Rhymebus RM5G User manual

AC MOTOR DRIVE
Operation Manual
RM5G series
ISO 9001:2008

Quality․Satisfaction․Improvement․Innovation
http://www.rhymebus.com.tw
2004.01.09 Edition
2014.02.27 Revised

Thank you for using RHYMEBUS RM5G/P series drive. For proper operations and
safety purposes, please do read and follow specific instructions contained in this
manual before using the product. The manual shall be placed on the top of the
machine, and all the setup parameters and reference numbers must be properly
recorded in Attachment 2 to facilitate future maintenance and repairs.
PREFACE

Please read this manual thoroughly and pay attention to the safety precautions
marked with ― DANGER ‖ or ― CAUTION ‖ before the installation, wiring,
maintenance, or troubleshooting.
Only the qualified personnel may proceed with the installation, wiring, testing,
troubleshooting, or other tasks.
※Qualified Personnel: Must be familiar with the fundamentals, structures,
characteristics, operating procedures, and installation, and this personnel must
read the manual in details and follow the steps of security measures to prevent
possible dangers.
DANGER
User may cause the casualty or serious damages if user
does not abide by the instructions of the manual to
execute the tasks.
CAUTION
User may cause injuries to the people or damage the
equipment if user does not abide by the instructions of
the manual to execute the tasks.
※Although the ― ‖ mark may indicate minor damages, serious damages or
injuries may be possibly incurred if the caution is not under user’s attention.
Installation
CAUTION
a. The installation shall take place only on top of the metal surface or any material
with the fire resistant. Any place or location of high temperature, moist, oil and
gas, cotton fiber, metal powder and erosive gas shall be avoided.
b. If the product specification indicates IP00 (the protective level of the equipment
structure), any human contact is forbidden to avoid the electric shock. The option
of installing AC reactor(ACL) or DC reactor(DCL) shall be very cautious, too.
c. Please note the surrounding temperature shall not exceed 50°C (or 40°C for
RM5P) when the installation needs to be placed inside the control panel.
d. For the environment of storage and installation, please follow the instructions of
the environmental conditions illustrated in the sections of the common
specification of RM5G and RM5P.
SAFETY PRECAUTION

Wiring
DANGER
a. Do Not conduct any wiring during the systempower ON to avoid the electric shock.
b. R/L1,S/L2,T/L3 are power inputs (electric source terminals) and U/T1,V/T2,W/T3
are drive’s outputs connecting to a motor. Please Do Not connect these input and
output terminals to P, P○
+, N, N○
-, P1 and PR terminals.
c. Once the wiring is completed, the cover of the drive must be put back and must
seal the drive to avoid other’s accidental contact.
d. 100V or 200V series drives must not be connected to the electric source of
346/380/415/440/460/480V.
e. The main circuit and multi-function terminals cannot connect to ground
terminal(PE).
f. PE terminal must be exactly grounded. Ground the drive in compliance with
the NEC standard or local electrical code.
g. Please refer to the ―section 2-3-4 Description of Terminals”for the screwing
torque of the wiring terminal.
h. Please refer to the national or local electric code for the appropriate spec. of the
cords and wires.
i. Please install an appropriate Molded Case Circuit Breaker (MCCB) or Fuse at
each path of power lines to a drive.
j. Please install the thermal relay between the individual motor and the drive when
using one drive to propel several motors.
k. Do Not connect power factor leading capacitor, surge absorber, or
non-three-phase motor to drive’s U/T1,V/T2,W/T3 side.
l. AC reactor (ACL) installation is required when the power capacity exceeds
500kVA or 10 times or more than the drive rated capacity.
m. After power off (30HP below models must wait at least 5 minutes; 40HP~75HP
models must wait at least 10 minutes; 100HP above models must wait at least
20 minutes). Do Not touch the drive or perform any unwiring actions before drive
indicator light (CHARGE) turns off. Use a multimeter with the DC voltage stage
to measure the cross voltage between P(+) and N(-) ports (DC bus voltage must
be less than 25V).
n. Whenthe motor dothe voltage-proof, insulationtesting, unwiringthe U/T1,V/T2,W/T3
terminal of drive at first.
CAUTION
a. The RM5G/P series are designed to drive a three-phase induction motor. Do Not
use for single-phase motor or other purposes.
b. The main circuit and control circuit must be wired separately; control circuit must
use a shielded or twisted-pair shielded wires to avoid possible interferences.

Operation
DANGER
a. Do Not open or remove the cover while power is on or during the operation. Do
close up the cover before powering on the drive. Do Not remove the cover except
for wiring or periodic inspection when power off.
b. At the function F_078=1 or 3, the drive will automatically restart when the power
is restored. Stay away from the motor and machine.
c. At the function F_003=0 and F_001=0 or 1, the
STOP
RESET
key on keypad is ineffective.
Please use an emergency stop switch separately for safe operations.
d. The drive can produce high frequency outputs. Before adjusting the frequency,
please check the specifications of motor carefully to prevent the motor from
unexpected damages.
e. If any of the protective functions have been activated, and the start command is
set to terminal control (F_001=0 or 1). First remove the case and check if the all
running commands set to OFF. Then press the
STOP
RESET
key to release the alarm.
CAUTION
a. Do Not touch the heat sink or brake resistors due to the high heat.
b. Some models attach nylon rope. Do Not proceed the movement or hanging the
drive by this nylon rope to avoid unexpecting accident. Please select a suitable
rope to proceed the movement or hanging the drive.

Compliance with UL standards and CSA standards (cUL-listed for Canada)
CAUTION
1. "Risk of Electric Shock"
Before starting or inspection, turn OFF the power and wait at least 5 minutes,
and check for residual voltage between terminal P and N with a multimeter or
similar instrument has dropped to the safe level (50VDC or below), to avoid a
hazard of electric shock.
2. These devices are intended for use in Pollution Degree 2 environments.
3. Maximum surrounding air temperature is 50C for RM5G series and 40C for
RM5P series.
4. Short circuit rating
"Suitable For Use On A Circuit Capable Of Delivering Not More Than 5000 rms
Symmetrical Amperes, 240V Maximum for 200V class." Models RM5G, RM5P
rated for 200V class input.
"Suitable For Use On A Circuit Capable Of Delivering Not More Than 5000 rms
Symmetrical Amperes, 480V Maximum for 400V class." Models RM5G, RM5P
rated for 400V class input.
"Integral solid state short circuit protection does not provide branch circuit
protection. Branch circuit protection must be provided in accordance with the
National Electrical Code and any additional local codes."
5. Install UL certified branch circuit fuse between the power supply and the drive,
referring to the table below.
Single-Phase 200V Series
Model number
Fuse type
Fuse current rating (A)
RM5G-2001/2-1PH
Class RK5
(250Vac, 200kA I.R.)
10
RM5G-2001-1PH
20
RM5G-2002-1PH
50

Compliance with UL standards and CSA standards (cUL-listed for Canada)
(continued)
CAUTION
Three-Phase 200V Series
Model number
Fuse type
Fuse current rating (A)
RM5G-2001/2
Class RK5
(250Vac, 200kA I.R.)
5
RM5G-2001
10
RM5G-2002
15
RM5G-2003
20
RM5G-2005
30
RM5G-2007
Class T
(300Vac, 200kA I.R.)
50
RM5G-2010
80
RM5G-2015
100
RM5P-2010
80
RM5P-2015
100
Three-Phase 400V Series
Model number
Fuse type
Fuse current rating (A)
RM5G-4001
Class RK5
(600Vac, 200kA I.R.)
5
RM5G-4002
10
RM5G-4003
15
RM5G-4005
20
RM5G-4007
Class T
(600Vac, 200kA I.R.)
30
RM5G-4010
30
RM5G-4015
40
RM5G-4020
60
RM5P-4010
30
RM5P-4015
40
RM5P-4020
60

CAUTION
6. Main circuit terminal wiring
"Use 75C Cu wire only."
―Field wiring connection must be made by a UL Listed and CSA Certified
closed loop terminal connector sized for the wire gauge involved. Connector
must be fixed using the crimp tool specified by the connector manufacturer.‖
See table below for main circuit wire size.
200V Class Series
Model number
Wire size AWG (mm2)
Input
(R/L1, S/L2, T/L3)
Output
(U/T1, V/T2, W/T3)
Grounding
RM5G-2001/2-1PH
16 (1.3)
16 (1.3)
16 (1.3)
RM5G-2001-1PH
12 (3.3)
16 (1.3)
12 (3.3)
RM5G-2002-1PH
12 (3.3)
16 (1.3)
RM5G-2001/2
16 (1.3)
16 (1.3)
16 (1.3)
RM5G-2001
16 (1.3)
16 (1.3)
RM5G-2002
14 (2.1)
16 (1.3)
14 (2.1)
RM5G-2003
14 (2.1)
14 (2.1)
RM5G-2005
10 (5.3)
10 (5.3)
10 (5.3)
RM5G-2007
8 (8.4)
8 (8.4)
RM5G-2010
6 (13.3)
6 (13.3)
8 (8.4)
RM5G-2015
4 (21.1)
4 (21.1)
RM5P-2010
6 (13.3)
6 (13.3)
8 (8.4)
RM5P-2015
4 (21.1)
4 (21.1)

Compliance with UL standards and CSA standards (cUL-listed for Canada)
(continued)
CAUTION
400V Class Series
Model number
Wire size AWG (mm2)
Input
(R/L1, S/L2, T/L3)
Output
(U/T1, V/T2, W/T3)
Grounding
RM5G-4001
18 (0.8)
18 (0.8)
18 (0.8)
RM5G-4002
18 (0.8)
18 (0.8)
RM5G-4003
16 (1.3)
16 (1.3)
16 (1.3)
RM5G-4005
14 (2.1)
14 (2.1
14 (2.1)
RM5G-4007
12 (3.3)
12 (3.3)
12 (3.3)
RM5G-4010
10 (5.3)
10 (5.3)
10 (5.3)
RM5G-4015
8 (8.4)
10 (5.3)
RM5G-4020
8 (8.4)
8 (8.4)
RM5P-4010
10 (5.3)
10 (5.3)
10 (5.3)
RM5P-4015
8 (8.4)
10 (5.3)
RM5P-4020
8 (8.4)
8 (8.4)

No Text on This Page

Features
a.
RM5G series are suitable for the constant torque load, like mixer,
conveyor, etc.
b.
RM5P series are suitable for variable torque load, like fan, pump, etc.
c.
RM5G series designed for heavy-duty load applications. Overload
capability is 150% drive’s rated output current for 1 min.
d.
RM5P series designed for light-duty load applications. Overload
capability is 120% drive’s rated output current for 1 min.
e.
Energy-saving setting for light-duty load.
f.
The analog input signal filter has the adjustable function.
g.
The analog input signal with addition, subtraction, and multiplication
functions can select V or F for the independent adjustment.
h.
The responding time of the digital input signal is adjustable (5 ~ 16
ms).
i.
6 digit 7-segment display can exhibit 8 different statuses (frequency,
speed, voltage, current, etc.).
j.
Programmable input and output terminals. The input signal can be
switched as SINK/SOURCE mode.
k.
Two sets of programmable relays.
l.
Two types of keypads. (digital type: KP-201C; analog type: KP-202)
m.
Drive can connect 3 sets of individual display (DM-501) to display
operating status.
n.
Running hours and supply power time of drive can be recorded.
o.
The drive can control and start the synchronous motor.
p.
The switching frequency can be adjusted between 800Hz ~ 15kHz.
q.
Adjustable accel/decel time from 0.015sec up to 222days.
INTRODUCTIONS

Chapter 1 Cautions Before Installation.................................... 1
1-1 Product Verification ................................................................................1
1-1-1 Confirmation of Appearance...............................................................1
1-1-2 The description of nomenclature:........................................................1
1-1-3 Confirmation of Accessories...............................................................2
1-2 RM5G Standard Specifications ...............................................................2
1-2-1 Single-Phase 100V Series..................................................................2
1-2-2 Single-Phase 200V Series..................................................................3
1-2-3 Three-Phase 200V Series ..................................................................3
1-2-4 Three-Phase 400V Series ..................................................................5
1-3 RM5P Standard Specifications................................................................7
1-3-1 Three-Phase 200V Series ..................................................................7
1-3-2 Three-Phase 400V Series ..................................................................8
1-4 The Features of Control and Operation.................................................10
1-4-1 RM5G Series...................................................................................10
1-4-2 RM5P Series...................................................................................13
Chapter 2 Installation and Confirmation................................ 17
2-1 Basic Equipment...................................................................................17
2-2 Installing the Drive................................................................................17
2-3 Descriptions of Terminal and Wiring Diagram ......................................21
2-3-1 Wiring Diagram................................................................................21
2-3-2 SINK / SOURCE Definition...............................................................27
2-3-3 Using a PLC Circuit..........................................................................27
2-3-4 Description of Terminals...................................................................28
2-3-5 Control Board..................................................................................35
2-3-6 Wiring Cautions and Specifications...................................................37
Chapter 3 The Setting of Keypad............................................ 41
3-1 Digital Type Keypad (KP-201C) for RM5G/P..........................................41
3-2 Analog Type Keypad (KP-202) for RM5G/P ...........................................41
3-2-1 Description of Switches and Pot Knob...............................................42
3-2-2 Description of DIP Switches..............................................................44
3-3 Status of Multi-Function Input/Output Terminals and DIP Switch .........44
3-3-1 DIP Switch ......................................................................................44
3-3-2 Multi-function Input/Output Terminals................................................44
3-4 The Operation of Keypad (KP-201C) and Monitor Mode........................45
3-4-1 Operation of Keypad........................................................................45
3-4-2 Description of Monitor Mode.............................................................46
3-4-3 Description of Function Setting Mode................................................47
3-4-4 Description of Parameter Setting Mode .............................................47
3-4-5 Operation at Monitor Mode...............................................................48
3-4-6 Start / Stop Operation of Drive..........................................................48
3-4-7 Parameter Copy; Restore Default Value; Save/Restore Setting Value .49
Chapter 4 Parameter List ........................................................ 53
Chapter 5 Parameter Setting Description.............................. 64
A. The Keypad Setup.............................................................. 64
TABLE OF CONTENTS

B. Preset Speed Setup............................................................ 70
C. Multi-Speed Accel./Decel. Time Setup.............................. 72
D. V/F Pattern Setup ............................................................... 74
E. Analog Input Command Setup .......................................... 76
F. The Upper and Lower Frequency Limit Setup.................. 81
G. Analog Output Setup ......................................................... 82
H. Motor Protection Setup...................................................... 84
I. Multi-Function Input Setup.................................................. 85
J. Multi-Function Outputs Setup............................................ 92
K. Frequency Detection.......................................................... 97
L. Automatic Torque Compensation ..................................... 97
M. Overload Detection Setup................................................. 97
N. Stall Prevention Setup ....................................................... 99
O. DC Braking Setup............................................................. 100
P. Drive Status after Power Failure ..................................... 101
Q. Jump Frequency .............................................................. 103
R. Speed Tracing................................................................... 103
S. Holding Frequency and Time Interval............................. 104
T. External Indicators ........................................................... 104
U. Other Functions................................................................ 105
V. Function Selection of KP-202 Keypad............................ 108
Chapter 6 Operation Procedures and Fault Protection ...... 112
6-1 Operation Procedures.........................................................................112
6-2 Fault Protection Display and Troubleshooting....................................114
Appendix A Peripheral Equipment of Drive......................... 120
Appendix B Motor Selection and Insulation Measurement 121
a. Standard Motor.....................................................................................121
b. Special Motors......................................................................................121
c. Insulation Measurement of Drive and Motor .........................................122
1. Measure the drive insulation impedance...............................................122
2. Measure the motor insulation impedance .............................................122
Appendix C Instruction of Drive Charging .......................... 123
Appendix D Dynamic Brake Unit and Braking Resistor ..... 124
a. Braking transistor is installed in the following models .........................124
b. Outline of braking resistor (option).......................................................124
c. Rated specification of braking resistor .................................................124
d. Recommending specification of braking resistor .................................125
AC 200V Series......................................................................................125
AC 400V Series......................................................................................126
e. Recommending specification of dynamic brake unit (DBU6) and braking
resistor .................................................................................................127
AC 200V Series......................................................................................127
AC 400V Series......................................................................................127

f. Wiring Diagram of External Braking Resistor and Thermal Switch........128
g. Wiring Diagram of External Dynamic Brake Unit(DBU6) and Thermal
Switch...................................................................................................130
Appendix E Selection of Reactor.......................................... 132
AC Reactor (ACL) Specifications..............................................................133
DC Reactor (DCL) Specifications..............................................................134
Outline dimensions of AC reactor (ACL)...................................................135
Outline dimensions of DC reactor (DCL)...................................................136
Appendix F Selection of Zero-Phase Radio Frequency Filter
................................................................................................... 137
Appendix G Selection of EMC Filter..................................... 141
Appendix H Instruction of Remote Controller and External
Display....................................................................................... 143
a. Remote controller .................................................................................143
b. External display: DM-501 ......................................................................145
Appendix I Outline Dimension Drawing of Drives............... 146
Appendix J Auxiliary Controller (ACE-S Series)................. 150
Attachment 1 Dimension of Keypad (KP-201C, KP-202) .... 153
Attachment 2 Setting Memo.................................................. 154
Attachment 3 Fault Display................................................... 157

Chapter 1 Cautions Before Installation
1
1
Chapter 1 Cautions Before Installation
1-1 Product Verification
The product has passed the strictest quality test before shipped out from the
factory. However, the product might possibly sustain minor damages due to the
impact, shaking, vibration, and other factors during the transportation. Please
make sure to verify the following items after receiving this product. If the product
verification finds anything abnormal, please contact the agent immediately for
the further assistance.
1-1-1 Confirmation of Appearance
1. Check up the specifications at shipping label on the carton is identical
with the nameplate of drive.
2. Check up the appearance of drive for any paint chipped off, smearing,
deformation of shape, etc.
3. Check up the nameplate (as below example by RM5G-2050) of the
drive to verify the product descriptions with the order specification.
Rhymebus Corporation, TAIWAN
BXXXXXXXX
103F4-1(AZXXXXXX)
3PH 200-240V 145A 0.1-400.0Hz
3PH 200-240V 176A 50/60Hz
RM5G-2050
SERIAL NO.
PGM NO.
OUTPUT
INPUT
TYPE
Model Number
Input Power Specs
Output Current & Capability
Software Number
Product Serial Number
ISO 9001 IP20
BXXXXXXXX
1-1-2 The description of nomenclature:
RM5G -2 050 B (-1PH) Input Power Phase
Brake type
Type code See maximum applicable motor
Input voltage 1: AC 100~120V
Blank: Three-phase
-1PH: Single-phase
B: build-in braking transistor
(with build-in braking transistor which is the
standard for the drive with rated power less
than 15HP, 200V class and 25HP, 400V class.
These standard brake type is not indicated in
the nameplate of the drive)
Blank: no braking resistor included
2: AC 200~240V
Product series RM5G: Heavy-duty load usage
RM5P: Light-duty load usage
4: AC 380~480V

Chapter 1 Cautions Before Installation
2
1
Maximum Applicable Motor (HP/Kw)
Type
code
Horse
power
Type
code
Horse
power
Type
code
Horse
power
Type
code
Horse
power
001/2
0.5
015
15
075
75
300
300
001
1
020
20
100
100
350
350
002
2
025
25
125
125
420
420
003
3
030
30
150
150
500
500
005
5
040
40
175
175
600
600
007
7.5
050
50
200
200
700
700
010
10
060
60
250
250
-
-
1-1-3 Confirmation of Accessories
One operation manual is inclusive. Please verify other accessories
inclusively such as braking resistor, AC reactor, etc..
※Please refer to the standard specifications to verify the product
specifications with your requirements.
1-2 RM5G Standard Specifications
1-2-1 Single-Phase 100V Series
Model name
(RM5G-□□□□-1PH)
1001/2
1001
1002
Maximum applicable motor (HP / kW)
0.5/0.4
1/0.75
1.5/1.1
Rated output capability (kVA)
1
1.6
2.3
Rated output current (A)
2.5
4.2
6
Rated output voltage (V)
Three-phase 200~240V
Range of output frequency (Hz)
0.1~400.00Hz
Power source (ψ, V, Hz)
Single-phase 100~120V 50/60Hz
Input current (A)
8.8
18
24
Permissible AC power source
fluctuation
90~132V 50/60Hz / ±5%
Overload protection
150% of drive rated output current for 1 min.
Cooling method
Nature cooling
Fan cooling
Applicable safety standards
—
Protective structure
IP20
Weight / Mass(kg)
1.7
1.8
1.8

Chapter 1 Cautions Before Installation
3
1
1-2-2 Single-Phase 200V Series
Model name
(RM5G-□□□□-1PH)
2001/2
2001
2002
Maximum applicable motor (HP / kW)
0.5/0.4
1/0.75
2/1.5
Rated output capability (kVA)
1.1
1.9
3
Rated output current (A)
3
5
8
Rated output voltage (V)
Three-phase 200~240V
Range of output frequency (Hz)
0.1~400.00Hz
Power source (ψ, V, Hz)
Single-phase 200~240V 50/60Hz
Input current (A)
7
13.5
19
Permissible AC power source
fluctuation
176~264V 50/60Hz / ±5%
Overload protection
150% of drive rated output current for 1 min.
Cooling method
Nature cooling
Fan cooling
Applicable safety standards
UL508C, CSA C22.2 No. 14-05
Protective structure
IP20, UL open type
Weight / Mass(kg)
1.8
1.9
2
※Please refer to page 112 for the single-phase application of220V.
1-2-3 Three-Phase 200V Series
Model name
(RM5G-□□□□)
2001/2
2001
2002
2003
2005
2007
2010
2015
Maximum applicable
motor (HP / kW)
0.5/0.4
1/0.75
2/1.5
3/2.2
5/3.7
7.5/5.5
10/7.5
15/11
Rated output capability
(kVA)
1.1
1.9
3
4.2
6.5
9.5
13
18
Rated output current (A)
3
5
8
11
17
25
33
46
Rated output voltage (V)
Three-phase 200~240V
Range of output
frequency (Hz)
0.1~400.00Hz
Power source (ψ, V, Hz)
Three-phase 200~240V 50/60Hz
Input current (A)
5
6
10
14
18
30
40
60
Permissible AC power
source fluctuation
176~264V 50/60Hz / ±5%
Overload protection
150% of drive rated output current for 1 min.
Cooling method
Nature cooling
Fan cooling
Applicable safety
standards
UL508C, CSA C22.2 No.14-05
Protective structure
IP20, UL open type
Weight / Mass(kg)
1.8
1.8
1.9
2
2.1
5.3
5.4
5.7

Chapter 1 Cautions Before Installation
4
1
Model name
(RM5G-□□□□)
2020
2025
2030
2040
2050
2060
2075
2100
Maximum applicable
motor (HP / kW)
20/15
25/18.5
30/22
40/30
50/37
60/45
75/55
100/75
Rated output capability
(kVA)
23
28
34
44
55
67
84
112
Rated output current (A)
60
74
90
115
145
175
220
295
Rated output voltage (V)
Three-phase 200~240V
Range of output
frequency (Hz)
0.1~400.00Hz
Power source (ψ, V, Hz)
Three-phase 200~240V 50/60Hz
Input current (A)
69
85
103
132
176
200
240
280
Permissible AC power
source fluctuation
176~264V 50/60Hz / ±5%
Overload protection
150% of drive rated output current for 1 min.
Cooling method
Fan cooling
Applicable safety
standards
-
Protective structure
IP20
IP00 (IP20 OPTION)
Weight / Mass(kg)
16
16
16
17
40
41
44
61
Model name
(RM5G-□□□□)
2125
2150
2200
2250
-
-
Maximum applicable
motor (HP / kW)
125/90
150/110
200/160
250/200
-
-
Rated output capability
(kVA)
132
154
223
267
-
-
Rated output current (A)
346
405
585
700
-
-
Rated output voltage (V)
Three-phase 200~240V
Range of output
frequency (Hz)
0.1~400.00Hz
Power source (ψ, V, Hz)
Three-phase 200~240V 50/60Hz
Input current (A)
330
380
550
660
-
-
Permissible AC power
source fluctuation
176~264V 50/60Hz / ±5%
Overload protection
150% of drive rated output current for 1 min.
Cooling method
Fan cooling
Applicable safety
standards
-
Protective structure
IP00 (IP20 OPTION)
Weight / Mass(kg)
89
90
164
167
-
-

Chapter 1 Cautions Before Installation
5
1
1-2-4 Three-Phase 400V Series
Model name
(RM5G-□□□□)
4001
4002
4003
4005
4007
4010
4015
4020
Maximum applicable
motor (HP / kW)
1/0.75
2/1.5
3/2.2
5/3.7
7.5/5.5
10/7.5
15/11
20/15
Rated output capability
(kVA)
1.9
3
4.6
6.9
11
14
18
23
Rated output current (A)
2.5
4
6
9
14
18
24
30
Rated output voltage (V)
Three-phase 380~480V
Range of output
frequency (Hz)
0.1~400.00Hz
Power source (ψ, V, Hz)
Three-phase 380~480V 50/60Hz
Input current (A)
3.5
5
8
12
16
22
28
38
Permissible AC power
source fluctuation
332~528V 50/60Hz / ±5%
Overload protection
150% of drive rated output current for 1 min.
Cooling method
Nature
cooling
Fan cooling
Applicable safety
standards
UL508C
UL508C,
CSA C22.2 No.14-05
Protective structure
IP20, UL open type
Weight / Mass(kg)
1.8
1.9
2
2
5.3
5.4
5.6
5.7
Model name
(RM5G-□□□□)
4025
4030
4040
4050
4060
4075
4100
4125
Maximum applicable
motor (HP / kW)
25/18.5
30/22
40/30
50/37
60/45
75/55
100/75
125/90
Rated output capability
(kVA)
30
34
46
56
66
84
114
134
Rated output current (A)
39
45
61
73
87
110
150
176
Rated output voltage (V)
Three-phase 380~480V
Range of output
frequency (Hz)
0.1~400.00Hz
Power source (ψ, V, Hz)
Three-phase 380~480V 50/60Hz
Input current (A)
45
52
70
84
100
130
155
177
Permissible AC power
source fluctuation
332~528V 50/60Hz / ±5%
Overload protection
150% of drive rated output current for 1 min.
Cooling method
Fan cooling
Applicable safety
standards
-
Protective structure
IP20
IP00 (IP20 OPTION)
Weight / Mass(kg)
5.8
16
16
17
18
44
45
47
Other manuals for RM5G
1
Table of contents
Other Rhymebus Controllers manuals
Popular Controllers manuals by other brands

Storm Manufacturing
Storm Manufacturing Buckner Superior Sterling Series Frequently asked questions

Eaton
Eaton CAAE-01/01 Instruction leaflet

Eaton
Eaton DS7 Series Instructional Leaflet

IAI
IAI RCP6 Series First step guide

YASKAWA
YASKAWA CIPR-GA50C series Installation and operation instruction

BIFFI
BIFFI FCB Series Service instructions