manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Rifox
  6. •
  7. Control Unit
  8. •
  9. Rifox EF 1112 User manual

Rifox EF 1112 User manual

Other Rifox Control Unit manuals

Rifox 10210 User manual

Rifox

Rifox 10210 User manual

Rifox WO-1210-ZR User manual

Rifox

Rifox WO-1210-ZR User manual

Rifox 1513 User manual

Rifox

Rifox 1513 User manual

Rifox WU-1550 User manual

Rifox

Rifox WU-1550 User manual

Popular Control Unit manuals by other brands

Seitz 14A80 user manual

Seitz

Seitz 14A80 user manual

Wilo RS485 Installation and operating instructions

Wilo

Wilo RS485 Installation and operating instructions

Becker CentralControl CC41 Commissioning Instruction

Becker

Becker CentralControl CC41 Commissioning Instruction

SICK CDB650 operating instructions

SICK

SICK CDB650 operating instructions

Panduit NetKey NKP5E88M Series installation instructions

Panduit

Panduit NetKey NKP5E88M Series installation instructions

MX Options Concentric Petite Fitting instructions

MX

MX Options Concentric Petite Fitting instructions

Clean Water Systems Fleck 2510 Installation & start?up guide

Clean Water Systems

Clean Water Systems Fleck 2510 Installation & start?up guide

Fairchild FSB44104A user guide

Fairchild

Fairchild FSB44104A user guide

LEGRAND Wattstopper LMIN-104 installation instructions

LEGRAND

LEGRAND Wattstopper LMIN-104 installation instructions

PMK ATT10BNCS instruction manual

PMK

PMK ATT10BNCS instruction manual

Tektronix TDS3FFT user manual

Tektronix

Tektronix TDS3FFT user manual

Woodward easYgen Technical manual

Woodward

Woodward easYgen Technical manual

Balluff BNI EIP-502-105-R015 user guide

Balluff

Balluff BNI EIP-502-105-R015 user guide

NXP Semiconductors TWR-LS1021A Getting started

NXP Semiconductors

NXP Semiconductors TWR-LS1021A Getting started

Advantech PCM-3117 Startup manual

Advantech

Advantech PCM-3117 Startup manual

Danfoss MCO 101 manual

Danfoss

Danfoss MCO 101 manual

Moons' Lin Engineering R701P user manual

Moons'

Moons' Lin Engineering R701P user manual

Aventics RV1 operating instructions

Aventics

Aventics RV1 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Rev. 02/2017-Di Page 1 of 4 Subject to modification !
for Type EF 1112
as Flow Control Unit ZR, PN 25
1.0 Safety instructions
1.1 Proper use
Any improper use, intervention in the design and deviation from the design data automatically
lead to termination of the warranty. The
float-con
trolled condensate trap is designed for the
discharge of condensate from steam,
co
mpressed air and pressure gas systems. Any other
use is not permissible. The manufacturer is not liable for
dam
age resulting from any other
use. The user
o
r operator bears the risk in this case. This also applies analogouslyto
incorrect assembly, startup, use
an
d maintenance.
1.2 Warnings and symbols
There is a risk of personal injury due to escaping operating medium as well as because of
pressure, temperature and weight. Failure to comply with these warnings may lead to accidents.
Follow the instructions in this operating manual.
The operator must ensure that this operating manual and, if necessary, other relevant
documents are available on site.
Only trained or instructed personnel maybe assigned to handling this
equipment. Any mode of operation that mayimpair safety must be avoided.
2.0 General description and use
Design of the condensate trap
1 Housing
cover
2 Housing
gasket
3 Housing with
connections
5 Set of screws with
nuts
7 Float
control
8 Supporting
structure
w
ith
rotary slide
valve
9 Float with
fork
10
Bush
11 Set of
Seals
12 Sight
glass
13 Set of screws with
nuts
14
RWG-Frame
16 Control
screw
17
RWG-Seals
Fig.1
2.2 Identification, operating limits on rating plate or housing
Rev. 02/2017-Di Page 2 of 4 Subject to modification !
2.3 Functional limit of standard float control (PMO in bar g): According to Fig. 2
Fig.2
2.4 Performance: According to Works Standard-Sheet/ RIFOX
2.5 Installation: According to Fig. 2
2.6 Functional limit of standard float control
Cross-Section
Max- line
pressure
in bar ü
Dimension Z mm
20/190
12
appr.110
20/340
8
appr.110
SQ/SK
Spec. design acc. to operating data
2.7 Flow control unit: Function / gas compensation
In the lower float position the supply flow is open and closed in upper
position. When reaching a lower tank level the float control unit opens. The
addition to the tank is determined by the dimension Z. To allow a free rising
and failing of the tank level existing in the flow control unit, a pressure
compensation line has to be installed (as shown in figure 2).
3.0 Assembly
3.1 Fitting
Remove protective caps from inlet and outlet.
Fitting position according to Fig. 1 and 2
Flow direction according to the arrow provided on the rating plate
4.0 Maintenance / Inspection
4.1 Opening the flow control unit an d dismantling the float control
1. The condensate trap must be depressurized
2. Remove the flow control unit completely
3. Loosen hexagon nuts (5.) evenly crosswise,take off cover (1).
4. Loosen support screw (10) and unscrew it completely
Rev. 02/2017-Di Page 3 of 4 Subject to modification !
Punch mark
Notch
Fig.3
4.2 Disassembling and cleaning the float control (Fig.3)
1. After removing the cotter pin (i), the rotary valve (d)
is simply pulled out to the side.
2. Clean the parts using, for example, benzine.
3. Check the rotary valve (d) for wear along the sealing edge. If wear is
detected, the support body (c) together with the rotary valve (d)
must be replaced. A precise leak test must be carried out by Rifox.
4. During assembly ensure that the notch in the rotary
valve (d) points to the punch mark on the support body (c)
and the cotter pin (i) is inserted and secured again carefully.
5. The float must be able to move up and down
without resistance.
4.3 Installing the control and assembling
1. The complete float control is inserted into the conical
Housing seat with the support body
(8).
Ensure here that the pipe (7) shows
upward.
2. The support body (8) is fixed in bush (10) by screwing with a tightening torque approx. 50 Nm.
3. Check the housing gasket (2) and replace necessary.
4. Assembly of housing as shown in figure 1 and acc. to paragraph 3.
5. Tighten housing bolts
crosswise.
Tighten torque: 70
Nm.
4.4 Care and maintenance, spare parts
In the case of a great risk of dirt accumulation, the housing should be rinsed thoroughly from time to
time, but while depressurized. If necessary, the float control should also be checked according
section 4.2.
In most cases the float control usually does not require special care. Maintenance primarily depends
on the wear resistance of the valve seal. See sections 4.1 and 4.2 in this connection.
Spare parts: Only genuine spare
pa
rts may be used.
Item
Designation
Dimension/DIN
Housing C22.8
Housing 1.4571
2
Housing Seal
195 x 188
Soft iron, grooved
SS profiled graphite
5
Stud bolts + nuts
M16, DIN939/934
A4-70
A4-70
7
Float control
Standard SS
SS 1.4571
8
Support assembly,
rotary valve, pin
Standard SS
SS 1.4571
9
Float wit lever
SS 1.4301 (1.4571)
SS 1.4301 (1.4571)
10
Bush
M 32 x 1,5
SS 1.4571
SS 1.4571
11
Seal for pos. 12
Soft material
Soft material
12
Sight glass
DIN 7081
Borosilicate
Borosilicate
13
Set of hex. bolts
DIN 912
14
Frame
RSt 37-2
SS 1.4571/1.4541
16
Support screw
G 1/4
SS 1.4571/1.4541
SS 1.4571/1.4541
17
Seal
G 1/4
Soft iron
SS profiled graphite
Rev. 02/2017-Di Page 4 of 4 Subject to modification !
7.0 Declaration of conf ormity CE
We declare conformity with Directive 2014/68/EU for the following pressure equipment:
Category 3, fluid group1 ,module B1 +D
The pressure equipment described is a pressure-keeping component in accordance with Article
1, 2.1.4. Applied conformity assessment procedure according to Annex III:
Designated office: Lloyd’s Register Quality Assurance GmbH, Mönkebergstr. 27, D-20095,
Hamburg, Germany, identification no. 0525.
In the case that the equipment is modified without our approval, this declaration shall no longer be
valid.