Risco RWT6CO User manual

CO Detector
Installation Instructions
Model: RWT6CO / RWX6CO

2
Language
Page
3
15
28
42
55
69

3
1. Description
The CO Detector is used for detecting the buildup of Carbon Monoxide. Upon detecting
the CO gas, the unit emits an alarm and notifies the control panel.
Note: This CO detector is designed to detect carbon monoxide gas from any source of combustion.
It is not designed to detect any other gas.
What you should know about Carbon Monoxide
CO cannot be seen, smelled, or tasted and can be fatal. The buildup of CO in the blood is
called the carboxyhemoglobin (COHb) level and interferes with the body’s ability to
supply itself with oxygen. Depending on the concentration, CO can kill in minutes.
The most common sources of CO are malfunctioning gas appliance used for heating and
cooking, vehicles running in an attached garage, blocked chimneys or flues, portable fuel
burning heaters, fireplaces, fuel powered tools and operating a grill in an enclosed space.
Indications of carbon monoxide poisoning include symptoms similar to the flu, but with
no fever. Other symptoms include dizziness, fatigue, weakness, headache, nausea,
vomiting, sleepiness and confusion. Everyone is susceptible to the danger of CO, but
experts agree that unborn babies, small children, pregnant women, senior citizens and
people with heart or respiratory problems are at the highest risk for serious injury or
death. Every year a qualified technician should inspect and clean your heating system,
vents, chimney, and flues.
The following symptoms are related to CARBON MONOXIDE POISONING and should
be discussed with ALL members of the household:
•Mild Exposure: Slight headache, nausea, vomiting, fatigue (often described as "Flu-
like" symptoms).
•Medium Exposure: Severe throbbing headache, drowsiness, fast heart rate.
•Extreme Exposure: Unconsciousness, cardiorespiratory failure, death.

4
The above levels of exposure relate to healthy adults. Levels differ for those at high risk.
Exposure to high levels of carbon monoxide can be fatal or cause permanent damage and
disabilities. Many cases of reported carbon monoxide poisoning indicate that while
victims are aware they are not well, they become so disoriented they are unable to save
themselves by either exiting the building or calling for assistance. Also, young children
and household pets may be the first effected. Familiarization with the effects of each level
is important.
WARNING! Exposure to high levels of carbon monoxide can be fatal or cause permanent
damage and disabilities.
CAUTION:
•This CO detector is designed for indoor use only. DO not expose to rain or moisture.
DO not knock or drop the detector. DO not open or tamper with the alarm as this
could cause malfunction.
•The alarm will not protect against the risk of carbon monoxide poisoning when the
battery has drained.
•Installation of the alarm should not be used as a substitute for proper installation, use
and maintenance of fuel burning appliances including appropriate ventilation and
exhaust systems.

5
2. Installation
Step 1: Selecting the Mounting Location
When choosing your installation locations, make sure you can hear the alarm from all
sleeping areas. If you install only one CO detector in your home, install the alarm near
bedrooms, not in the basement or furnace room. The recommended position for the unit
should be at least 1.8 meters (about 6 feet) above the floor level.
Step 2: Recommended Installation Locations
Figure 1 –Recommended Installation Locations
The following suggestions are intended to help you with the placement and installation
of your CO detector.
•Place out of the reach of children. Under no circumstance should children be allowed
to handle the CO detector.
•Install in a bedroom or hallway located close to the sleeping area. Take special care to
verify the alarm can be heard in sleeping areas.
•It is recommended that a CO detector be installed on each level of a multilevel home.
•Locate 1~3 meter (3.3~10feet) away from all fuel burning appliances.

6
•Placing at eye level allows for optimum monitoring of the red and green indicator
lights.
•Ensure that all vents of the unit are unobstructed.
•Do not install in dead air spaces such as peaks of vaulted ceilings, or gabled roofs.
•Do not install in turbulent air from ceiling fans.
•Do not place near fresh air vents or close to doors and windows that open to the
outside.
•Keep the CO detector away from excessively dusty, dirty, or greasy areas such as
kitchens, garages and furnace rooms. Dust, grease and household chemicals can affect
the sensor.
•Keep out of damp and humid areas such as the bathroom. Avoid spraying aerosols
near the CO detector.
Step 3: Mounting
Figure 2 –Mounting
1. Drill two ф5.0mm holes in the wall; the distance between two holes center should be
52mm (2 inches).
2. Insert the two supplied plastic stoppers into the holes until the screw heads are
approximately 5mm from the wall.
3. Test the unit by pressing the TEST/SILENCE button (see Figure 2). Ensure the unit
sound is of the alarm pattern.
4. Hook the unit over the screws and then onto the keyholes in the back of unit.
TEST /
SILENCE
Button

7
3. Using your CO Detector
Start Up
After connecting the battery, all three LEDs light up briefly and the CO detector confirms
start-up with a beep.
After power on, the green LED flashes once per second within 60 seconds indicating
the preheated state. 60 seconds later the green LED flashed every 40 seconds indicating
that the unit is functioning properly.
Registering the CO Detector to the System’s Receiver
For the CO Detector to identify itself to the system’s receiver, perform the registration
either by entering the CO Detector’s 11-digit serial code number or by the following RF
allocation steps.
Note: In case of performing device registering (enrollment) by entering the detector’s 11-digit
serial number, make sure to use the serial number of the Main Unit (by scanning the QR sticker
on the package via the HandyApp application).
1. Set the system to Learn Mode.
2. Remove the batteries from the battery compartment and then reinsert the batteries,
paying attention to the polarity.
3. Wait until the system receiver indicates that it has received the allocation message.
LED Indication
LED
State
Description
Green
Flash every 40 sec.
Normal condition
Yellow
Steady
Trouble
Red
Steady
CO detector status
Fault Warning Silence
When the alarm sounds in the fault warning state, pressing the TEST/SILENCE button
will cause the detector to enter silence status for about 9 hours. The FAULT indicator
(yellow LED) will flash repeatedly.

8
Low Battery Voltage Warning
If the alarm beeps once every 40 seconds, the FAULT indictor (yellow LED) will flash.
This indicates low battery state.
Notes:
•You need to replace the batteries immediately when the alarm enters this state.
•The alarm will not protect against the risk of carbon monoxide poisoning when the battery has
drained.
•Low battery voltage warning sounds (refer to “4. Battery Replacement”).
Low Battery Voltage Warning Silence
When the alarm sounds in the low battery warning state, pressing the TEST/SILENCE
button will result in the alarm being silenced for about 9 hours. The FAULT indicator
(yellow LED) will flash repeatedly.
Note: Replace the battery to ensure normal working condition.
End of Life Warning
If the alarm beeps 3 times every 40 seconds and the FAULT indicator (yellow LED)
flashes, this indicates end of life of the CO detector. In this case, replace the CO detector.
End of Life Warning Silence
When the alarm is in the end-of-life warning, pressing the TEST/SILENCE button will
cause the detector to enter silence status for about 9 hours. The FAULT indicator (yellow
LED) will flash repeatedly.
CO detector Warning
When the alarm detects a dangerous level of CO, the alarm will emit a loud alarm pattern
of 4 short beeps followed by 5 seconds of silence. This cycle repeats itself as long as a
dangerous CO condition exists. The red alarm LED will flash in the same pattern.
This signal will repeat until the alarm resets after dissipation of CO.
Sensitivity Setting: Conforms to EN 50291-1:2018 standard.

9
30PPM
No alarm for 120 minutes
50PPM
Between 60 to 90 minutes
100PPM
Between 10 to 40 minutes
300PPM
Less than 3 minutes
Note: Refer to “5. Actions to Take When Alarm Sounds” when you hear the sound of the CO
detector warning.
CO Detector Warning Silence
When the device is in CO detector mode, pressing the TEST/SILENCE button will pause
the detector’s alarm sound for about 10 minutes. The ALARM indictor (red) will keep
flashing to indicate the detector is entering the CO detector silence mode.
Notes:
•The audible alarm signal will reactivate about 10 minutes from the time the TEST/SILENCE
button is operated where the concentration of CO surrounding the alarm remains at 50 PPM or
greater.
•The audible alarm signal cannot be silenced if the alarm is at concentration above 200 PPM.
•The alarm silencing activation is once throughout a CO detector period.
WARNING! Before you enable the CO detector warning silence feature, you
should assume that the alarm is due to dangerous levels of carbon monoxide
and the residence should be evacuated.
Human Alarm Sounds
If the alarm enters the CO detector warning status, the alarm will begin sounding in a lower
alarm volume (<85dB) for the first 8 sounds, then issuing a normal alarm volume (>85dB).
This is to prevent people from being frightened by the sudden intensity of the alarm sound.

10
Test the unit
To test the alarm, press and hold TEST/SILENCE button (see Figure 2). You should hear
the alarm sound pattern with a corresponding ALARM indicator (red LED) flash and an
alert message is sent to the system’s receiver. The alarm sound patterns will stop when
the TEST/SILENCE button is released.
The test alarm sound pattern includes: 4 short beeps followed by 5 seconds of silence.
Repeat the pattern until you release the TEST/SILENCE button.
Notes:
•After the TEST/SILENCE button is enabled, the alarm sounds and the red alarm light flashes.
This does not indicate that CO is present.
•Test the unit weekly! If at any time your unit does not perform as described, replace it immediately.
4. Battery Replacement
When two beeps with a corresponding FAULT indicator (yellow LED) flash twice every
40 seconds, this indicates low battery. Replace the battery with the specified battery,
(see “7. Technical Specifications“).
To install or replace the battery in unit, please perform the following steps:
1. Take down the unit from the screw heads on the wall.
2. Open battery compartment.
3. Remove the old battery and replace with a new battery.
4. Check the alarm; the green LED should flash once a second in the first 60 seconds. If
not, remove the battery and put back again.
5. Close the battery compartment.
6. Hook the alarm body over the screw heads onto the keyholes in the back of the unit.
7. Perform a test alarm using the TEST/SILENCE button. If the testing alarm is ok, this
indicates that the product is operating normally.
WARNING! Use only the battery specified. Use of different battery may have
a detrimental effect on the CO detector. A good safety measure is to replace the
battery at least once a year.
Note: Reinstall immediately after cleaning and then test unit using the TEST/SILENCE button!

11
5. Actions to Take When Alarm Sounds
WARNING!
Actuation of your CO detector indicates the presence of Carbon Monoxide
(CO) which can KILL YOU.
Action of this device indicates the presence of dangerous levels of CO! CO can
be fatal!
If the alarm sounds:
1. Press the TEST/SILENCE button (see Figure 2).
2. Shut down furnaces and gas supply.
3. Immediately move outdoors to fresh air or by an open door/window. Check that all
persons in the area are accounted for. Do not reenter the premises nor move away
from the open door/window until the emergency services responders have arrived,
the premises have been aired out, and your alarm remains in its normal condition.
4. If your alarm reactivates within a 24-hour period, repeat steps 1-3 and call a qualified
technician to investigate for sources of CO from fuel burning equipment and
appliances and for proper operation of this equipment.
If problems are identified, the equipment should be immediately serviced
Note: Make sure that motor vehicles are not or have not been operating in an adjacent garage to
the residence.

12
6. Maintenance
To keep your CO detector in good working order, please follow these simple steps:
•Verify operation of the unit's alarm sound and indicators by pressing the
TEST/SILENCE button once a week.
•Remove the unit from the wall and clean the alarm cover and vents with a soft brush
attachment once a month to remove dust and dirt.
•Never use detergents or other solvents to clean the unit.
•Avoid spraying air fresheners, hair spray, or other aerosols near the CO detector.
•Do not paint the unit. Paint will seal the vents and interfere with the sensor's ability to
detect CO. Never attempt to disassemble the unit or clean inside. This action will void
your warranty.
•As soon as possible, place the CO detector back in its proper location to assure
continuous protection from carbon monoxide poisoning.
•When household cleaning supplies or similar contaminants are used, the area should
be ventilated.
WARNING:
The following substances can affect the sensor and may cause false actions:
methane, propane, isobutene, isopropanol, ethylene, benzene, toluene, ethyl
acetate, hydrogen sulfide, sulfur dioxides, alcohol-based products, paints,
thinner, solvents, adhesives, hair sprays, aftershaves, perfumes and some
cleaning agents.
Your CO detector will not be operational and will not monitor for CO levels
without battery.
This apparatus is designed to protect individuals from the acute effects of
carbon monoxide exposure. It will not fully safeguard individuals with
specific medical conditions. If in doubt consult a medical practitioner.

13
7. Technical Specifications
Parameter
Description
Power Supply
3V DC (2pcs alkaline battery)
Battery Type
AA 1.5V
Current Consumption
<20µA standby (average)
Power Output
10mW Max.
Product Life
10 years after manufacture
Sensor Type
Electrochemical
Model Type
B
Alarm Current
<30mA (average)
Operating Temperature,
Ambient Condition
-10℃-+40℃(14◦F -+104◦F), 30~95% non-condensing
Storage Temperature,
Ambient Condition
-20℃-+50℃(-4◦F -+122◦F), 10~95% non-condensing
Alarm Sound
≥85DB at 3m @3.2±0.5KHz pulsing alarm
CO detector Silence
10 min. approx.
Other Warning Silence
9 hrs approx.
Detection Range
40 m2 max. indoors
Frequency
433.92MHz, 868.65MHz
8. Ordering Information
Model
Description
RWT6CO40000B
1-Way WL CO DETECTOR 433MHz
RWT6CO80000B
1-Way WL CO DETECTOR 868MHz
RWX6CO40000A
2-Way WL CO DETECTOR 433MHz
RWX6CO80000A
2-Way WL CO DETECTOR 868MHz

14
UKCA and CE RED Compliance Statement
Hereby, RISCO Group declares that this equipment is in compliance with the essential
requirements of the UKCA Radio Equipment Regulations 2017 and CE Directive
2014/53/EU.
For the UKCA and CE Declaration of Conformity please refer to our website:
www.riscogroup.com

15
1. Description
Le détecteur de CO permet de détecter l’accumulation de monoxyde de carbone.
Lorsqu’elle détecte la présence de monoxyde de carbone, l’unité déclenche une alarme
et en informe la centrale.
Remarque : ce détecteur de CO est conçu pour détecter le monoxyde de carbone provenant de
toute source de combustion. Il n’est pas conçu pour détecter d’autres gaz.
Ce que vous devez savoir sur le monoxyde de carbone (CO)
Invisible, inodore et insipide, le monoxyde de carbone est un gaz mortel.
L’accumulation de CO dans le sang, appelée taux de carboxyhémoglobine (COHb),
empêche l’organisme de s’approvisionner en oxygène. Selon la concentration, le CO
peut tuer en quelques minutes.
Des émanations de CO peuvent notamment se produire dans les cas suivants : mauvais
fonctionnement des appareils à gaz utilisés pour le chauffage et la cuisson, véhicules
fonctionnant dans un garage attenant, cheminées ou conduits obstrués, appareils de
chauffage au fioul, cheminées, outils à combustible et utilisation d’un gril dans un
espace clos.
Une intoxication au monoxyde de carbone se traduit notamment par des symptômes
similaires à ceux de la grippe, mais sans fièvre. Il existe également d’autres symptômes
comme les vertiges, la fatigue, l’atonie, les maux de tête, les nausées, les vomissements,
la somnolence et la confusion. Bien que nous soyons tous exposés aux dangers du
monoxyde de carbone, les experts s’accordent à dire que les personnes les plus
vulnérables sont les fœtus, les jeunes enfants, les femmes enceintes, les personnes âgées
et les personnes souffrant de problèmes cardiaques ou respiratoires. Chaque année, un
technicien qualifié devrait inspecter et nettoyer votre système de chauffage, vos évents,
votre cheminée et vos conduits.
Les symptômes suivants sont liés à l’intoxication au MONOXYDE DE CARBONE et
doivent être connus de TOUS les membres de la famille :

16
•Exposition légère : légers maux de tête, nausées, vomissements, fatigue (souvent
décrits comme des symptômes similaires à ceux de la grippe).
•Exposition moyenne : maux de tête violents et lancinants, somnolence, arythmie.
•Exposition extrême : perte de conscience, défaillance cardiorespiratoire, décès.
Les niveaux d’exposition ci-dessus concernent des adultes en bonne santé. Ils peuvent
différer pour les personnes à haut risque. L’exposition à des niveaux élevés de
monoxyde de carbone peut être mortelle ou entraîner des lésions et des handicaps
permanents. De nombreux cas d’intoxication au monoxyde de carbone signalés
indiquent que, bien que les victimes soient conscientes de ne pas se sentir bien, elles
sont tellement désorientées qu’elles sont incapables de quitter le bâtiment ou de
demander de l’aide. De plus, les jeunes enfants et les animaux domestiques peuvent
être les premiers touchés. Il est donc important de se familiariser avec les effets de
chaque niveau d’exposition.
AVERTISSEMENT ! L’exposition à des niveaux élevés de monoxyde de carbone peut
être mortelle ou entraîner des lésions et des handicaps permanents.
ATTENTION :
•Ce détecteur de CO est conçu pour une utilisation en intérieur uniquement. Ne
l’exposez pas à la pluie ou à l’humidité. Veillez à NE PAS lui faire subir de choc et à
ne pas le faire tomber. Veillez à ne pas ouvrir ou saboter le détecteur, sous peine
d’entraîner un dysfonctionnement.
•Le détecteur ne protège pas contre le risque d’intoxication au monoxyde de carbone
si les piles sont épuisées.
•L’installation du détecteur ne doit pas se substituer à l’installation, l’utilisation et
l’entretien corrects des appareils à combustion, y compris les systèmes de
ventilation et d’évacuation appropriés.

17
2. Installation
Étape 1 : Sélection de l’emplacement d’installation
Lorsque vous choisissez votre emplacement d’installation, assurez-vous de pouvoir
entendre l’alarme depuis toutes les chambres. Si vous n’installez qu’un seul détecteur
de CO chez vous, installez-le près des chambres à coucher, et non au sous-sol ou dans
la chaufferie. Il est recommandé de placer le détecteur à au moins 1,8 m au-dessus du
niveau du sol.
Étape 2 : Emplacements d’installation recommandés
Figure 1 –Emplacements d’installation recommandés
Les suggestions suivantes vous aident à placer et à installer votre détecteur de CO.
•Placez-le hors de portée des enfants. Les enfants ne doivent en aucun cas être
autorisés à manipuler le détecteur de CO.
•Installez le détecteur dans une chambre ou un couloir situé à proximité des
chambres à coucher. Veillez tout particulièrement à pouvoir entendre l’alarme
depuis les chambres à coucher.

18
•Il est recommandé d’installer un détecteur de CO à chaque étage si votre logement
comporte plusieurs étages.
•Placez le détecteur à une distance de 1 à 3 mètres de tous les appareils de combustion.
•Placé à hauteur des yeux, il permet une surveillance optimale des voyants rouge et vert.
•Assurez-vous que tous les évents de l’unité ne sont pas obstrués.
•N’installez pas le détecteur dans des espaces sans circulation d’air, notamment au
sommet de plafonds voûtés ou sur des toits à pignon.
•N’installez pas le détecteur à proximité de ventilateurs de plafond.
•Ne le placez pas à proximité de bouches d’aération ou près de portes et de fenêtres
qui donnent sur l’extérieur.
•Tenez le détecteur de CO à l’écart des zones excessivement poussiéreuses ou sales
ou exposées à la graisse, notamment les cuisines, les garages et les chaufferies. La
poussière, la graisse et les produits chimiques ménagers peuvent avoir une
incidence négative sur le capteur.
•Tenez le détecteur à l’écart des endroits humides, comme la salle de bains. Évitez de
pulvériser des aérosols à proximité du détecteur de CO.
Étape 3 : Montage
Figure 2 –Montage
1. Pratiquez deux trous de 5,0 mm de diamètre dans le mur ; la distance
entre le centre des deux trous doit être de 52 mm.
Bouton
TEST /
SILENCE

19
2. Insérez les deux chevilles en plastique fournies dans les trous jusqu’à
ce que les têtes de vis soient à environ 5 mm du mur.
3. Testez l’unité en appuyant sur le bouton TEST/SILENCE (reportez-vous
à la Figure 2). Assurez-vous que le son émis correspond au mode
d’alarme.
4. Accrochez l’unité aux vis, puis aux trous à l’arrière de l’unité.

20
3. Utilisation de votre détecteur de CO
Démarrage
Après avoir connecté la batterie, les trois voyants s’allument brièvement et le détecteur
de CO confirme le démarrage par un signal sonore.
Après la mise sous tension, le voyant vert clignote une fois toutes les secondes pendant
60 secondes, indiquant l’état de préchauffage. 60 secondes plus tard, le voyant vert
clignote toutes les 40 secondes, indiquant que l’unité fonctionne correctement.
Enregistrement du détecteur de CO sur le récepteur du
système
Pour que le détecteur de CO s’identifie auprès du récepteur du système, enregistrez-le
soit en saisissant le numéro de série à 11 chiffres du détecteur de CO, soit en suivant les
étapes d’attribution RF suivantes.
Remarque : si vous procédez à l’enregistrement (l’inscription) de l’appareil en saisissant le
numéro de série à 11 chiffres du détecteur, veillez à utiliser le numéro de série de l’unité
principale (en scannant l’autocollant QR sur l’emballage via l’application HandyApp).
1. Mettez le système en mode d’apprentissage.
2. Retirez les piles du compartiment à piles, puis remettez-les en place en respectant la
polarité.
3. Attendez que le récepteur du système indique qu’il a reçu le message d’attribution.
Indication du voyant
Voyant
État
Description
Vert
Clignote toutes les 40 secondes
Condition normale
Jaune
Stable
Incidents
Rouge
Stable
État de l’alarme de CO
This manual suits for next models
5
Table of contents
Languages:
Popular Gas Detector manuals by other brands

Sensitron
Sensitron SMART3 NC instruction manual

DALEMANS
DALEMANS DAX 3F-I Installation, operating and maintenance instructions

Duran Electronica
Duran Electronica FIDEGAS S/3-2 quick guide

Tecnogas
Tecnogas 12030 Operation manual

LEGRAND
LEGRAND Tynetec Aidcall ZXT486 instructions

Honeywell
Honeywell FS20X Series user manual