Resol FlowSol B User manual

*48006771*
48006771
Thank you for buying this RESOL product.
Please read this manual carefully to get the best performance from this unit.
Please keep this manual carefully. www.resol.com
Manual
en
Installation
Operation
Commissioning
Manual for the
specialised craftsman
FlowSol®B/B HE

2
Subject to technical change. Errors excepted.
© 20170628_48006771_FlowSol_B.monen.indd
Safety advice
Please pay attention to the following safety advice in order to avoid danger and
damage to people and property.
Instructions
Attention must be paid to the valid local standards, regulations and directives!
Information about the product
Proper usage
The pump station may only be used in the solar circuit of solar thermal systems in
compliance with the technical data specied in these instructions. Due to its de-
sign the station must be mounted and operated as described in these instructions!
CE-Declaration of conformity
The product complies with the relevant directives and is therefore la-
belled with the CE mark. The Declaration of Conformity is available upon
request, please contact RESOL.
Target group
These instructions are exclusively addressed to authorised skilled personnel.
Only qualied electricians should carry out electrical works.
Initial installation must be effected by qualied personnel named by the manufac-
turer. Contents
1 Overview .............................................................................................. 3
2 Mounting the station........................................................................... 4
3 Flushingandllingthesolarsystem.................................................. 4
4 Ball valve positions .............................................................................. 5
5 Draining the system............................................................................ 5
6 Non-return valves................................................................................ 5
7 Flowmeter............................................................................................ 6
8 Air separator ....................................................................................... 6
9 Maintenance......................................................................................... 6
10 Safety devices....................................................................................... 6
11 Accessories .......................................................................................... 7
12 Information about the pump ............................................................. 7
13 Lists of spare parts ............................................................................. 7
Description of symbols
WARNING! Warnings are indicated with a warning triangle!
ÎThey contain information on how to avoid the danger
described.
Signal words describe the danger that may occur, when it is not avoided.
• WARNING means that injury, possibly life-threatening injury, can occur.
• ATTENTION means that damage to the appliance can occur.
Note
Notes are indicated with an information symbol.
ÎArrows indicate instruction steps that should be carried out.
Disposal
• Dispose of the packaging in an environmentally sound manner.
• Dispose of old appliances in an environmentally sound manner. Upon request
we will take back your old appliances bought from us and guarantee an environ-
mentally sound disposal of the devices.

en
3
1 Overview
• Pre-assembled twin-line pump station
• Safety assembly with connection for the diaphragm-type expansion
vessel, safety valve and pressure gauge
• Fill and drain valves
• Wall mounting bracket and mounting material
• Standardorhigh-efciencypump
• Ballvalvesinowandreturn
• Air separator
Technical data
Circulating pump:
FlowSol®B: Wilo ST 15/6 ECO or 15/7 ECO FlowSol®B HE: Wilo Yonos
PARA ST15/7.0-PWM2 (
ErP power consumption of the pump*
: 23 W);Wilo Stratos
TEC 15/6 or 15/7 (
ErP power consumption of the pump*
: 25 W / 35 W)
Safety valve: 6 bar
Pressure gauge: 0 … 10 bar
Flowmeter: 1 … 13 l/min
Non-return valves: opening pressure 20 mbar, openable
Connection to diaphragm-type expansion vessel: ¾'' ET, at sealing
Outlet safety valve: ¾'' IT
Connections to the solar pipes: ¾'' IT
Maximumtemperatureow/return:120 °C / 95 °C
Maximum pressure: 6 bar
Medium: Water with max. 50 % glycol
Dimensions: approx. 481 × 320 × 190 mm (with insulation)
Distance centres: 100 mm
Distance centre / wall: 67 mm
Material: Fittings: brass
Seals:AFM 34
Insulation: EPP foam
*50 % of the rated power consumption
Note:
This pump station can be used with the heat transfer uids Tyfocor L, L
eco and LS.
Wilo Yonos Para ST 15/7 max.
Delivery height (m)
Flow rate (l/min)
Pressure loss (bar)
FlowSol®B
Wilo ST 15/6 ECO max.
W
ilo ST 15/7 ECO max.
0
1
2
3
4
5
6
7
8
0 5 10 15 20 25 30 35 40 45
0,0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
Delivery height (m)
Flow rate (l/min)
Pressure loss (bar)
FlowSol®B
Pumpcharacteristics/pressurelosscharacteristics
FlowSol®B standard pumps
FlowSol®B HE high-efciency pumps

en
4
2 Mounting the station
10 11
12
13
10 Wall mounting bracket
11 Back half of the insulation
12 Front half of the insulation
13 Hinged controller panel
Controller and controller panel depend on the version of the station
ÎDetermine the mounting site of the station.
ÎMark the drill holes by means of the template enclosed, then drill and insert
wall plugs (see gure to the right).
ÎTake the station out of the packaging.
ÎRemove the front half of the insulation. Leave the pump station attached to the
back half of the insulation!
ÎFasten the pump station to the wall with the enclosed screws. For this pur-
pose, use a crosshead screw driver.
ÎFold the hinged controller panel to the left.
ÎConnect the pipework between pump station and store and collector re-
spectively.
Note
All connections are already tightened such that they usually do not have
to be tightened again. However, during commissioning of the system all
connections have to be checked for leaks (pressure test).
3 Flushingandllingthesolarsystem
WARNING! Scald danger!
Pressure surge damage!
If the medium enters strongly heated, empty collectors, pressure
surges caused by evaporation can occur.
ÎInordertopreventthesolaruidfromvaporisingin-
sidethecollectors,donotllorushthesystemdur-
ing times of strong irradiation!
5
4
3
1
2
6
7
9
8
1 Safety valve
2 Pressure gauge
3 Drain valve
4 Ball valve (return) with thermometer and integrated non-return valve
5 Fill valve
6 Pump
7 Flowmeter
8 Ball valve ( ow) with thermometer and integrated non-return valve
9 Air separator

en
5
Beforeushingthesystem
ÎDisconnect the expansion vessel from the solar thermal system.
ÎConnect the pressure hose of the lling and ushing
station to the ll valve (5) of the pump station.
ÎConnect the ushing hose of the lling and ushing
station to the drain valve (3) of the pump station.
2.
ÎClose the ball valve of the pump station (4).
ÎOpen the ll valve (5) and the drain valve (3).
ÎSwitch on the lling pump of the lling and ushing
station.
ÎFlush the solar thermal system for at least 15 minutes by means of the lling
and ushing station until the discharged solar uid is free of gas bubbles and
dirt particles.
ÎDuring ushing, bleed the solar thermal system several times until the dis-
charged solar uid (e. g. Tyfocor®, see chap. 11) is free of air bubbles.
ÎOpen the ball valve of the pump station (4).
Afterushingthesystem
ÎConnect the expansion vessel to the solar thermal system
ÎClose the drain valve (3) of the pump station while the lling pump is running.
ÎIncrease system pressure (approx. 3.5 - 4 bar). The
system pressure can be read from the pressure gauge.
ÎClose the ll valve (5).
ÎSwitch off the lling pump.
BAR
ÎCheck the pressure gauge to see whether the system pressure reduces and
eliminate leaks where necessary.
ÎSlowly discharge the heat transfer uid by means of the drain valve (3) until
the operating pressure is set.
ÎRemove the hoses of the lling and ushing station and screw the caps onto
the ll and drain valves. Manually start the solar thermal pump at maximum
speed (see controller manual) and let the uid circulate for at least 15 minutes.
ÎBleed the solar thermal system several times.
ÎCheck the system pressure at the pressure gauge.
ÎCheck the antifreeze ratio (not required if a
ready-mix is used).
11.
%
4 Ball valve positions
WARNING! Scald danger! Damage by overpressure!
When the ball valve is closed, too high pressure may occur in the
blocked-off line if it is heated.
ÎIn order to prevent scald danger and damage by over-
pressure,make sure the blocked-off line is not heated.
Non-return valve in operating position, uid ow in ow
direction only
Ball valve open, uid ow in both directions possible
Ball valve closed, no uid ow
5 Draining the system
ÎOpen the ball valve (4).
ÎOpen the air vent at the highest point of the system (above the collectors).
ÎOpen the drain valve.
6 Non-return valves
The non-return valves of the pump station are integrated into the ball valves in
ow and return and have an opening pressure of 20 mbar.
In order to completely drain the system, the non-return valves have to be opened.
ÎFor this purpose, turn the handles of the ball valves by 45°.
ÎFor normal system operation, open the ball valves completely.
7 Flowmeter

en
6
The owmeter measures and indicates the ow rate with a range of 1-13 l/min.
For the device to function faultlessly, the system must be ushed and free of grit.
Read the ow rate from the upper edge of the oat
8 Air separator
WARNING! Scald danger!
During venting, the air discharged can reach temperatures of
more than 100°C.
ÎIn order to avoid scalding, pay attention to the sys-
tem temperatures!
The air separator is used for venting the water/ glycol mixture
in the solar circuit. The air separated from the heat transfer uid
gathers in the air scoop and can be discharged manually at the
air vent valve.
ÎOpen the air vent valve and collect the discharged uid in a
suitable container.
ÎCheck the system pressure after bleeding and, if necessary,
increase it to the specied operating pressure.
9 Maintenance
In the case of maintenance (such as a replacement of the pump) proceed as follows:
ÎClose the ball valve (4).
ÎTurn the slot of the owmeter spindle by 90° anti-
clockwise (see gure below).
The heat transfer uid can now be drained from the pump.
ÎOpen the drain valve (3).
If necessary, open the union nut at the pressure side.
ÎNow dismount the pump.
10 Safety devices
The pump station is equipped with a diaphragm safety valve which corresponds to
the relevant directives and regulations. For installation and operation, please pay
attention to the following advice:
• The safety valve has to be easily accessible. The efciency of the valve must not
be inuenced or disabled by barriers!
• The strainer or other restriction devices must not be mounted between collec-
tor (-eld) and safety valve!
• The diameter of the discharge pipe must correspond to the diameter of the
valve outlet; the maximum length must not exceed 2 m; more than 2 bends are
inadmissible. When these values are exceeded, you have to install a discharge
pipe with larger dimensions. Do not use more than 3 bends and pipes longer
than 4 m!
• If the discharge pipe leads into a drain pipe with a funnel, the diameter of the
drain pipe has to be at least twice as large as the valve inlet. The opening of
the discharge pipe must be inclined downwards. It must be routed such that
the opening can be seen but does not present any risk to a person standing or
passing by.
• We recommend placing a container below the discharge pipe. If the safety valve
opens, the uid will be collected and can be relled into the system when the
pressure is too low.

en
7
11 Accessories
SBS2000llingandushingstation
The SBS 2000 has been especially designed for profes-
sionally lling and ushing solar thermal and heating sys-
tems. Its many thought-out details facilitate transport,
operation and cleaning, the attractive design makes it the
ideal companion for a professional performance.
Heattransferuids
In our product portfolio, you will nd a range of heat
transfer uids for different applications, available as
readymix or concentrate.
Note:
This pump station can be used with the heat
transfer uids Tyfocor L, L eco and LS.
Wall mounting for diaphragm-type expansion ves-
sel
Wall mounting for diaphragm-type expansion vessel with
screws and wall plugs, high grade steel corrugated tube
and connection thread ¾". Including quick release valve
coupling enabling removal of expansion without draining
down of the system.
Wall mounting for diaphragm-type expansion vessel with
screws and wall plugs, high grade steel corrugated tube
Filling and injection pump
Filling and injection pump with non-return valve for pres-
sure increase and re lling of heat transfer uids. ½" OT
self-sealing with O-ring, 15mm tube connection. Pump
output 2 l/min, 4.5 bar max.
ALS15 discharge hose
1.5 m hose for connection to the safety valve of the
FlowSol® B / B HE pump station.
See our full range of accessories on our website:
www.resol.com
12 Information about the pump
Depending on the version, the station is equipped with different pumps. Data con-
cerning the pump in your station are available at the pump manufacturer under
www.wilointec.com. Upon request we will provide you with further information.
13 List of spare parts
12a-c
2
5
1
6a-c
7
8
10 11 4
13
3
Pos. Art. no. Article
1 11200054 Safety valve 6 bar
2 11200039 Pressure gauge (10 bar)
3 11200058 Fill / Drain valve
4 11200069 Ball valve (return) with thermometer and integrated non-return valve
5 11200058 Fill / Drain valve
6a 28000610 Pump WILO ST15/6
6b or 28000620 Pump WILO ST15/7
6c or 11204195 Pump WILO Yonos Para ST 15/7 (HE pump)
7 28000490 Flowmeter
8 11200062 Ball valve ( ow) with thermometer and integrated non-return valve
9 28000491 Air separator (not shown)
10 11200071 Wall mounting bracket
11 70001512 Back half of the insulation
12a 70001614 Front half of insulation DeltaSol®BX series
12b or 70001613 Front half of the insulation DeltaSol®BS
series / CS series (not shown)
12c or 70001516 Front half of the insulation DeltaSol®SL series (not shown)
13 70001612 Hinged controller panel

Distributed by: RESOL – Elektronische Regelungen GmbH
Heiskampstraße 10
45527 Hattingen / Germany
Tel.: +49 (0) 23 24 / 96 48 - 0
Fax: +49 (0) 23 24 / 96 48 - 755
www.resol.com
Important note
The texts and drawings in this manual are correct to the best of our knowledge. As
faults can never be excluded, please note:
Your own calculations and plans, under consideration of the current standards and
directions should only be basis for your projects.We do not offer a guarantee for
the completeness of the drawings and texts of this manual - they only represent
some examples.They can only be used at your own risk. No liability is assumed for
incorrect, incomplete or false information and / or the resulting damages.
Note
The design and the specications can be changed without notice.
The illustrations may differ from the original product.
Imprint
This mounting- and operation manual including all parts is copyrighted. Another
use outside the copyright requires the approval of RESOL – Elektronische Rege-
lungen GmbH. This especially applies for copies, translations, micro lms and the
storage into electronic systems.
© RESOL – Elektronische Regelungen GmbH
Other manuals for FlowSol B
2
This manual suits for next models
1
Table of contents
Other Resol Water Pump manuals
Popular Water Pump manuals by other brands

THE TRADING
THE TRADING MERCATO MEC-20 manual

Oase
Oase AquaMax Eco Premium4000 operating instructions

dosatron
dosatron GENUINE D14MZ5VVFII manual

GORMAN-RUPP PUMPS
GORMAN-RUPP PUMPS T8A71S-B Installation, operation, and maintenance manual with parts list

Metabo
Metabo HWA 6000 Inox manual

SCENTYS
SCENTYS R'PULSE 150 user guide