Reznor XL30 User manual

TABLE OF CONTENTS
GENERAL INFORMATION....................................................................1
Applicability ..............................................................................1
Important Safety Information .................................................................1
POWER VENT KITS .........................................................................2
Voltage ..................................................................................2
Kit Selection ..............................................................................2
Venter Assembly ..........................................................................3
Control System............................................................................4
Venter Adapter ............................................................................4
Power Venter Sequence of Operation ..........................................................5
KIT INSTALLATION .........................................................................5
VENTING..................................................................................9
Specific Venting Requirements ...............................................................9
Connecting Vent Cap To Double-Wall (Type B) Vent Terminal Pipe..................................12
Connecting Single-Wall Vent Run to Double-Wall (Type B) Vent Terminal Pipe.........................12
OPERATIONAL TESTING ...................................................................12
REPLACEMENT PARTS.....................................................................13
Revision: X-CA1,2,3,4 (01-22) 136958-A
POWER VENT KIT INSTALLATION FOR DUCT FURNACES
Supersedes: X-CA1,2,3,4 (11-21) 136958-A
OPTIONS CA1, CA2, CA3, AND CA4 FOR MODEL X
AND OBSOLETE MODELS (H)CX, DX, (H)XE, AND (H)CXE
GENERAL INFORMATION
This optional power venter is a motorized vent exhauster designed to permit the installation of a gravity-vented heater
in an area of negative pressure up to 0.15 IN WC or where horizontal venting is required.
Applicability
NOTE: Models with the H prefix are standard and are not listed separately throughout this manual.
The venter assembly in this instruction form is designed to be installed only on the following equipment:
•Models X/DX/HX and CX/HCX: duct furnace
•Models XE/HXE and CXE/HCXE: packaged duct furnace and blower
•Models XL/CXL and XLB/CXLB: fan and blower type unit heaters (power venter cannot be installed on model
XLB/CXLB units in sizes 030–105 when equipped with an optional blower cabinet)
Important Safety Information
•Refer to the installation manual provided with the unit for important safety information.
•Pay attention to all dangers, warnings, cautions, and notes highlighted in this manual. Safety markings should not
be ignored and are used frequently throughout to designate a degree or level of seriousness.
⚠ DANGER ⚠
Improper installation, adjustment, alteration, service, or maintenance can cause property damage,
injury, or death. Read the installation, operation and maintenance instructions thoroughly before
installing or servicing this equipment.

2X-CA1,2,3,4 (01-22) 136958-A
GENERAL INFORMATION—CONTINUED
Important Safety Information—Continued
⚠ WARNING ⚠
• The optional power venter and venter flue adapter are designed for USEWITHTHESE DESIGNATED
PRODUCTS ONLY.
• DO NOT install these power venters on any other equipment including model F or B gravity-vented
unit heaters (use only the power venting kits that are especially designed for F and B models).
• DO NOT install these venters on equipment manufactured by others.
POWER VENT KITS
Descriptions, specifications, and component listings for power vent kit components are as follows.
Voltage
Voltage for power vent kit options is listed in Table 1.
Table 1. Voltage for Power Vent Kit Options
Option Voltage
CA1 115V
CA2 208V
CA3 230V
CA4 460V
Kit Selection
Power vent kit packages are listed in Table 2 for currently-manufactured models and for obsolete models in Table
3. Review carefully and ensure that parts are correct for the duct furnace being serviced. Required field-supplied
components are as follows:
•For furnace with horizontal flue: six (6) #10 sheet metal screws
•For furnace with vertical flue: nine (9) #10 sheet metal screws and vent pipe elbow (4- or 6-inch depending on
furnace model/size)
•Wiring: 18 GA for control (24V) wiring and 14 GA for line voltage
•Wiring accessories: flexible conduit for both control and line voltage wires, wire connectors, and conduit connectors
Table 2. Power Vent Kit Components for Currently-Manufactured Models
Component Model Option
Unit Size
075 100 125 150, 175 200, 225 250, 300*350** 400
PN
Option package X/DX/CX/XE/CXE
CA1 136959 136960 136961 136962 136963 136964 136965
CA2 136966 136967 136968 136969 136970 136971 136972
CA3 136973 136974 136975 136976 136977 136978 136979
CA4 136980 136981 136982 136983 136984 136985 136986
Venter assembly X/DX/CX/XE/CXE
CA1 29992 29992 29992 29994
CA2 30229 30229 30229 30233
CA3 30231 30231 30231 30235
CA4 29992 29992 29992 29994
Venter flue adapter X/DX/CX/XE/CXE All 14516 6536 6539 6542 12730 12731 12732
CX/CXE — — — 46163 —
Transformer, 0.25KVA,
460V to 115V X/DX/CX/XE/CXE CA4 11279 11279 11279
*For model DX, unit size 300, select the option package for model X, unit size 400.
**Option package PNs listed do not apply to unit size 350 for model CX or CXE. These units require the same components listed for unit size
350 except that the venter flue adapter is different.

3
X-CA1,2,3,4 (01-22) 136958-A
Table 3. Power Vent Kit Components for Obsolete Models
Component Model Option
Unit Size
030–105 125 140 150 170 200 225, 250 300 350, 400
PN
Option package*
XL/XLB CA1 — 136961 136961 136962 136962 136962 136963 —
CXL/CXLB — 136961
XL/XLB CA2 — 136968 136968 136969 136969 136969 136970 —
CXL/CXLB — 136968
XL/XLB CA3 —136975 136975 136976 136976 136976 136977 —
CXL/CXLB — 136975
XL/XLB CA4 — 136982 136982 136983 136983 136983 136984 —
CXL/CXLB — 136982
Venter assembly
XL/XLB CA1 29992 29992 29992 29992 29992 29992 29994
CXL/CXLB —
XL/XLB CA2 30229 30229 30229 30229 30229 30229 30233
CXL/CXLB —
XL/XLB CA3 30231 30231 30231 30231 30231 30231 30235
CXL/CXLB —
XL/XLB CA4 29992 29992 29992 29992 29992 29992 29994
CXL/CXLB —
Venter flue adapter XL/XLB All ** 6539 6539 6542 6542 6542 12730 24017 46163
CXL/CXLB — 6539
Transformer, 0.25KVA,
460V to 115V
XL/XLB/CXL/
CXLB CA4 11279 11279 11279 11279
*There are no kits for unit sizes 030–105, 300, 350, or 400. Order venter assembly, flue adapter, and transformer separately by unit size and
voltage.
**Flue adapter PNs are as follows: 6838 for unit sizes 030, 045, and 060, 6534 for unit size 075, or 20901 for unit size 105.
Venter Assembly
The venter assembly’s (see Figure 1) blower and motor are enclosed in a corrosion-resistant steel housing with a
baked enamel finish. The centrifugal blower with forward-curved blades is statically and dynamically balanced. The
venter assembly’s dimensions are listed in Table 4, its blower specifications are listed in Table 5, and its electical
specifications are listed in Table 6.
Table 4. Venter Assembly Dimensions
Unit Size Height Width Length Adapter Connection
ID
Vent Pipe
Connection ID
Inches (mm)
030–300 7-1/2 (191) 10 (254) 7-1/16 (179) 4-1/16 (103) 4-1/16 (103)
350–400 9-3/8 (238) 10-5/8 (270) 8-1/2 (216) 6 (152) 6 (152)
Figure 1. Venter Assembly
Table 5. Venter Assembly Blower Specifications
Unit Size
Static Pressure (IN WC)
0.00 0.25 0.50 0.75 1.00 1.25
CFM (70°F)
030–300 220 205 190 160 75 —
350–400 265 255 245 240 220 185

POWER VENT KITS—CONTINUED
Venter Assembly—Continued
Table 6. Venter Assembly Electrical Specifications
PN Voltage Amps Shipping Weight
(LB)
Control Motor*Full Load Locked Rotor
29992 24 115 1.4 1.94 11
29994 12
30229 24 208 0.72 0.95 11
30233 12
30231 24 230 0.7 0.94 11
30235 12
*Motor is 2-pole with nominal 3,000 RPM and maximum permissible voltage of 127V for 115V unit, 228V for 208V unit, and 250V for 230V
unit.
Control System
A pressure switch starts and stops the burner. A thermal switch provides post-purge. Low-voltage control includes
a built-in relay.
Venter Adapter
Ensure that the venter adapter (see Figure 2) designed and tested for the model and unit size of the furnace being
serviced is used to connect the venter to the furnace flue. The venter controls the volume of dilution air flow through
the drafthood and vent pipe to provide safe and efficient operation.
Model P/N Dimensions Model P/N Dimensions ModelP/N Dimensions
XL, XLB,
CXL,
CXLB 30,
45, 60
6838 XL, XLB,
CXL, CXLB
105
20901 X, XE, CX,
CXE 250,
300
12731
XL, XLB,
CXL,
CXLB 30,
45, 60
6534 X, CX, XE, CXE
125;
XL, XLB 125,
140;
CXL, CXLB
140, 170
6539 XL, XLB,
CXL, CXLB
300
24017
X, CX,
XE, CXE
75
14516 X, XE 150,
175;
CX, CXE 175;
XL, XLB 150,
170, 200;
CXL, CXLB
150, 200
6542 X, XE 350,
400; CX,
CXE 400;
DX 300
12732
X, CX,
XE, CXE
100
6536 X, XE 200, 225;
CX, CXE 225;
XL, XLB, CXL,
CXLB 225, 250
12730 XL, XLB,
CXL, CXLB
350, 400;
CX, CXE
350
46163
4X-CA1,2,3,4 (01-22) 136958-A
Figure 2. Venter Adapters

5
X-CA1,2,3,4 (01-22) 136958-A
Power Venter Sequence of Operation
Before installation, it is helpful to understand the fundamental operation and sequencing of the power venter as follows:
1. Venter’s relay coil is wired in series with thermostat—when thermostat calls for heat, thermostat contacts close
circuit.
2. After delay of 15–60 seconds, venter starts.
3. When venter starts, air from venter blower closes pressure switch that is built into venter.
4. Closing of pressure switch completes electric circuit to burner controls to open gas valve.
5. When thermostat is satisfied, gas valve closes.
6. Thermal switch permits post-purge venter blower operation to prevent unnecessary lockouts by temperature-
sensitive blocked vent system on furnace.
7. When venter blower stops, pressure switch opens.
KIT INSTALLATION
⚠ DANGER ⚠
This power venter is to be installed by a qualified agency in accordance with these instructions and
in compliance with all codes and requirements of authorities having jurisdiction. Failure to follow
instructions could result in death, serious injury, and/or property damage. The qualified agency
performing this work assumes responsibility for this installation.
Install the power vent kit in accordance with the following steps. Check model, unit size, and voltage to ensure that
the kit is correct for the furnace being serviced (refer to Table 1 and Table 2 or Table 3).
1. If furnace is installed, turn OFF gas and electric.
NOTE: The flue adapter has a large collar (either oblong or round) that connects to the flue collar
on the furnace and a smaller collar (4- or 6-inch) that connects directly to the venter (units with
horizontal flue) or vent pipe (units with vertical flue).
2. Install flue adapter (see Figure 3, DETAIL A):
a. Position adapter with smaller round collar B toward top (units with horizontal flue) or front (units with vertical
flue) of furnace.
b. Fit larger collar A over flue collar on furnace.
c. While holding adapter in place, drill 1/8-inch diameter hole (#30 bit) through connecting overlap of furnace
flue and adapter collar:
(1) For oblong horizontal flue, drill first hole on either side of top.
(2) For round horizontal flue, drill first hole in top portion of circle.
(3) For oblong vertical flue, drill first hole on either end of side toward front of furnace.
(4) For round vertical flue, drill first hole on portion of circle toward front of furnace.
d. Install #10 sheet metal screw in hole drilled in step c to secure collar A to furnace flue.
e. Drill two more holes through connecting overlap of furnace flue and adapter collar and install #10 sheet metal
screws. For oblong flue, drill one hole in opposite edge on same side as first hole and one hole in middle of
opposite side. For round flue, space three holes at equal distance apart.

6X-CA1,2,3,4 (01-22) 136958-A
DETAIL A DETAIL B
DETAIL C
KIT INSTALLATION—CONTINUED
Figure 3. Flue Adapter and Venter Assembly Installation
⚠ CAUTION ⚠
DO NOT position the venter with the discharge outlet (vent connection) pointing in a direction
below horizontal.
NOTE: The venter assembly is assembled and wired at the factory. It includes the blower, motor,
capacitor, pressure switch, thermal switch, and junction box.
3. Install venter assembly:
a. For units with horizontal flue (see Figure 3, DETAIL B):
(1) Position venter assembly on flue adapter with venter discharge outlet (vent connection) pointing in horizontal
to vertical direction.
(2) While holding venter assembly in place, drill hole through connecting overlap in top portion of venter
assembly and venter adapter.
(3) Install #10 sheet metal screw in hole drilled in step (2) to secure venter assembly to venter adapter.
(4) Drill two more holes at equal distance apart and install equal distances apart and install #10 sheet metal
screws.

7
X-CA1,2,3,4 (01-22) 136958-A
b. For units with vertical (top) flue (see Figure 3, DETAIL C):
(1) Position venter assembly on vent pipe elbow with venter discharge outlet (vent connection) pointing in
horizontal to vertical direction.
(2) While holding venter assembly in place, drill hole through connecting overlap in top portion of venter
assembly and vent pipe elbow.
(3) Install #10 sheet metal screw in hole drilled in step (2) to secure venter assembly to vent pipe elbow.
(4) Drill two more holes at equal distance apart and install equal distances apart and install #10 sheet metal
screws.
⚠ DANGER ⚠
This venter must be installed and wired in accordance with these installation instructions. The
venter pressure switch MUST be wired in series with the thermostat to interrupt the main gas valve
circuit and,after installation,pressure switch operation MUST be checked to verify proper operation.
NOTES:
• All wiring and connections, including electrical grounding, MUST be made in accordance with
the National Electric Code ANSI/NFPA No. 70 (latest edition) or in Canada, with the Canadian
Electrical Code, Part I-C.S.A. Standard C22.1.
• This installation must comply with local ordinances and applicable gas company requirements.
• A fuse required on C.G.A. units manufactured before OCT 1989.
• Model X, CX, XE and CXE furnaces manufactured before APR 1991 and model XL, CXL, CXLB,
and CXLB furnaces are not equipped with a blocked vent switch.
• Model X, CX, XE, and CXE furnaces manufactured after MAR 1991 are equipped with a blocked
vent switch. The blocked vent switch is standard on all units manufactured after MAR 1991.
• Model X, CX, XE, and CXE furnaces manufactured after SEP 2003 are equipped with a spark pilot.
• A thermal switch is standard on optional venters manufactured after MAR 1993.
4. Connect electrical wiring in accordance with wiring diagrams shown in Figure 4, Figure 5, or Figure 6
using flexible conduit for both line voltage and control voltage wiring.
Figure 4. Wiring Diagrams for Obsolete Optional Venters with Line Voltage Controls
(Models V201, V301, and V401)

8X-CA1,2,3,4 (01-22) 136958-A
FACTORY WIRING
FIELD WIRING
WHITE - W
PURPLE - PR
BLUE - BL
GREEN - G
YELLOW - Y
ORANGE - O
RED - R
BROWN - BR
BLACK - BK
WIRING CODE
TOTAL WIRE MINIMUM RECOMMENDED
LENGTH WIRE SIZE
150 FEET #18 GA.
250 FEET #16 GA.
350 FEET #14 GA.
FIELD CONTROL WIRING
BLOWER MOTOR
CUSTOMER'S
CONTACTOR COIL
CR
DISCONNECT SWITCH
115/1/60
GGRD
BL R
Y
LIMIT
CONTROL
W
OPTIONAL SINGLE
STAGE THERMOSTAT
R
WIRING IN VENTER (SHIPPED SEPARATE)
R
BK
R
BK
2 4
CONTACTS
VENTER RELAY
W
BK W
BK
Y
8 7
8 10 7
4
11
6
7
7
7
BK BR
H TD H
BR
BR
7
BK
BL
16
FAN TD
HEATER
MAIN
PILOT
BLOCKED VENT
SWITCH
MANUAL RESET
1Y
CR 11
COIL
VENTER RELAY
BR
BL
BL BK
PRESSURE
SWITCH
31
B
40 VA. CONTROL
BK
BL
24V
115V
BR
TRANSFORMER
Y
VENTER MOTOR
& CAPACITOR
(SEE NOTES)
REDUNDANT GAS VALVE
ALTERNATE W.R. OR ROBERTSHAW
BL P
BK
BR
MAIN
PILOT
M
C
PV
PILOT
MV
PV-MV
MAIN
REDUNDANT GAS VALVE
HONEYWELL
TERMINAL BLOCK -- HEATER COMPARTMENT
10, 11, B & W
CONTACTS
FAN TD
1 3
THERMAL SWITCH
6Y
BK
Y
BL
IGNITION
CONTROLLER PROBE
GND
SPARK
FLAME SENSING
MV/PV
MV
SENSE
TH
PV
24V GND
BR
GND BURNER
G
BURNER
GROUND
BK
- DOTTED WIRING AND THE FOLLOWING CONTROLS ARE SUPPLIED AND INSTALLED BY OTHERS: BLOWER RELAY
BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105° C., EXCEPT FOR
- CAUTION: IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED, IT MUST
- THE FOLLOWING CONTROLS ARE SUPPLIED AS OPTIONAL EQUIPMENT: THERMOSTAT
- THE FOLLOWING CONTROLS ARE SUPPLIED BY REZNOR FOR FIELD INSTALLATION: VENTER
- LINE AND BLOWER MOTOR BRANCH CIRCUIT WIRE SHOULD BE SIZED TO
PREVENT VOLTAGE DROP BEYOND FIVE PERCENT OF SUPPLY LINE VOLTAGE.
SENSOR LEAD WIRE WHICH MUST BE 150° C.
NOTES
- USE #14 GA. WIRE FOR LINE WIRING ON UNIT.
- USE #18 GA. WIRE FOR 24 VOLT CONTROL WIRING ON UNIT.
FUSES AND SIZE ACCORDING TO 1.25 TIMES THE MAXIMUM TOTAL INPUT AMPS.
- WHEN PROVIDING OR REPLACING FUSES IN THE FUSIBLE DISCONNECT SWITCH, USE DUAL ELEMENTS TIME DELAY
- DISCONNECT SWITCH IS FIELD FURNISHED OR AVAILABLE FROM FACTORY AS AN OPTION.
1, 4, 6, 7, 8,
- BLOWER MOTOR REMAINS ON AS DETERMINED BY FAN TIME DELAY.
- THE SENSING PROBE PROVES THE PRESENCE OF THE PILOT FLAME.
MAIN VALVE. THE MAIN GAS IGNITES AND UNIT FIRES AT FULL RATE.
- VENTER PRESSURE SWITCH CLOSES ENERGIZING THE PILOT GAS VALVE AND SPARK GAP TO PRODUCE A PILOT FLAME
ON EACH OPERATING CYCLE. THE SENSING PROBE PROVES THE PRESENCE OF THE PILOT FLAME AND ENERGIZING THE
SAFETY SWITCH PORTION OF THE CONTROL. THE SWITCH ACTION DE-ENERGIZES THE SPARK GAP AND ENERGIZES THE
- THERMOSTAT CALLS FOR HEAT ENERGIZING THE VENTER MOTOR.
- BLOWER MOTOR OPERATES FROM FAN TIME DELAY.
- SET THERMOSTAT AT LOWEST SETTING FOR SHUTDOWN.
- ENERGIZING THE GAS VALVE.
- DE-ENERGIZING THE IGNITOR.
- SET THERMOSTAT SWITCH AT DESIRED SETTING.
- TURN ON POWER, MAIN AND PILOT MANUAL GAS VALVES.
- SET THERMOSTAT SWITCH AT LOWEST SETTING.
OPERATING SEQUENCE
- IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION, THE SAFETY SWITCH CLOSES THE MAIN VALVE.
IF THE PILOT IS NOT ESTABLISHED WITHIN 120 SEC. THE UNIT LOCKS OUT FOR ONE HOUR, UNLESS IT IS RESET BY
INTERRUPTING POWER TO THE CONTROL CIRCUIT. (SEE LIGHTING INSTRUCTIONS)
6
7
8
9
10
11
12
13
14
15
16
17
18
26
25
24
23
22
21
20
19
6
7
8
9
10
11
12
13
14
15
16
17
18
26
25
24
23
22
21
20
19
VENTER
KIT INSTALLATION—CONTINUED
Figure 5. Wiring Diagram for Model X Unit with Spark Pilot
(Applies to Units with Block Vent Switch and Venter Assembly with Pressure Switch)

9
X-CA1,2,3,4 (01-22) 136958-A
Figure 6. Wiring Diagram for Unit with Match-Lit Pilot
(Applies to Units Manufactured After JUL 2012 with Sail Switch Replaced by Pressure Switch)
VENTING
⚠ DANGER ⚠
If this furnace is replacing an existing furnace, ensure that the vent is properly sized for the furnace
being installed. A properly-sized vent system is required for safe operation of this furnace. An
improperly-sized vent system can cause unsafe conditions and/or create condensation.
⚠ WARNING ⚠
Units installed in multiples require individual vent pipe runs and vent caps. Manifolding of vent
runs is not permitted.
NOTES:
• Venting must be in accordance with the National Fuel Gas Code Z223.1 or CAN/CGA B149.1 and
B149.2, Installation Code for Gas Burning Appliances and Equipment, and all local codes. Local
requirements supersede national requirements.
• A horizontal vent run is recommended for maximum fuel savings.
With the power venter installed, these furnaces are designed to operate safely and efficiently with either a horizontal
or vertical vent. Use either vent pipe approved for a Category III heater or appropriately-sealed single-wall pipe. Or,
if at least half of the equivalent length of the vent system is vertical, vent pipe approved for a Category I heater may
be used. A vent cap of a type approved for use with this heater is required.
Specific Venting Requirements
Venting requirements change with the addition of the power venter. Comply with the following specific requirements
and instructions:
• Vent pipe: If installed with a horizontal vent run, use either vent pipe approved for a Category III heater or
appropriately-sealed 26-gauge galvanized steel or equivalent single-wall pipe. If at least half of the equivalent
length of the vent system is vertical, vent pipe approved for a Category I heater may be used. Single-wall pipe or
double-wall (Type B) vent pipe are suitable for use with a Category I heater.
• Vent length: Minimum vent length is 5 feet.
• Pipe diameter: Use only one of the diameter(s) listed in Table 7 for the furnace being installed.
PRESSURE

10 X-CA1,2,3,4 (01-22) 136958-A
Table 7. Pipe Dimensions
Vent Diameter
(Inches (mm))
Unit Size
030–150 175 200 225 250 300 350 400
Maximum Length (Feet (Meters)*
4 (102) 100 (30) 75 (23) 50 (15) 35 (11) 30 (9) 15 (4.5) — —
6 (152) — — — — 100 (30)** 100 (30) 100 (30) 92 (28)
*Reduce the vent pipe length by 7 feet (2 meters) for a 45-degree elbow, 15 feet (4.5 meters) for a 90-degree elbow, or 10 feet (3 meters) for
a vent cap.
**If the venter outlet is 4 inches (102 mm), connect a taper-type enlarger to the venter outlet when installing 6-inch (152-mm) vent pipe.
• Vent system joints: Vent system joints depend on the installation and the type of pipe being used. If installed as
a Category III heater (required if more than half of the equivalent length of the vent system is horizontal), use vent
pipe specifically approved for Category III vent systems. Follow the pipe manufacturer’s instructions for proper
sealing. If installed with a Category I vent system (allowed only if at least half of the equivalent length of the vent
system is vertical), use at least two non-corrosive screws per vent pipe joint on single-wall pipe or follow the pipe
manufacturer’s instructions for joining double-wall pipe.
• Vent system support: Lateral runs should be supported every 6 feet using a non-combustible material, such as
strap steel or chain. Do not rely on the heater to support either horizontal or vertical vent pipe.
• Condensation: Any length of single-wall vent pipe exposed to cold air or run through an unheated area or an
area with an ambient temperature of ≤45°F must be insulated along its entire length with a minimum of 1/2-inch
foil-faced fiberglass, 1-1/2# density insulation.
• Vent terminal (pipe and vent cap): The vent cap must be the same size as the vent pipe (vent pipe is either 4
or 6 inches diameter). For optimum stability under wind conditions, use a manfacturer approved vent cap. See
Figure 7 and Figure 8 for requirements of vertical and horizontal vent termination. The vent terminal pipe may be
either single-wall or double-wall (type B). Check local codes for double-wall terminal requirement. If double-wall
pipe is used in the vent terminal with a single-wall vent run, follow the instructions below to attach the vent cap
and to connect the double-wall pipe to the single-wall vent pipe run.
⚠ WARNING ⚠
Vent terminal arrangements illustrated are applicable only to units with a power venter. Horizontal
vent termination requires a power venter. DO NOT use horizontal vent with gravity venting.
VENTING—CONTINUED
Specific Venting Requirements—Continued
Figure 7. Vertical Vent Terminal
Single-Wall Vent/Single-Wall Terminal Single-Wall Vent/Double-Wall Terminal

11
X-CA1,2,3,4 (01-22) 136958-A
Single-Wall Vent/Double-Wall Terminal
Single-Wall Vent/Single-Wall Terminal
Figure 8. Horizontal Vent Terminal
⚠ DANGER ⚠
If the vent terminal is to be installed near ground level, position it at least 6 inches above maximum
anticipated snow depth.
NOTE: Products of combustion can cause discoloration of some building finishes and deterioration
of masonry materials. Applying a clear silicone sealant that is normally used to protect concrete
driveways can protect masonry materials. If discoloration is an esthetic problem, relocate the vent
or install a vertical vent.
• Horizontal vent terminal clearances: A vent cap is required. Maintain a clearance of 18 inches from the wall to the
vent terminal cap for stability under wind conditions. The location of the termination of the horizontal vent system
must be in accordance with National Fuel Gas Code Z223.1. Required minimum clearances are listed in Table 8.
Table 8. Minimum Clearance Requirements for Horizontal Vent Terminal
Component/Structure Minimum Clearance, All Directions Unless Specified (Feet (Meters))
Forced air inlet within 10 feet (3.1 meters)*3 (0.9) above
Combustion air inlet of another appliance 6 (1.8)
Mechanical air supply inlet to any building Canada: 6 (1.8)
Any building opening (door, window, or gravity air inlet) 4 (1.2) horizontal and below
1 (0.3) above
Gas meter,** electric meter, and relief equipment US: 4 (1.2) horizontal
Canada: 6 (1.8) horizontal
Gas regulator** US: 3 (0.9) horizontal
Canada: 6 (1.8) horizontal
Adjoining building or parapet 6 (1.8)
Adjacent public walkway 7 (2.1) above
Grade (ground level) 3 (0.9) above
*Does not apply to the inlet of a direct vent appliance.
**Do not terminate the vent directly above a gas meter or service regulator.

12 X-CA1,2,3,4 (01-22) 136958-A
VENTING—CONTINUED
Connecting Vent Cap To Double-Wall (Type B) Vent Terminal Pipe
1. Position vent cap at exhaust end of double wall pipe—refer to flow arrow on vent pipe.
2. Slide vent cap inside pipe.
3. Drill hole—slightly smaller than screw being used—through overlap of vent cap and pipe.
4. Secure vent cap to pipe using 3/4-inch-long sheet metal screw.
5. Drill two more holes evenly spaced (120-degrees apart) and install two additional screws.
Connecting Single-Wall Vent Run to Double-Wall (Type B) Vent Terminal Pipe
1. Slide single-wall pipe inside inner wall of double-wall terminal pipe.
2. Drill hole—slightly smaller than screw being used—through both walls of double- and single-wall pipe.
3. Secure two pieces of pipe using 3/4-inch-long sheet metal screw. Do not overtighten.
4. Drill two more holes evenly spaced (120-degrees apart) and install two additional screws.
5. Seal annular opening (gap between single- and double wall pipe) with large bead of silicone sealant in opening.
Bead of sealant must be large enough to seal opening, but it is not necessary to fill full volume of annular area.
OPERATIONAL TESTING
⚠ DANGER ⚠
• DO NOT put a heater into service that does not properly exhaust flue gases to the outside
atmosphere.
• The gas burner in this gas-fired equipment is designed and equipped to provide safe and
economically-controlled complete combustion. However, if the installation does not permit the
burner to receive the proper supply of combustion air, complete combustion may not occur.
The result is incomplete combustion, which produces carbon monoxide, a poisonous gas that
can cause death. Safe operation of indirect-fired gas burning equipment requires a properly-
operating vent system which vents all flue products to the outside atmosphere. FAILURE TO
PROVIDE PROPERVENTINGWILL RESULT IN A HEALTH HAZARDTHAT COULD CAUSE SERIOUS
PERSONAL INJURY OR DEATH.
• Always comply with the combustion air requirements in the installation codes and instructions.
Combustion air at the burner should be regulated only by manufacturer-provided equipment.
NEVER RESTRICT OR OTHERWISE ALTERTHE SUPPLY OF COMBUSTION AIR TO ANY HEATER.
Indoor units installed in a confined space must be supplied with air for combustion as required by
code and in the heater installation manual. MAINTAIN THE VENT SYSTEM IN A STRUCTURALLY-
SOUND AND PROPERLY-OPERATING CONDITION.
1. Turn on the electric and the gas.
2. Refer to lighting instructions provided with furnace to light unit.
3. Test unit for proper venting:
a. With building at maximum negative pressure, operate furnace at normal input.
b. Note and check flow direction at relief opening of drafthood—room air should be flowing into relief opening.

13
X-CA1,2,3,4 (01-22) 136958-A
REPLACEMENT PARTS
NOTES:
• Currently-manufactured venter assemblies used in these power vent kits have 24V controls and
are identified by the prefix LV (LV301 and LV401).
• Obsolete venter assemblies with the prefix V have line voltage controls. These models are no
longer available, but replacement parts are the same as those listed for low-voltage models (see
Figure 4).
• Obsolete 200,300, and 400 series venters and components are not available.Replace the complete
venter with the correct currently-manufactured model.
• Replacement parts are shown in Figure 9 and listed in Table 9.
Table 9. Replacement Parts for Currently-Manufactured Venter Assemblies
Item
No. Component Description Venter Assembly PN
29992 30229 30231 29994 30233 30235
1 Cover Venter junction box 29596 29596
2Switch
Sail (replaced by pressure switch AUG 2012) — —
Pressure (replaced sail switch AUG 2012) 205444 205442
3 Thermal 121866 121866
4 Relay Assembly, with wires 30248 30248
Relay only 18549 18549
5Blower housing Assembly 268640 268641
6 Wheel Venter 29791 29792
7Junction box Venter, less cover and mounting bracket 29595 29595
8 Plate Cover 29594 29597
9 Fan blade 3-1/4 RHF, 312S bore 29793 29793
10 Mounting bracket Assembly, venter junction box 31393 31393
11 Motor
115V 87434 — 87434 —
208V — 30249 — — 30249 —
230V — — 29571
12 Capacitor Motor (replaces PN 87435 or 103181) 163894 — 163894 —
13 Tubing Silicone rubber, 10 inches 130388 130388
Figure 9. Replacement Parts
1
4
5
6
7
8910
11
12
3
2

14 X-CA1,2,3,4 (01-22) 136958-A
NOTES

15
X-CA1,2,3,4 (01-22) 136958-A
NOTES
This manual suits for next models
94
Table of contents
Other Reznor Fan manuals
Popular Fan manuals by other brands

RS PRO
RS PRO 470-4318 Instruction leaflet

Velleman
Velleman Perel CFANUSBD3 user manual

Kichler Lighting
Kichler Lighting 54 Skye LED instruction manual

LMF Clima
LMF Clima HPX Series Installation, operation & maintenance manual

Vornado
Vornado iControl Guide de l'utilisateur

minkaAire
minkaAire STEAL F729 instruction manual

Home Decorators Collection
Home Decorators Collection HAVERBROOK AM634-PN Use and care guide

Hunter
Hunter 50881 installation manual

MrCool
MrCool UNIVERSAL MDUCC150 Series Owners & installation manual

Regency Ceiling Fans
Regency Ceiling Fans CABANA owner's guide

Di4
Di4 Aria Forze 35 manual

Fanimation
Fanimation Islander FP320 Series Specification sheet