specification sheet

Real Time Automation
Real Time Automation 460SCQT-N2E Specification sheet

Real Time Automation
Real Time Automation 460BMSAWS-N2E Specification sheet

Real Time Automation
Real Time Automation 460EAV User manual